Bio-Analysis of Cross-Mixed Coolants in High-Powered Liquid-Cooled Data Center
NSF Public Access Repository / ASME Journal of Electronic Packaging · Pardeep Shahi, Ali Heydari et al.
A 2025 ASME Journal of Electronic Packaging paper testing how residual coolant left after flushing drives microbial growth in liquid-cooled data centres, sampled every 30 and 10 days.
On this page
Overview
The paper focuses on flushing, the step applied to cooling equipment in single-phase liquid-cooled data centres. Flushing removes closed-loop contamination, but draining never removes all coolant, so residuals stay behind. Fresh coolant can be contaminated by them, and biological growth from cross-contamination brings fouling, corrosion and poor heat transfer.
The experiment has two parts. In the first, a coupon set of TCS-loop wetted materials is submerged in a cross-contaminated solution of known concentration for an extended period, with microbial growth sampled every 30 days; this mirrors stagnant loops and equipment stored after flushing. In the second, two separate loops with a microfin cold plate on a heater base are flushed with type II DI water and treated water, refilled with fresh coolant and circulated, with sampling every 10 days.
The study concludes that routine bio-analysis and effective microbial control measures are needed in liquid-cooled data centres. The repository releases the full text on 1 December 2026; the abstract is the basis here.
Key points
- The issue is residual coolant left after flushing contaminating fresh coolant.
- Coupon test: TCS wetted materials sit in cross-contaminated solution, sampled every 30 days.
- Circulation test: two loops with microfin cold plates are flushed with type II DI water and treated water, sampled every 10 days.
- Bacteria can cause fouling, corrosion and inadequate heat transfer.
- The conclusion calls for routine bio-analysis and microbial control.
Using it in design
- Write residual volume and a pre-fill microbial check into the flushing and filling procedure.
- Set a dry-storage or biocide-hold rule for loop components that sit stagnant after flushing.
- Add periodic microbial sampling of the TCS coolant to the operations plan.
- Treat switching between coolant brands as a cross-mixing risk in the maintenance procedure.
Who should read it
Operations and maintenance teams of liquid-cooled facilities and engineers writing coolant specifications.
Publication details
- Authors
- Pardeep Shahi; Ali Heydari; Lochan Sai Reddy Chinthaparthy; Himanshu Modi; Anto Barigala; Sean Sivapalan; Harold Miyamura; Mohammad Tradat; Dereje Agonafer; Jeremy Rodriguez
- Publisher
- NSF Public Access Repository / ASME Journal of Electronic Packaging
- Year
- 2025
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
NSF publishes an official grant-linked bibliographic record and deposited abstract; ASME publisher page blocked. Full content embargo remains until 2026-12-01. No redistribution license established.
Citation
Pardeep Shahi; Ali Heydari; Lochan Sai Reddy Chinthaparthy; Himanshu Modi; Anto Barigala; Sean Sivapalan; Harold Miyamura; Mohammad Tradat; Dereje Agonafer; Jeremy Rodriguez (2025). Bio-Analysis of Cross-Mixed Coolants in High-Powered Liquid-Cooled Data Center. NSF Public Access Repository / ASME Journal of Electronic Packaging. https://doi.org/10.1115/1.4069444
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.