Lande Power Distribution Unit: Configuration and Mounting Guide
Lande
Lande's PDU catalogue describes a modular part-number system for 19-inch 1U/2U housings that selects protection, sockets, blanking plates and input plug separately, with a worked 381.6 mm module-space calculation.
On this page
Overview
Lande's English PDU catalogue covers a range from basic 19-inch socket strips with a 16 A breaker to monitored vertical PDUs of up to 8000 W. It includes basic PDUs (Schuko, French UTE, BS1363 and IEC C13 sockets; with on/off switch, breaker, surge protection or ammeter), vertical monitored and managed PDUs, and a configurable PDU section. The configurable section is the subject of this page.
The configuration key reads LN-PRZ-[1U/2U]-protection-sockets-blanking plate-plug. The protection module (on/off switch, ammeter display and so on, joined with '+'), the socket types (Schuko SC, French UTE, BS1363, C13, C19, 2C13, 4C19), the half- or full-module blanking plates (N and O) that close the remaining space, and the input plug (C14, C20, UK, Schuko, 16 A and 32 A single- and three-phase industrial plugs, letters P to Y) are chosen separately. The standard power cable is 3 m.
Because the aluminium 19-inch profile holds a fixed full-module blanking plate (O) over the cable entry, the configurable space in 1U and 2U housings is 381.6 mm. In the catalogue example, 6 Schuko sockets (6 x 42.4 mm = 254.4 mm), one 2C13 block (63.6 mm), one on/off switch (42.4 mm) and one half-module blank (21.2 mm) add up to exactly 381.6 mm and fit a standard 1U.
Users may build their own configuration, but Lande reviews and approves the technical compatibility and quotes only if the review is positive. Configurations can also be made in Lande's online configurator. The catalogue also shows the modular 19-inch mounting bracket and its 20 bracket assembly variations. The document is a catalogue and gives no short-circuit withstand, detailed derating or test data.
Key points
- Configurable PDUs use a 438 mm wide 19-inch aluminium profile in 1U or 2U.
- A fixed full-module blanking plate covers the cable entry; configurable space left is 381.6 mm.
- Module widths: Schuko socket 42.4 mm, 2C13 block 63.6 mm, on/off switch 42.4 mm, half blank 21.2 mm.
- Input plug options: C14 (max 10 A), C20 (16 A), UK (13 A), Schuko (16 A), IEC 60309 16 A and 32 A single- and three-phase.
- Standard power cable is 3 m.
- Basic PDU examples carry a 16 A breaker with 4000 W (Schuko and C13) and 3250 W (BS1363).
- Monitored vertical PDU example: 24 outlets (20 x C13 + 4 x C19), two 16 A breakers, 8000 W, 32 A IEC 60309 plug, daisy chain of one master and four slaves.
- The IZP series meters total energy, voltage, current, power, power factor and temperature/humidity; the YNP series adds per-outlet current, power, energy, threshold setting and switching.
- Custom configurations pass Lande's technical compatibility review before quotation.
- The 19-inch bracket has 20 assembly variations.
Using it in design
- For a rack PDU, add up the widths of the socket and protection modules against the 381.6 mm limit and fill any surplus with blanking plates.
- Select the plug by feeder current: C14 up to 10 A, C20 and Schuko 16 A, industrial plugs 16 or 32 A.
- Where per-rack load visibility is needed, choose an ammeter or monitored series such as IZP or YNP; require YNP for outlet-level metering and switching.
- Plan custom configurations with the Lande compatibility review included in the quotation time.
- Separate the 36U, 42U, 45U and 47U vertical PDU options by rack height and state the bracket assembly variation in the specification.
Who should read it
IT infrastructure designers defining in-rack power distribution and electrical engineers writing PDU specifications.
Document contents
- Basic Power Distribution Units (PDU)
- Vertical PDU: Metered, Monitoring and Managed Intelligent
- Configurated PDU: PDU Components
- Part Number Sequence and Explanation
- PDU 19-inch Mounting Bracket Modularity and Options of Assembly
Publication details
- Authors
- Lande
- Publisher
- Lande
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Lande Lande Power Distribution Unit: Configuration and Mounting Guide. Lande. https://lande.com.tr/uploads/catalog/_Lande-PDU-eng-catalogue.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.