A TSception–Transformer–TCN-Based Temperature-Prediction Method for Enclosed Cold-Aisle Data-Center Rooms
Buildings (MDPI AG) · Junwei Yan, Zhixian Yang et al.
A 2026 Buildings (MDPI) paper proposing a hybrid deep-learning model that predicts the maximum temperature of an enclosed cold aisle in a large data center in a hot-summer, warm-winter region with 0.285 °C MAE and 1.13% MAPE.
On this page
Overview
The study notes that in enclosed cold-aisle data-center rooms, hotspot temperature is directly tied to server inlet air safety and air-conditioning performance, so high-accuracy prediction matters for thermal-risk warning and operational optimization. The target is the maximum temperature of one selected cold aisle in a large data center in a hot-summer and warm-winter region.
The proposed model integrates TSception, Transformer and TCN to capture multi-scale local disturbances and cross-period temporal dependencies. Inputs and the historical time window are set through cold-hot separation analysis, cold-aisle temperature-stability comparison, lag analysis between supply air and cold-aisle temperature, and correlation analysis of candidate variables.
For the AB aisle the errors are MAE 0.285 °C, RMSE 0.438 °C, NRMSE 4.76% and MAPE 1.13%, outperforming Persistence, BP, LSTM, XGBoost and several ablation models. Multi-aisle experiments show low errors maintained in independent prediction tasks for other cold aisles. The authors state the method can serve as a reference for hotspot-risk identification and operational optimization of precision air-conditioning.
Key points
- The prediction target is the maximum temperature of a selected enclosed cold aisle.
- The hybrid model combines TSception, Transformer and TCN.
- AB aisle errors: MAE 0.285 °C, RMSE 0.438 °C, NRMSE 4.76%, MAPE 1.13%.
- It outperforms Persistence, BP, LSTM, XGBoost and ablation models.
- The input window follows from supply-air to cold-aisle lag analysis and correlation analysis.
- Low errors are maintained for independent predictions in other cold aisles of the same room.
Using it in design
- Design sensor placement and data logging in enclosed cold aisles so that supply air and aisle temperature time series are captured as model inputs.
- Measure the lag between supply air and cold-aisle temperature to set the control and alert time horizon.
- Before linking hotspot alerts to air-conditioning control, define prediction error (for example MAE in °C) as an acceptance criterion.
Who should read it
Engineers designing monitoring and predictive control for contained cold-aisle rooms, and data analytics teams.
Related standards
- ASHRAE TC 9.9 thermal guidelines
Publication details
- Authors
- Junwei Yan; Zhixian Yang; Xuan Zhou; Miao Wang
- Publisher
- Buildings (MDPI AG)
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: https://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Junwei Yan; Zhixian Yang; Xuan Zhou; Miao Wang (2026). A TSception–Transformer–TCN-Based Temperature-Prediction Method for Enclosed Cold-Aisle Data-Center Rooms. Buildings (MDPI AG). https://doi.org/10.3390/buildings16183580
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.