Kelvion Hybrid Cooler (factsheet)

Kelvion

Kelvion Hybrid Cooler is a heat-rejection unit that switches between dry and wet modes and uses a deluge water film to raise capacity; it covers 800-3,400 kW with 10-18 EC fans.

On this page

Overview

This July 2023 Kelvion factsheet presents the Hybrid Cooler, positioned between cooling towers and adiabatic systems. The unit uses water to enhance the cooling effect and is optimised for both dry and wet operation. Applications are data centres, HVAC and refrigeration.

The heat exchanger is a four-row coil with a special anticorrosion E-coating and Kelvion's high-efficiency fin design. In wet mode, deluge water forms a film across the coil fins and acts as an additional heat-transfer medium. Cooling is therefore still achievable when ambient temperature exceeds the process temperature. Fans are 910 mm EC fans, from 10 to 18 per unit.

On the control side, a conductivity sensor optimises water consumption, a highly efficient submersible pump is used and advanced level sensors manage water balancing. Control is Modbus, with BACnet optional and Profibus and Profinet on request. In the table, models LV-LA 205 to 209 run from 6.7 to 11.5 m in length and 5,700 to 10,080 kg empty weight.

The factsheet is a short catalogue page. It gives no data-centre temperature level, water consumption or capacity rating condition. The entering and leaving water conditions behind the capacity range should be obtained from the manufacturer.

Key points

  1. Capacity range 800-3,400 kW.
  2. Fans: 910 mm EC type, 10, 12, 14, 16 or 18 per unit; Modbus control.
  3. Coil: four rows, E-coating and high-efficiency fin design.
  4. In wet mode, deluge water forms a film on the fins; cooling works even when ambient is above process temperature.
  5. A conductivity sensor optimises water consumption.
  6. Controls: Modbus; optional BACnet; Profibus and Profinet on request.
  7. LV-LA 205: 6.7 x 3.4 x 2.7 m, 5,700 kg empty, 7,076 kg operational.
  8. LV-LA 209: 11.5 x 3.4 x 2.7 m, 10,080 kg empty, 12,327 kg operational.

Using it in design

  • Use local wet-bulb data to estimate the dry-to-wet switching hours and annual water consumption, which the sheet does not give.
  • Check roof or ground bearing capacity against operating weights of 7,076-12,327 kg.
  • State the Modbus and BACnet options explicitly in the BMS integration specification.
  • Add water treatment, conductivity and drain management for wet mode to the maintenance programme.
  • Obtain in writing the entering and leaving water conditions behind the capacity range.

Who should read it

Mechanical designers comparing dry coolers, adiabatic and hybrid heat-rejection options for data centres.

Document contents

  1. Hybrid Cooler overview
  2. Fans and applications
  3. Heat exchanger
  4. Hybrid function
  5. Dimensions and weight table

Publication details

Authors
Kelvion
Publisher
Kelvion
Year
2023
Document number
Version 01 07/23
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

© Kelvion, All rights reserved

Citation

Kelvion (2023). Kelvion Hybrid Cooler (factsheet). Kelvion. Version 01 07/23. https://d2xjeen3zaup4u.cloudfront.net/asset/767398133948/document_15qhbgvu594lb6f6ocjlqiv560/SPE_Hybrid_EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.