Modelling the Temperature of a Data Centre Cooling System Using Machine Learning Methods
Energies (MDPI AG) · Adam Kula, Daniel Dąbrowski et al.
A 2025 Energies paper comparing TiDE, TSMixer, Random Forest, XGBoost and AutoARIMA for forecasting hot-aisle temperature in an operating data centre from weather, server power and cooling state; TiDE had the lowest error, N-RMSE 0.1270.
On this page
Overview
The paper states that reducing energy consumption in an operating data centre without compromising the working conditions of compute resources requires a temperature model. The model estimates the temperature in the hot corridor of the cooling system from external weather conditions and internal conditions such as server energy consumption and cooling system state. It is published in Energies (MDPI).
The work discusses the dataset creation process and the evaluation of a model forecasting hot-corridor temperature. Two new neural network architectures, Time-Series Dense Encoder (TiDE) and Time-Series Mixer (TSMixer), are compared with Random Forest, XGBoost and AutoARIMA. The lowest prediction error is TiDE at N-RMSE 0.1270, followed by XGBoost at 0.1275. Additional analysis shows that XGBoost tends to underestimate temperature as it approaches higher values, which matters for avoiding safety violations of the compute units.
Key points
- The target is forecasting hot-aisle temperature in an operating data centre.
- Inputs: external weather conditions, server energy consumption and cooling system state.
- Models compared: TiDE, TSMixer, Random Forest, XGBoost and AutoARIMA.
- TiDE gives the lowest error: N-RMSE 0.1270.
- XGBoost is close behind: N-RMSE 0.1275.
- XGBoost tends to underestimate temperature at higher values, a safety concern.
Using it in design
- Add server power, outside air and cooling state as inputs in data collection design for hot-aisle temperature forecasting.
- Evaluate forecast models by the direction of deviation in the high-temperature region (underestimation) as well as average error.
- Define the safety margin before connecting model output to a control loop.
- Retrain and validate the model in your own hall; results rest on one operating data set.
Who should read it
Engineers and researchers developing time-series models for data centre cooling optimisation and temperature forecasting.
Publication details
- Authors
- Adam Kula; Daniel Dąbrowski; Marcin Blachnik; Maciej Sajkowski; Albert Smalcerz; Zygmunt Kamiński
- Publisher
- Energies (MDPI AG)
- Year
- 2025
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: https://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Adam Kula; Daniel Dąbrowski; Marcin Blachnik; Maciej Sajkowski; Albert Smalcerz; Zygmunt Kamiński (2025). Modelling the Temperature of a Data Centre Cooling System Using Machine Learning Methods. Energies (MDPI AG). https://doi.org/10.3390/en18102581
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.