RegulationFree to read2025

Data Center and Cloud Service (Operation and Management) Directives, 2081 (2025)

Original title Data Center and Cloud Service (Operation and Management) Directives, 2081: unofficial English translation

Nepal Ministry of Communication and Information Technology

Nepal's Ministry of Communication and Information Technology directives, approved January 2025, require data-centre and cloud providers to register and set a minimum of Tier 3 for providers storing government data.

On this page

Overview

The directives were issued by Nepal's Ministry of Communication and Information Technology under the Electronic Transactions Act (2008) and approved on 28 January 2025 (unofficial English translation). They require data-centre and cloud providers to be listed with the Department of Information Technology before offering services. Applications include fire-safety assurance, building completion certificate, security and privacy policy, business continuity plan, location map, Tier details, physical security methods, high-level electrical design and technical staff details.

Existing operators must apply for mandatory registration within six months of commencement. Data centres attach an information-security standard certificate for both the primary and disaster-recovery (DR) site; cloud providers attach information security and IT service management certificates. After inspection and physical verification, listing may follow within one month, and details are updated each year by the end of Poush. Non-compliance or misuse of data leads to removal after a 15-day period to respond.

The Tier requirements appear in a schedule referencing the Uptime Institute. Providers storing government data must reach at least Tier 3, with a Tier certificate submitted within the listing year. Provider duties include equal access, annual security audit, compliance officer, incident reporting, business continuity, and racks, network gear, HVAC, fire safety, reliable internet and power, access control, CCTV (footage kept at least three months), a NOC, regular backup and irrecoverable disk destruction.

Government bodies host their data at the Integrated Data Management Center, and departmental data centres move to the government facility on the steering committee's timetable. The committee is chaired by the ministry secretary with seven ministry or agency representatives and an expert. The directives provide for an effectiveness review after two years. They are an administrative instrument: no detailed engineering specification is given, and the Tier table is a high-level set of criteria.

Key points

  1. Providers must be listed with the Department of Information Technology before offering services; existing operators have six months to apply.
  2. Applications include high-level electrical design, Tier details, fire-safety assurance and a business continuity plan.
  3. Data centres storing government data must be at least Tier 3.
  4. Schedule availability: Tier 1 99.671% (under 28.8 hours downtime a year), Tier 2 99.749% (22 hours), Tier 3 99.982% (1.6 hours), Tier 4 99.995% (26.3 minutes).
  5. Schedule power backup: Tier 1 12 hours, Tier 2 12-24 hours, Tier 3 24-48 hours, Tier 4 48 hours.
  6. Tier 3 expects N+1 active components and concurrent maintainability; Tier 4 expects 2(N+1) and fault tolerance.
  7. Providers conduct at least one security audit a year and keep CCTV footage at least three months.
  8. Government bodies host data in the government data centre; removal from the list follows a 15-day response period.

Using it in design

  • For sites hosting Nepali government data, make Tier 3 architecture (N+1, concurrent maintainability, dual path) the design basis.
  • Convert the schedule's power backup duration (24-48 hours for Tier 3) into generator fuel storage sizing.
  • Prepare the high-level electrical single-line, fire-safety and physical-security documents early for the listing package.
  • Include access control, CCTV (at least three months of storage capacity) and DCIM/NOC requirements in scope.
  • Add separate information-security certification for the primary and DR sites to the project schedule.

Who should read it

Operators setting up data-centre or cloud services in Nepal or serving government data, and their design teams.

Document contents

  1. Short title and commencement
  2. Definitions
  3. Listing of Data Center and Cloud Service Providers
  4. Details to be updated
  5. Removal from the List
  6. Tiers of Data Center
  7. Conditions to be fulfilled by providers
  8. Client's duties, responsibilities and rights
  9. Duties of the Department
  10. Integrated Data Management Center
  11. Functions of the Center
  12. Steering Committee
  13. Monitoring and Evaluation
  14. Schedule: Tier criteria

Publication details

Authors
Nepal Ministry of Communication and Information Technology
Publisher
Nepal Ministry of Communication and Information Technology
Year
2025
Document number
Directives 2081 (2025)
Document language
English
Source type
Government / public
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public official source inspected. No document-specific commercial redistribution permission established. Metadata and original brief summaries only; local evidence is not a redistribution package.

Citation

Nepal Ministry of Communication and Information Technology (2025). Data Center and Cloud Service (Operation and Management) Directives, 2081: unofficial English translation. Nepal Ministry of Communication and Information Technology. Directives 2081 (2025). https://giwmscdnone.gov.np/media/pdf_upload/data%20center%20translation_bhnhhri.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.