Kaltra Lambda In-Row Gen.II technical specifications, PDF p.6
Kaltra
Kaltra Lambda In-Row Gen.II is a 600 mm wide chilled water in-row cooler rated 141.1 kW in the normal fan layout and 100.3 kW in the N+1 layout (15/21°C water, 40°C air).
On this page
Overview
Kaltra's Lambda In-Row brochure presents a 140 kW class chilled water in-row cooling solution with microchannel evaporators. It compares cooling density per floor area against competing in-row and CRAC units and claims the number of installed units for the same load can drop by more than fourfold; the density is stated for 15/21°C water and 40°C, 25% relative humidity inlet air.
The technical table gives two fan operating layouts on separate rows: Gen.II (3+0 fans, 24000 m³/h) and Gen.II N+1 (2+1 fans, 16000 m³/h). The normal layout yields 141.1 kW at 15/21°C water and 40°C air while the N+1 layout falls to 100.3 kW. At 12/18°C water and 35°C air the values are 129.2 and 93.6 kW. The duty capacities of the two configurations cannot be treated as equal.
Fan redundancy relies on hot-swappable fan assemblies; if one fan goes offline the others raise speed. EC fans are said to cut power use by up to 20%. In the water circuit a smart balancing system measures pressure drop on the return and bypass lines and adjusts two-way valves to hold coil flow in variable-flow systems, and dew point control prevents condensation.
Coupled to a chiller with a free-cooling circuit, the unit can run up to 98% of the time in free-cooling mode (12/18°C water, Nuremberg climate data). Raising cooling air temperature up to 27°C increases free-cooling opportunities. LAN networking of up to 16 units, temperature monitoring of up to 16 racks and Android-based remote monitoring are offered.
Key points
- Gen.II (3+0 fans) at 15/21°C water, 40°C and 25% humidity air: 141.1 kW, EER 41.3, airflow 24000 m³/h, fan power 3.42 kW, waterside pressure drop 10.5 kPa.
- Gen.II N+1 (2+1 fans) at the same condition: 100.3 kW, EER 50.9, 16000 m³/h, 1.97 kW, 7.5 kPa.
- At 12/18°C water and 35°C air, Gen.II gives 129.2 kW (EER 37.8) and N+1 gives 93.6 kW (EER 47.5).
- Size is 600×1295×2000 mm (W×D×H); external static pressure value is 20 Pa.
- Up to 98% free-cooling time (12/18°C water, Nuremberg).
- EC fans cut power consumption by up to 20%; the hot-swappable fan assembly is an option.
- Networking of up to 16 units and monitoring of up to 16 racks.
- Kaltra states the number of units needed for the same load can fall by more than four times.
Using it in design
- Cover the design load from the N+1 (2+1) row, not the normal (3+0) row, when redundancy is required; capacity drops by about 29 kW.
- Match the water and air condition (15/21°C and 40°C, or 12/18°C and 35°C) to the project's real condition.
- The EER column uses the table's own numeric definition; confirm that definition with the manufacturer before using it in energy calculations.
- For variable-flow systems, specify the two-way valve and the bypass balancing valve.
- Run an hours analysis for free-cooling time with your own climate data, chiller and water temperatures.
Who should read it
Data-centre mechanical designers selecting chilled water in-row cooling and operations engineers relating fan redundancy to capacity.
Document contents
- Small unit that outperforms big CRACs
- Improve PUE
- Microchannel evaporators
- Easy startup
- Freecooling operation
- Controls
- Air distribution
- EC fans
- Rack monitoring
- Dew point control
- Cooling coils and air filtration
- Water circuit
- Remote control and networked operation
- Technical specifications
- Package, options and accessories
- Hot-swappable fans
Publication details
- Authors
- Kaltra
- Publisher
- Kaltra
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Kaltra Kaltra Lambda In-Row Gen.II technical specifications, PDF p.6. Kaltra. https://www.kaltra.com/wp-content/uploads/2020/01/SB_In-Row-II_1.0_EN.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.