Assessment of Single-Phase Liquid Cooling in Data Centers: Thermal Performance, Fluid Integrity, and System Resiliency
University of Texas at Arlington · Anto Joseph Barigala Charles Paulraj
A 2025 University of Texas at Arlington PhD dissertation testing CDU failure scenarios, wetted-material corrosion and micro-channel cold plates (up to 172 W/cm²) in single-phase liquid cooling.
On this page
Overview
The dissertation is a mechanical engineering PhD supervised by Dr. Dereje Agonafer. It assesses single-phase liquid cooling on three axes: thermal performance, fluid integrity and system resiliency. The experiments cover both direct-to-chip (D2C) and single-phase immersion configurations, starting from the premise that rising power density is outpacing air cooling.
In the resiliency part, a liquid-to-liquid (L2L) in-row coolant distribution unit (CDU) is tested under operating and failure scenarios: total and partial loss of primary flow, pump failures and CDU failover. The conclusion is that temperature can climb within minutes when primary cooling fails, so quick-acting redundancy is essential.
In the fluid-integrity part, corrosion of wetted materials (copper, brass, stainless steel 304 and 316) is measured under ASTM D1384 and D8040. Several commercial PG-25 coolants and a PAO 2 dielectric oil are benchmarked, and material compatibility and loss rates vary markedly with coolant formulation. The last part evaluates single-phase immersion cooling with several heatsink and cold-plate geometries.
Full text of the dissertation is embargoed until 12 August 2027; the public page carries the abstract, from which the findings above are taken.
Key points
- Failure scenarios tested: total and partial primary flow loss, pump failure and CDU failover.
- After a primary cooling failure, temperature can rise rapidly within minutes, so quick-acting redundancy is decisive.
- Corrosion tests cover copper, brass and stainless steel 304/316 under ASTM D1384 and D8040.
- Fluids compared: several commercial PG-25 coolants and PAO 2 dielectric oil; compatibility varies significantly with formulation.
- Micro-channel cold plates reached the highest heat flux (up to 172 W/cm²) and the lowest thermal resistance (about 0.041 °C/W).
- Micro-channel plates outperformed traditional skived-fin designs, at the cost of higher flow impedance.
Using it in design
- Judge CDU redundancy by transfer time as well as equipment count; make the post-failure temperature rise rate a design criterion.
- Approve the wetted-material list together with the inhibitor chemistry of the selected PG-25 coolant, backed by ASTM D1384-type test data.
- When selecting cold plates, weigh the thermal resistance gain against the added pump head.
- Add primary flow loss and pump failure scenarios to commissioning acceptance tests.
Who should read it
Mechanical designers of liquid-cooled halls, engineers selecting CDUs and coolants, and commissioning teams.
Publication details
- Authors
- Anto Joseph Barigala Charles Paulraj
- Publisher
- University of Texas at Arlington
- Year
- 2025
- Document number
- Mechanical and Aerospace Engineering Dissertations, 434
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
The article-specific repository License section states CC BY 4.0. Full text is embargoed until 12 August 2027 and was not requested; redistributable remains false for the unavailable full-text asset. Public abstract only.
Citation
Anto Joseph Barigala Charles Paulraj (2025). Assessment of Single-Phase Liquid Cooling in Data Centers: Thermal Performance, Fluid Integrity, and System Resiliency. University of Texas at Arlington. Mechanical and Aerospace Engineering Dissertations, 434. https://mavmatrix.uta.edu/mechaerospace_dissertations/434/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.