CDU-1MW Coolant Distribution Unit

Original title CDU-1MW Coolant Distribution Unit: Universal direct-to-chip liquid cooling solution delivering 1,350 kW

LiquidStack · LiquidStack (a Trane Technologies company)

A LiquidStack data sheet (April 2026) stating that the CDU-1MW delivers 1,350 kW at 13 °C TCS ΔT and 4 °C approach, 1,004 kW at 10 °C ΔT, with 1,500 lpm maximum flow and a 10-45 °C facility water range.

On this page

Overview

The document is the product sheet of a CDU configurable for direct-to-chip (DTC) cooling, in row-style dimensions (900 mm wide, 1,242 mm deep, 2,200 mm high). The unit is designed for elevated operating water temperatures, narrow approach temperatures and higher differential pressure, and is positioned for new and retrofit data centres.

The performance table gives three TCS (technology cooling system) ΔT points: 1,004 kW at 10 °C, 1,202 kW at 12 °C and 1,350 kW at 13 °C (at 4 °C approach temperature difference); maximum TCS flow is 1,500 lpm in all three and the glycol rating is PG 25. The heat dissipation ratio is 1.50, 1.25 and 1.15 lpm/kW respectively.

Hardware includes dual hot-swappable VSD pumps, a 316 stainless steel plate heat exchanger, an integrated ATS with controller supercapacitor, a 2-way E-PICV or 3-way control valve, dual 25 micron filtration and a PN16 static pressure rating. Communication is MODBUS TCP/IP, RESTful API, BACnet IP and SNMP; the 7-inch interface shows a live P&ID view and environmental monitoring with dew point control.

The facility water (FWS) range is 10-45 °C, power input 380-480 VAC three-phase, consumption 23 kW (11 kW per pump), TCS volume 78.92 L, FWS volume 119.24 L, weight 911 kg dry and 1,165 kg operating, with noise below 68 dBA at 3 m. The manufacturer claims 36% less cooling energy, 48% lower CAPEX versus air cooling, 62% less white space and a nominal 25% TCO improvement over 20 years; these are manufacturer claims.

Key points

  1. Cooling capacity at 4 °C approach: 1,004 kW (ΔT 10 °C), 1,202 kW (12 °C), 1,350 kW (13 °C).
  2. Maximum TCS flow is 1,500 lpm; glycol rating PG 25; heat dissipation ratio 1.50 / 1.25 / 1.15 lpm/kW.
  3. FWS water temperature range is 10-45 °C.
  4. Dual hot-swappable VSD pumps; power consumption 23 kW (11 kW per pump).
  5. 316 stainless steel plate heat exchanger; dual 25 micron filtration; PN16 static pressure.
  6. Dimensions 900 x 1,242 x 2,200 mm; dry weight 911 kg, operating weight 1,165 kg.
  7. Communication: MODBUS TCP/IP, RESTful API, BACnet IP, SNMP; temperature, pressure and flow sensors across TCS and FWS loops.
  8. Manufacturer claims: 36% less cooling energy, 48% lower CAPEX, 62% less white space, 25% TCO improvement over 20 years.

Using it in design

  • Read CDU capacity against design TCS ΔT and approach: at 10 °C ΔT it falls to 1,004 kW.
  • Check flow against the heat dissipation ratio (1.15-1.50 lpm/kW) and size headers for 1,500 lpm.
  • Compare the FWS side with the 10-45 °C range; check the upper limit in dry-cooler-led plants.
  • Carry the 380-480 VAC supply, 70 A MOP and integrated ATS into the power schematic; include 23 kW in the PUE calculation.
  • Specify BACnet IP, MODBUS TCP/IP and SNMP points and dew point control for BMS integration.
  • Check the 1,165 kg operating weight and 2,200 mm height against floor loading and layout.

Who should read it

Mechanical and controls engineers selecting and integrating CDUs for direct-to-chip data halls.

Document contents

  1. Universal direct-to-chip liquid cooling solution
  2. Intelligent design and operation
  3. Features and benefits
  4. Accessories and options
  5. Performance information (CDU-1MW TCS performance)
  6. Technical information

Publication details

Authors
LiquidStack (a Trane Technologies company)
Publisher
LiquidStack
Year
2026
Document number
CDU-SLB001-EN
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

© 2026 LiquidStack. All Rights Reserved (p. 3)

Citation

LiquidStack (a Trane Technologies company) (2026). CDU-1MW Coolant Distribution Unit: Universal direct-to-chip liquid cooling solution delivering 1,350 kW. LiquidStack. CDU-SLB001-EN. https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Sales/CDU-SLB001-EN_04202026.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.