Modelling of noise reduction for Datacentre buildings fire protection with inert gas systems
MATEC Web of Conferences / EDP Sciences · Cristina-Maria Mihalache, Cristin Bigan et al.
A 2019 MATEC Web of Conferences paper: noise from INERGEN inert gas discharge has been linked to hard disk drive (HDD) faults in data centres since 2008, and the paper models nozzle placement to reduce the effect.
On this page
Overview
The paper addresses INERGEN clean gas total flooding suppression systems. These are engineered for occupied or unoccupied areas and have proven long-term efficiency, but because INERGEN is stored as a gas it discharges invisibly and can have a more destructive impact than the fire itself. The authors note that since 2008 several reports have been recorded each year of INERGEN discharges leading to faults in hard disks (HDD) in data centres protected by such a solution, due to the noise level produced.
The paper presents an analysis of this problem: detecting the source of hard disk damage and optimising by modelling nozzle placement in the protected space, as a technical solution to avoid these side effects of the extinguishing system.
Key points
- Subject: effect of inert gas (INERGEN) discharge noise on hard disks in data centres.
- Since 2008 reports of INERGEN discharges leading to HDD faults have been recorded each year.
- The gas discharges invisibly and can have a more destructive impact than the fire itself.
- Proposed solution: model and optimise nozzle placement to reduce noise-related damage.
- The work covers identifying the source of HDD damage and nozzle position within the space.
Using it in design
- In halls with HDDs, make inert gas discharge noise a design criterion and evaluate nozzle placement with an acoustic model.
- Consider locating nozzles so they do not point directly at drive racks and verify by measurement or model.
- Weigh the choice of extinguishing agent against noise effects according to the HDD and SSD mix in the hall.
- Plan to monitor hard disk performance during discharge in acceptance testing.
Who should read it
Designers of inert gas suppression systems, operators of storage-heavy data centres, and acoustic and fire engineers.
Publication details
- Authors
- Cristina-Maria Mihalache; Cristin Bigan; Valentin Panduru; Cristian Tsakiris
- Publisher
- MATEC Web of Conferences / EDP Sciences
- Year
- 2019
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Article-specific CC BY 4.0 notice verified on the publisher landing page. PDF download returned 403; only the public abstract is summarized. Round 5/6 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Cristina-Maria Mihalache; Cristin Bigan; Valentin Panduru; Cristian Tsakiris (2019). Modelling of noise reduction for Datacentre buildings fire protection with inert gas systems. MATEC Web of Conferences / EDP Sciences. https://doi.org/10.1051/matecconf/201929012006
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.