NERC Alert Level 2: Large Load Interconnection, Study, Commissioning, and Operations
Original title NERC Level 2 Alert - Industry Recommendation: Large Load Interconnection, Study, Commissioning, and Operations
North American Electric Reliability Corporation (NERC)
NERC's Level 2 industry recommendation of 9 September 2025 responds to unexpected load reductions above 1,000 MW and recommends interconnection criteria, models, commissioning validation and operating protocols for large loads such as data centres.
On this page
Overview
The alert is based on analysis of widespread, customer-initiated, unexpected load reductions on the North American bulk power system (BPS). The events involved more than 1,000 MW of unexpected load reduction in total, most in 2024 or 2025. NERC set up the Large Loads Task Force (LLTF) in August 2024, and its July 2025 white paper highlights rapid demand fluctuation and cyclical ramping. A Large Load is any single-site load facility that can pose BPS reliability risks, including data centres, cryptocurrency mining, hydrogen electrolyzers, manufacturing facilities and arc furnaces.
The alert gives five recommendations. 1: transmission owners (TOs) should put facility design and performance criteria, and high-speed disturbance data capture such as PMUs, into interconnection requirements; model data, ramp limits, post-disturbance voltage and frequency recovery, voltage control modes and design that reduces oscillation interaction are requested. 2: planners should build a study process using steady-state, dynamic and short-circuit models. 3: commissioning should be strengthened, 4: operating protocols and communication infrastructure set up, and 5: large loads included in long- and near-term demand forecasts.
Recommendation 3 on commissioning asks for consultation with operating entities before commercial operation, as-designed and as-built model updates, and model validation: comparing motor, IT and cooling load MVA with measurements and equipment nameplates, verifying power factor at the point of interconnection, and threshold-based model updates and restudy. For loads that phase in over years, commissioning and model validation should occur at each phase, not only at first energisation.
The document is not a reliability standard and non-implementation carries no penalty. Entities must acknowledge receipt by 16 September 2025 and respond by 28 January 2026; the question set has 44 questions for TOs and DPs, 22 for TPs and PCs, 27 for RCs, BAs and TOPs, and 9 for RPs.
Key points
- Multiple events involved more than 1,000 MW of unexpected large-load reduction in total, most in 2024 or 2025.
- The Large Load definition includes data centres, crypto mining, electrolyzers, manufacturing facilities and arc furnaces.
- Recommendation 1: TOs should put design and performance criteria and high-speed capture devices such as PMUs into interconnection requirements.
- Interconnection requirements: steady-state, dynamic and short-circuit models; ramp limits; post-disturbance voltage and frequency recovery.
- Recommendation 3: validate models by comparing motor, IT and cooling load MVA with measurements and nameplates, and verify power factor at the interconnection point.
- For loads that phase in over years, commissioning and model validation should occur at each phase.
- Recommendation 4: common real-time communication protocols, load forecasts and notification of major equipment status changes.
- The alert is not a reliability standard and carries no penalty; acknowledgement was due 16 September 2025 and responses 28 January 2026.
Using it in design
- For grid-connected data-centre projects, prepare the modelling data the transmission owner asks for (steady-state, dynamic, short-circuit) during design and update it for as-built changes.
- Add PMU or high-resolution fault recorder placement at the interconnection point, and data storage capacity, to the electrical design.
- Plan a commissioning validation step comparing motor, IT and cooling load MVA with nameplates and measurements; validate each phase of a phased build separately.
- Define post-disturbance recovery and ramp-limit scenarios to study how UPS and cooling controls behave and shed load during grid disturbances.
- Write a real-time communication and load-forecast sharing procedure with the grid operator into the operating plan.
Who should read it
Data-centre developers planning grid connections, electrical designers, transmission companies and grid planning entities.
Document contents
- Purpose and background
- Large Load definition
- Recommendation 1: interconnection requirements
- Recommendation 2: interconnection and system-wide studies
- Recommendation 3: commissioning
- Recommendation 4: operating protocols and communication
- Recommendation 5: demand forecasts
- Reporting instructions and questions
Related standards
- IEEE 2800
- NERC MOD-032
Publication details
- Authors
- North American Electric Reliability Corporation (NERC)
- Publisher
- North American Electric Reliability Corporation (NERC)
- Year
- 2025
- Document language
- English
- Source type
- Expert / community
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
NERC alert document; no open licence stated.
Citation
North American Electric Reliability Corporation (NERC) (2025). NERC Level 2 Alert - Industry Recommendation: Large Load Interconnection, Study, Commissioning, and Operations. North American Electric Reliability Corporation (NERC). https://www.nerc.com/pa/rrm/bpsa/Alerts%20DL/NERC%20Alert%20Level%202%20%20Large%20Loads.pdf