A Comparative Study of a Single-Phase Immersion-Cooled Server with a Pin-Fin Heat Sink for Mitigation of the Flow Bypass Effect
Processes (MDPI AG) · Shau-Wai Cheng, Yong-Dong Zhang et al.
Cheng et al. (Processes 14(13), 2026): an optimised pin-fin heat sink cuts CPU thermal resistance 22.29% against a rectangular-fin sink at 3 LPM and reaches a pPUE of 1.015.
On this page
Overview
Single-phase oil immersion is a promising alternative to air cooling for high-power servers, but the high viscosity of dielectric fluids amplifies the bypass flow around the CPU heat sink through the adjacent RAM channels and degrades thermal performance. A simplified hydraulic-thermal analysis shows that this bypass penalty cannot be eliminated by reducing the fin pitch of a rectangular-fin heat sink alone.
A staggered pin-fin heat sink is therefore proposed, with pin diameter D, longitudinal pitch Sd and transverse pitch St optimised by three-dimensional CFD using PAO-6. The optimum geometry is D = 2.8 mm, St = 6 mm, Sd = 8.45 mm. The heat sink is fabricated and tested in a commercial server at oil inlet temperatures of 30-45°C and flow rates of 3-6 LPM. At 3 LPM, the pin-fin immersion server reduces CPU thermal resistance by 22.29% relative to a rectangular-fin immersion server using the same oil, and by 38.37% relative to an air-cooled server. Partial Power Usage Effectiveness (pPUE) reaches 1.015 against 1.126 for the air-cooled baseline, an 88.09% improvement. The results show that pin-fin geometries effectively mitigate the bypass penalty in single-phase oil immersion cooling.
Key points
- Problem: high-viscosity dielectric oil amplifies bypass flow around the CPU heat sink through RAM channels.
- Reducing fin pitch of a rectangular-fin sink alone cannot remove the bypass penalty.
- Optimum staggered pin-fin geometry: D = 2.8 mm, St = 6 mm, Sd = 8.45 mm (PAO-6, 3D CFD).
- Test condition: oil inlet 30-45°C, flow 3-6 LPM, commercial server.
- At 3 LPM CPU thermal resistance falls 22.29% against rectangular fins and 38.37% against air cooling.
- pPUE is 1.015 against 1.126 for the air-cooled baseline; improvement 88.09%.
Using it in design
- In immersion-cooled servers evaluate heat sink geometry together with oil viscosity and bypass through neighbouring flow channels; do not rely on smaller fin pitch alone.
- If a pin-fin heat sink is used, optimise pin diameter and pitches by CFD for the actual fluid (PAO-6).
- Select oil flow (3-6 LPM) and inlet temperature (30-45°C) together with CPU thermal resistance.
- In energy comparison calculate pPUE (1.015 against 1.126) on the same boundary as the air-cooled reference.
Who should read it
Thermal engineers and data-centre designers working on immersion-cooled servers and heat sinks.
Publication details
- Authors
- Shau-Wai Cheng; Yong-Dong Zhang; Li-Hung Chien; Chi-Chuan Wang
- Publisher
- Processes (MDPI AG)
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: https://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Shau-Wai Cheng; Yong-Dong Zhang; Li-Hung Chien; Chi-Chuan Wang (2026). A Comparative Study of a Single-Phase Immersion-Cooled Server with a Pin-Fin Heat Sink for Mitigation of the Flow Bypass Effect. Processes (MDPI AG). https://doi.org/10.3390/pr14132209
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.