A Comparative Study of a Single-Phase Immersion-Cooled Server with a Pin-Fin Heat Sink for Mitigation of the Flow Bypass Effect

Processes (MDPI AG) · Shau-Wai Cheng, Yong-Dong Zhang et al.

Cheng et al. (Processes 14(13), 2026): an optimised pin-fin heat sink cuts CPU thermal resistance 22.29% against a rectangular-fin sink at 3 LPM and reaches a pPUE of 1.015.

On this page

Overview

Single-phase oil immersion is a promising alternative to air cooling for high-power servers, but the high viscosity of dielectric fluids amplifies the bypass flow around the CPU heat sink through the adjacent RAM channels and degrades thermal performance. A simplified hydraulic-thermal analysis shows that this bypass penalty cannot be eliminated by reducing the fin pitch of a rectangular-fin heat sink alone.

A staggered pin-fin heat sink is therefore proposed, with pin diameter D, longitudinal pitch Sd and transverse pitch St optimised by three-dimensional CFD using PAO-6. The optimum geometry is D = 2.8 mm, St = 6 mm, Sd = 8.45 mm. The heat sink is fabricated and tested in a commercial server at oil inlet temperatures of 30-45°C and flow rates of 3-6 LPM. At 3 LPM, the pin-fin immersion server reduces CPU thermal resistance by 22.29% relative to a rectangular-fin immersion server using the same oil, and by 38.37% relative to an air-cooled server. Partial Power Usage Effectiveness (pPUE) reaches 1.015 against 1.126 for the air-cooled baseline, an 88.09% improvement. The results show that pin-fin geometries effectively mitigate the bypass penalty in single-phase oil immersion cooling.

Key points

  1. Problem: high-viscosity dielectric oil amplifies bypass flow around the CPU heat sink through RAM channels.
  2. Reducing fin pitch of a rectangular-fin sink alone cannot remove the bypass penalty.
  3. Optimum staggered pin-fin geometry: D = 2.8 mm, St = 6 mm, Sd = 8.45 mm (PAO-6, 3D CFD).
  4. Test condition: oil inlet 30-45°C, flow 3-6 LPM, commercial server.
  5. At 3 LPM CPU thermal resistance falls 22.29% against rectangular fins and 38.37% against air cooling.
  6. pPUE is 1.015 against 1.126 for the air-cooled baseline; improvement 88.09%.

Using it in design

  • In immersion-cooled servers evaluate heat sink geometry together with oil viscosity and bypass through neighbouring flow channels; do not rely on smaller fin pitch alone.
  • If a pin-fin heat sink is used, optimise pin diameter and pitches by CFD for the actual fluid (PAO-6).
  • Select oil flow (3-6 LPM) and inlet temperature (30-45°C) together with CPU thermal resistance.
  • In energy comparison calculate pPUE (1.015 against 1.126) on the same boundary as the air-cooled reference.

Who should read it

Thermal engineers and data-centre designers working on immersion-cooled servers and heat sinks.

Publication details

Authors
Shau-Wai Cheng; Yong-Dong Zhang; Li-Hung Chien; Chi-Chuan Wang
Publisher
Processes (MDPI AG)
Year
2026
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

Publisher-deposited Crossref licence metadata: https://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Shau-Wai Cheng; Yong-Dong Zhang; Li-Hung Chien; Chi-Chuan Wang (2026). A Comparative Study of a Single-Phase Immersion-Cooled Server with a Pin-Fin Heat Sink for Mitigation of the Flow Bypass Effect. Processes (MDPI AG). https://doi.org/10.3390/pr14132209

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.