Recommendations for Improved Seismic Performance of Nonstructural Components
National Institute of Standards and Technology / Applied Technology Council · Applied Technology Council
A 2018 Applied Technology Council report for NIST (GCR 18-917-43) that proposes performance objectives and a new seismic force equation for nonstructural components, with a data-centre example of post-earthquake function.
On this page
Overview
The report is the second phase of the ATC-120 project, started by the Applied Technology Council in 2014 under a NIST contract. Its aim is to improve the seismic design of nonstructural systems (mechanical and electrical equipment, piping, cladding, partitions) in the areas with the greatest effect on public safety and economic welfare, for construction regulated by building codes. It gathers the body of knowledge and produces recommended changes to codes and practice.
The first axis is performance objectives. For ordinary components, the report proposes no damage in frequent earthquakes and position retention in the design earthquake. For components needing post-earthquake functionality, continued function in the design earthquake is the target. Quantitative risk targets are judged premature for lack of data and left as a long-term goal. Data centres are named among the facilities, such as critical corporate data centres, where an owner may want enhanced assurance.
The second axis reviews the existing force equation in ASCE/SEI 7-16 and proposes a new primary equation. It sorts components by whether they are likely to be in resonance with the building and into low, moderate and high ductility categories, and raises the upper-bound design force where resonance is likely. Chapter 5 develops ductile design of supports and attachments through four examples: an elevated vessel, a partition wall, a mechanical unit and a piping support.
The data-centre example in section 2.5 speaks directly to facility designers. Servers, batteries, cable trays and conduit, cooling, security and fire suppression systems must be protected together. To avoid damaging water release, equipment rooms typically use non-water-based fire protection. The report recommends shake-table testing of essential equipment for post-earthquake reliability, on-site inspection during construction, and it lists resilience strategies beyond design for the owner.
Key points
- Data centres are often treated as Essential Facilities (Risk Category IV); shake-table testing of essential equipment is recommended for post-earthquake reliability.
- The data-centre example protects servers, batteries, cable trays and conduit, cooling, security and fire suppression systems together.
- Equipment rooms typically use non-water-based fire protection to prevent damaging water release during an earthquake.
- Server racks and cable trays are occasionally relocated, so periodic inspection after installation and detailed post-earthquake functionality-verification procedures are needed.
- Proposed objectives: ordinary components, no damage in frequent earthquakes and position retention in the design earthquake; components needing function, continued functionality in the design earthquake.
- The new force equation separates components likely to be in resonance from those that are not, and assigns low, moderate or high ductility categories.
- The upper-bound lateral design force (Fp,max) is raised where resonance is likely, and an overstrength factor is considered for brittle connections such as welds.
- Resilience strategies beyond design: on-site personnel with planned procedures, redundant service at an alternate site, spare components and access to a seismic engineer.
- Quantitative risk targets are left as a long-term goal because data to calibrate them are insufficient.
Using it in design
- For a data centre in a seismic region, scope functional protection to cover servers, batteries, cable trays, cooling, security and fire suppression together, and collect the anchorage requirements in one specification.
- Ask suppliers of critical equipment for shake-table test reports and require on-site inspection of anchorage and component interactions during construction.
- Assess the damage risk of water-based fire systems in equipment rooms and compare non-water-based options from the seismic standpoint as well.
- Add re-inspection of anchors and connections after any rack or tray relocation to operating procedures, and prepare a post-earthquake system functionality checklist in advance.
- For heavy equipment that may resonate (generators, cooling units), compare building period with component period and set anchor forces accordingly.
Who should read it
Structural and MEP engineers designing data centres in seismic regions, equipment anchorage and support designers, and facility owners.
Document contents
- Introduction
- Performance Objectives for Nonstructural Components
- Review of ASCE/SEI 7-16 Seismic Requirements for Nonstructural Components
- Understanding the Response of Nonstructural Components to Earthquakes
- Ductile Design of Nonstructural Supports and Attachments
- Holistic Approach to Protecting Nonstructural Components
- Recommendations
Publication details
- Authors
- Applied Technology Council
- Publisher
- National Institute of Standards and Technology / Applied Technology Council
- Year
- 2018
- Document number
- NIST GCR 18-917-43
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official PDF downloaded. Disclaimer reserves third-party photos/figures for separate permission; full-text redistribution not assumed for this contractor-authored report.
Citation
Applied Technology Council (2018). Recommendations for Improved Seismic Performance of Nonstructural Components. National Institute of Standards and Technology / Applied Technology Council. NIST GCR 18-917-43. https://doi.org/10.6028/NIST.GCR.18-917-43
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.