nVent Edge and Data Center Cooling Solutions: Precision and High Density Liquid Cooling (2019)

Original title Edge and Data Center Cooling Solutions: Precision and High Density Liquid Cooling

nVent · nVent (Hoffman / Schroff)

nVent's 2019 brochure: a cooling continuum from 2-6 kW per cabinet to 60-750+ kW direct-to-chip liquid cooling, with rear door coolers (25-55 kW), in-row units, aisle containment and edge computing air conditioners.

On this page

Overview

The brochure says rising heat densities driven by content streaming, cloud computing, AI and low-latency edge demand strain data centre cooling, and presents nVent's standard and custom air, indirect and direct water cooling solutions. Cooling a whole room with one CRAC/CRAH system worked while cabinets were sparse and heat load low, but becomes inefficient at high density.

A 'continuum of cooling' lists technologies by capacity per cabinet: integrated convection (2-6 kW), in-rack air conditioner (6-8 kW), in-row and aisle containment (8-12 kW and 15-25 kW), rear door cooling (passive/active, 25-55 kW) and direct-to-chip liquid cooling (60-750+ kW). A strategies table compares hot aisle/cold aisle, room-based containment, chimney, hot and cold containment, in-row and rack/rear door liquid cooling on raised floor need, capital and operating cost and average maximum kW per cabinet (for example hot aisle/cold aisle 6-8 kW, containment up to 10 kW, in-row 10-20 kW, rack and rear door liquid 20-40 kW, direct liquid above 40 kW).

The edge computing section covers indoor and outdoor air conditioners for wall-mount and free-standing cabinets (up to 8 kW), closed-loop cooling (separating clean recirculated air from ambient air), the T-series compact outdoor and SpectraCool indoor/outdoor models. The data centre section covers aisle containment (HAC/CAC), the SCHROFF RackChiller In-Row chilled water heat exchanger (300 and 600 mm widths) and the rear door cooler (RDC), reaching up to 25 kW per cabinet.

The document is a manufacturer brochure: it gives capacity ranges and a comparison across technologies and directs readers to selection tools for detailed selection data.

Key points

  1. Cooling continuum: 2-6 kW (integrated convection), 6-8 kW (in-rack AC), 8-12 and 15-25 kW (in-row, aisle containment), 25-55 kW (rear door), 60-750+ kW (direct-to-chip liquid).
  2. Strategies table, average maximum cabinet load: hot/cold aisle 6-8 kW, room-based containment up to 10 kW, chimney 10-20 kW, in-row 10-20 kW, rack/rear door liquid 20-40 kW, direct liquid above 40 kW.
  3. Containment and chimney strategies may not need a raised floor; random layout and hot/cold aisle are shown with raised floor.
  4. For edge applications, indoor/outdoor air conditioners provide up to 8 kW cooling; closed-loop cooling keeps clean air separate from ambient air.
  5. The rear door cooler (RDC) targets capacity up to 25 kW per cabinet.
  6. The SCHROFF RackChiller In-Row chilled water heat exchanger is modular in 300 and 600 mm widths and works with aisle containment.
  7. Traditional CRAC/CRAH room cooling suits sparse layouts and low heat load; it becomes inefficient as density rises.

Using it in design

  • Match per-cabinet design load to the continuum ranges; above 10 kW, evaluate local solutions such as containment, in-row or rear door.
  • Decide from cabinet load distribution whether high density of 25-55 kW needs passive/active rear door or liquid cooling above 40 kW.
  • On sites without or with limited raised floor, compare contained in-row solutions on capital and operating cost.
  • For edge cabinets above 8 kW load, accept that the convection limit is exceeded and add an air conditioner or closed-loop cooling.
  • Include chilled water infrastructure (temperature, flow, per-cabinet connections) for in-row and rear door solutions in the overall system design.

Who should read it

Designers choosing a cooling strategy for halls with rising cabinet density and engineers planning edge computing facilities.

Document contents

  1. Rising heat densities
  2. Continuum of cooling
  3. Edge computing cooling solutions (indoor/outdoor air conditioners)
  4. Free-standing cabinets and outdoor solutions
  5. Aisle containment
  6. RackChiller In-Row precision cooler
  7. Rear door cooler

Related standards

  • ASHRAE TC 9.9 liquid cooling classes

Publication details

Authors
nVent (Hoffman / Schroff)
Publisher
nVent
Year
2019
Document number
SB-H85398
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Vendor brochure; no open licence stated

Citation

nVent (Hoffman / Schroff) (2019). Edge and Data Center Cooling Solutions: Precision and High Density Liquid Cooling. nVent. SB-H85398. https://go.nvent.com/rs/760-EGW-100/images/nVent-SB-H85398-DNSCooling-EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.