Deploying Liquid Cooling in the Data Center: A Guide to High-Density Cooling (1 MW IT load)
Vertiv
A practical guide that walks through converting a 1 MW IT load to hybrid liquid/air cooling, with a worked example giving per-rack and cluster flow and heat split.
On this page
Overview
The guide's main example is 20 racks x 50 kW = 1 MW. Each rack sends 37.5 kW to liquid and 12.5 kW to air, which at cluster scale is 750 kW liquid and 250 kW air. Cold-plate flow is taken as about 1.5 L/min per kW (0.4 gpm/kW), giving 56.25 L/min for a 50 kW rack and 1,125 L/min for the cluster. A reader can thus turn a ratio like "75% liquid" straight into pipe and pump flow.
Technology choice is tied to rack density: passive rear doors suit roughly 5-25 kW racks and active rear doors 50-70 kW, while direct-to-chip is treated for higher densities. The newest AI servers are noted as approaching 6-10 kW TDP each, which explains why 50 kW per rack is becoming ordinary.
CDU placement (in-rack, end-of-row, centralised) and redundancy get separate treatment. Row-level N+1 needs two CDUs, one on duty and one standby, which carries a floor-space cost. The filtration rule is clear: cold plates with 100 micron fin pitch need filtration no coarser than 50 microns. On the electrical side, the paper discusses what changes when 100 x 10 kW racks become 20 x 50 kW racks. The introduction rests on Uptime data: 17% of data centers already use liquid cooling and another 61% are considering it. The guide dates from 2023 and centres on one 1 MW example; at far higher densities (racks above 100 kW) these flows and ratios should be revalidated.
Key points
- Worked example: 20 racks x 50 kW = 1 MW; 37.5 kW/rack to liquid and 12.5 kW to air (750 / 250 kW cluster)
- Cold-plate flow ~1.5 L/min per kW; 56.25 L/min per 50 kW rack; 1,125 L/min cluster
- Passive rear doors suit ~5-25 kW racks; active rear doors 50-70 kW
- Cold plates with 100 micron fin pitch need filtration no coarser than 50 microns
- Row-level N+1 CDU redundancy requires two CDUs (one duty, one standby)
- Newest AI servers approach 6-10 kW TDP per server
- Survey: 17% of data centers already use liquid cooling; another 61% considering it
Using it in design
- Calculation default: DLC flow = 1.5 L/min per kW of liquid-captured heat; to adjust by dT use flow = P/(4.18 x dT) L/s.
- Default secondary-loop filtration to 50 micron.
- In the rear-door catalog apply thresholds: passive <= 25 kW, active <= 70 kW racks.
- For CDU redundancy, show the floor-space cost of row-level N+1 against a centralised CDU gallery.
Who should read it
Facility and mechanical engineers converting an existing air-cooled hall to hybrid liquid cooling.
Related standards
- ASHRAE TC9.9 Liquid Cooling Guidelines
- OCP Advanced Cooling Solutions
Publication details
- Authors
- Vertiv
- Publisher
- Vertiv
- Year
- 2023
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Vertiv (2023). Deploying Liquid Cooling in the Data Center: A Guide to High-Density Cooling (1 MW IT load). Vertiv. https://prod.vertiv.cn/4a9616/globalassets/documents/white-papers/liquid-cooling/vertiv-liquidcooling-wp-en-na-sl-71113-web.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.