nVent Edge and Data Center Cooling Solutions: Precision and High Density Liquid Cooling (2019)
Original title Edge and Data Center Cooling Solutions: Precision and High Density Liquid Cooling
nVent · nVent (Hoffman / Schroff)
nVent's 2019 brochure: a cooling continuum from 2-6 kW per cabinet to 60-750+ kW direct-to-chip liquid cooling, with rear door coolers (25-55 kW), in-row units, aisle containment and edge computing air conditioners.
On this page
Overview
The brochure says rising heat densities driven by content streaming, cloud computing, AI and low-latency edge demand strain data centre cooling, and presents nVent's standard and custom air, indirect and direct water cooling solutions. Cooling a whole room with one CRAC/CRAH system worked while cabinets were sparse and heat load low, but becomes inefficient at high density.
A 'continuum of cooling' lists technologies by capacity per cabinet: integrated convection (2-6 kW), in-rack air conditioner (6-8 kW), in-row and aisle containment (8-12 kW and 15-25 kW), rear door cooling (passive/active, 25-55 kW) and direct-to-chip liquid cooling (60-750+ kW). A strategies table compares hot aisle/cold aisle, room-based containment, chimney, hot and cold containment, in-row and rack/rear door liquid cooling on raised floor need, capital and operating cost and average maximum kW per cabinet (for example hot aisle/cold aisle 6-8 kW, containment up to 10 kW, in-row 10-20 kW, rack and rear door liquid 20-40 kW, direct liquid above 40 kW).
The edge computing section covers indoor and outdoor air conditioners for wall-mount and free-standing cabinets (up to 8 kW), closed-loop cooling (separating clean recirculated air from ambient air), the T-series compact outdoor and SpectraCool indoor/outdoor models. The data centre section covers aisle containment (HAC/CAC), the SCHROFF RackChiller In-Row chilled water heat exchanger (300 and 600 mm widths) and the rear door cooler (RDC), reaching up to 25 kW per cabinet.
The document is a manufacturer brochure: it gives capacity ranges and a comparison across technologies and directs readers to selection tools for detailed selection data.
Key points
- Cooling continuum: 2-6 kW (integrated convection), 6-8 kW (in-rack AC), 8-12 and 15-25 kW (in-row, aisle containment), 25-55 kW (rear door), 60-750+ kW (direct-to-chip liquid).
- Strategies table, average maximum cabinet load: hot/cold aisle 6-8 kW, room-based containment up to 10 kW, chimney 10-20 kW, in-row 10-20 kW, rack/rear door liquid 20-40 kW, direct liquid above 40 kW.
- Containment and chimney strategies may not need a raised floor; random layout and hot/cold aisle are shown with raised floor.
- For edge applications, indoor/outdoor air conditioners provide up to 8 kW cooling; closed-loop cooling keeps clean air separate from ambient air.
- The rear door cooler (RDC) targets capacity up to 25 kW per cabinet.
- The SCHROFF RackChiller In-Row chilled water heat exchanger is modular in 300 and 600 mm widths and works with aisle containment.
- Traditional CRAC/CRAH room cooling suits sparse layouts and low heat load; it becomes inefficient as density rises.
Using it in design
- Match per-cabinet design load to the continuum ranges; above 10 kW, evaluate local solutions such as containment, in-row or rear door.
- Decide from cabinet load distribution whether high density of 25-55 kW needs passive/active rear door or liquid cooling above 40 kW.
- On sites without or with limited raised floor, compare contained in-row solutions on capital and operating cost.
- For edge cabinets above 8 kW load, accept that the convection limit is exceeded and add an air conditioner or closed-loop cooling.
- Include chilled water infrastructure (temperature, flow, per-cabinet connections) for in-row and rear door solutions in the overall system design.
Who should read it
Designers choosing a cooling strategy for halls with rising cabinet density and engineers planning edge computing facilities.
Document contents
- Rising heat densities
- Continuum of cooling
- Edge computing cooling solutions (indoor/outdoor air conditioners)
- Free-standing cabinets and outdoor solutions
- Aisle containment
- RackChiller In-Row precision cooler
- Rear door cooler
Related standards
- ASHRAE TC 9.9 liquid cooling classes
Publication details
- Authors
- nVent (Hoffman / Schroff)
- Publisher
- nVent
- Year
- 2019
- Document number
- SB-H85398
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Vendor brochure; no open licence stated
Citation
nVent (Hoffman / Schroff) (2019). Edge and Data Center Cooling Solutions: Precision and High Density Liquid Cooling. nVent. SB-H85398. https://go.nvent.com/rs/760-EGW-100/images/nVent-SB-H85398-DNSCooling-EN.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.