Research paperFree to read2025

Assessment of Single-Phase Liquid Cooling in Data Centers: Thermal Performance, Fluid Integrity, and System Resiliency

University of Texas at Arlington · Anto Joseph Barigala Charles Paulraj

A 2025 University of Texas at Arlington PhD dissertation testing CDU failure scenarios, wetted-material corrosion and micro-channel cold plates (up to 172 W/cm²) in single-phase liquid cooling.

On this page

Overview

The dissertation is a mechanical engineering PhD supervised by Dr. Dereje Agonafer. It assesses single-phase liquid cooling on three axes: thermal performance, fluid integrity and system resiliency. The experiments cover both direct-to-chip (D2C) and single-phase immersion configurations, starting from the premise that rising power density is outpacing air cooling.

In the resiliency part, a liquid-to-liquid (L2L) in-row coolant distribution unit (CDU) is tested under operating and failure scenarios: total and partial loss of primary flow, pump failures and CDU failover. The conclusion is that temperature can climb within minutes when primary cooling fails, so quick-acting redundancy is essential.

In the fluid-integrity part, corrosion of wetted materials (copper, brass, stainless steel 304 and 316) is measured under ASTM D1384 and D8040. Several commercial PG-25 coolants and a PAO 2 dielectric oil are benchmarked, and material compatibility and loss rates vary markedly with coolant formulation. The last part evaluates single-phase immersion cooling with several heatsink and cold-plate geometries.

Full text of the dissertation is embargoed until 12 August 2027; the public page carries the abstract, from which the findings above are taken.

Key points

  1. Failure scenarios tested: total and partial primary flow loss, pump failure and CDU failover.
  2. After a primary cooling failure, temperature can rise rapidly within minutes, so quick-acting redundancy is decisive.
  3. Corrosion tests cover copper, brass and stainless steel 304/316 under ASTM D1384 and D8040.
  4. Fluids compared: several commercial PG-25 coolants and PAO 2 dielectric oil; compatibility varies significantly with formulation.
  5. Micro-channel cold plates reached the highest heat flux (up to 172 W/cm²) and the lowest thermal resistance (about 0.041 °C/W).
  6. Micro-channel plates outperformed traditional skived-fin designs, at the cost of higher flow impedance.

Using it in design

  • Judge CDU redundancy by transfer time as well as equipment count; make the post-failure temperature rise rate a design criterion.
  • Approve the wetted-material list together with the inhibitor chemistry of the selected PG-25 coolant, backed by ASTM D1384-type test data.
  • When selecting cold plates, weigh the thermal resistance gain against the added pump head.
  • Add primary flow loss and pump failure scenarios to commissioning acceptance tests.

Who should read it

Mechanical designers of liquid-cooled halls, engineers selecting CDUs and coolants, and commissioning teams.

Publication details

Authors
Anto Joseph Barigala Charles Paulraj
Publisher
University of Texas at Arlington
Year
2025
Document number
Mechanical and Aerospace Engineering Dissertations, 434
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

The article-specific repository License section states CC BY 4.0. Full text is embargoed until 12 August 2027 and was not requested; redistributable remains false for the unavailable full-text asset. Public abstract only.

Citation

Anto Joseph Barigala Charles Paulraj (2025). Assessment of Single-Phase Liquid Cooling in Data Centers: Thermal Performance, Fluid Integrity, and System Resiliency. University of Texas at Arlington. Mechanical and Aerospace Engineering Dissertations, 434. https://mavmatrix.uta.edu/mechaerospace_dissertations/434/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.