Kaltra Lambda CW/CWU Chilled Water Precision Air Conditioners
Original title Lambda CW/CWU technical brochure
Kaltra
Kaltra Lambda CW/CWU is a 40-135 kW family of 24 chilled water precision air conditioners with microchannel coils; CW models give 39.6-108.3 kW at 7/12°C water with EER up to 84.2.
On this page
Overview
Kaltra's Lambda CW/CWU brochure presents a family of 24 chilled water precision air conditioners for mission-critical use, in three performance grades (G, S, H) with bottom or underfloor air discharge. Data centres, telecom facilities and clean rooms are the targets. The units carry two independent microchannel coils, which the brochure says gives high reliability.
The heat exchangers are all-aluminium microchannel: flat tubes, low pressure drop headers and a doubled-area A-shaped design keep airside pressure drop very low. Kaltra states up to 40% higher efficiency than old fin-and-tube designs, about 50% less weight and a smaller water volume. EC-motor radial fans and a modular design with 30% fewer parts are also highlighted.
The technical table lists CW models (sizes 09, 12, 15, 18 and grades G, S, H) at two conditions: 7/12°C water with 24°C air, and 15/20°C water with 35°C air. Grade G gives 39.6-84.7 kW at 7/12°C, grade S 43.3-101.3 kW and grade H 46.9-108.3 kW; at 15/20°C the values run from 47.5 to 130.2 kW. Power input in the table is fan power.
In the water circuit a smart balancing system measures pressure drop on the return and bypass lines and removes manual balancing in variable-flow systems through two-way valves; a three-way valve is optional for constant flow. Control supports continuous temperature, optional on-demand airflow, or constant pressure difference between cold and hot aisle strategies.
Key points
- At 7/12°C water and 24°C air, total capacity is CW09G 39.6, CW12G 49.7, CW15G 67.1, CW18G 84.7 kW; grade H gives 46.9, 59.0, 83.6 and 108.3 kW.
- At 15/20°C water and 35°C air, the same models give 47.5-101.3 kW (G), 51.9-121.5 kW (S) and 56.3-130.2 kW (H).
- EER is up to 84.2; the group average is 59.6 for 7/12°C water.
- Power input runs from 0.58 kW (CW09G) to 2.64 kW (CW18H).
- Airflow is 9000 to 25500 m³/h; external static pressure 20 Pa; 1 or 2 fans.
- Dimensions: width 985, 1285, 1585, 1885 mm; depth 920 mm; height 2050 mm.
- Water flow is 6.8-22.2 m³/h with 17.7-25.9 kPa waterside pressure drop; two microchannel heat exchangers.
- Microchannel coils give up to 40% higher efficiency and about 50% lower weight.
Using it in design
- Read capacity from the 7/12°C and 24°C, or 15/20°C and 35°C, row that matches the project; the same model gives different capacity at each condition.
- The table's EER is defined within the table and rests on fan power; verify total unit input separately for energy calculations.
- Compare grades G, S and H at equal width: grade H gives roughly 18-28% more capacity than G but draws more power.
- Specify two-way valves with automatic balancing for variable flow and the three-way valve option for constant flow.
- Add the waterside pressure drop (about 18-26 kPa) to pump and pipework calculations.
Who should read it
Data-centre mechanical designers selecting chilled water precision air conditioners and engineers weighing microchannel against conventional CRAH units.
Document contents
- Heat exchangers
- Controls
- Frame and assembly
- Highly efficient radial fans
- Water circuit
- Technical specifications (CW)
- Package, options and accessories
- Technical specifications (CWU)
- Model code
Publication details
- Authors
- Kaltra
- Publisher
- Kaltra
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Kaltra Lambda CW/CWU technical brochure. Kaltra. https://www.kaltra.com/wp-content/uploads/2020/01/SB_Lambda_CW-CWU_Ver.2.0_EN.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.