A TSception–Transformer–TCN-Based Temperature-Prediction Method for Enclosed Cold-Aisle Data-Center Rooms

Buildings (MDPI AG) · Junwei Yan, Zhixian Yang et al.

A 2026 Buildings (MDPI) paper proposing a hybrid deep-learning model that predicts the maximum temperature of an enclosed cold aisle in a large data center in a hot-summer, warm-winter region with 0.285 °C MAE and 1.13% MAPE.

On this page

Overview

The study notes that in enclosed cold-aisle data-center rooms, hotspot temperature is directly tied to server inlet air safety and air-conditioning performance, so high-accuracy prediction matters for thermal-risk warning and operational optimization. The target is the maximum temperature of one selected cold aisle in a large data center in a hot-summer and warm-winter region.

The proposed model integrates TSception, Transformer and TCN to capture multi-scale local disturbances and cross-period temporal dependencies. Inputs and the historical time window are set through cold-hot separation analysis, cold-aisle temperature-stability comparison, lag analysis between supply air and cold-aisle temperature, and correlation analysis of candidate variables.

For the AB aisle the errors are MAE 0.285 °C, RMSE 0.438 °C, NRMSE 4.76% and MAPE 1.13%, outperforming Persistence, BP, LSTM, XGBoost and several ablation models. Multi-aisle experiments show low errors maintained in independent prediction tasks for other cold aisles. The authors state the method can serve as a reference for hotspot-risk identification and operational optimization of precision air-conditioning.

Key points

  1. The prediction target is the maximum temperature of a selected enclosed cold aisle.
  2. The hybrid model combines TSception, Transformer and TCN.
  3. AB aisle errors: MAE 0.285 °C, RMSE 0.438 °C, NRMSE 4.76%, MAPE 1.13%.
  4. It outperforms Persistence, BP, LSTM, XGBoost and ablation models.
  5. The input window follows from supply-air to cold-aisle lag analysis and correlation analysis.
  6. Low errors are maintained for independent predictions in other cold aisles of the same room.

Using it in design

  • Design sensor placement and data logging in enclosed cold aisles so that supply air and aisle temperature time series are captured as model inputs.
  • Measure the lag between supply air and cold-aisle temperature to set the control and alert time horizon.
  • Before linking hotspot alerts to air-conditioning control, define prediction error (for example MAE in °C) as an acceptance criterion.

Who should read it

Engineers designing monitoring and predictive control for contained cold-aisle rooms, and data analytics teams.

Related standards

  • ASHRAE TC 9.9 thermal guidelines

Publication details

Authors
Junwei Yan; Zhixian Yang; Xuan Zhou; Miao Wang
Publisher
Buildings (MDPI AG)
Year
2026
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

Publisher-deposited Crossref licence metadata: https://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Junwei Yan; Zhixian Yang; Xuan Zhou; Miao Wang (2026). A TSception–Transformer–TCN-Based Temperature-Prediction Method for Enclosed Cold-Aisle Data-Center Rooms. Buildings (MDPI AG). https://doi.org/10.3390/buildings16183580

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.