NVIDIA DGX SuperPOD: Next Generation Scalable Infrastructure for AI Leadership: Featuring NVIDIA DGX GB300 Systems

NVIDIA

NVIDIA's DGX GB300 SuperPOD reference architecture: 1.2 MW TDP per 8-rack scalable unit (SU), eight power shelves per rack, scaling to 128 racks and 9216 GPUs.

On this page

Overview

The document describes the DGX SuperPOD reference architecture built on DGX GB300 systems powered by Grace CPUs and Blackwell Ultra GPUs. The architecture is based on scalable units (SUs) of 8 DGX GB300 rack systems, and this reference design shows scaling to 128 racks and 9216 GPUs. It covers InfiniBand, NVLink and Ethernet topologies, storage requirements, recommended rack layouts, wiring guidelines and the software stack.

The most important facility statement is that each SU requires a thermal design power (TDP) of 1.2 MW. The data centre is generally expected to meet Uptime Institute Tier 3, TIA-942-B Rated 3 or EN 50600 Availability Class 3 design levels, meaning concurrent maintainability and no single point of failure. The 1.2 MW figure belongs to the unit of compute, network, management and storage racks together, not to a single compute rack.

Each DGX GB300 rack system is a 72-GPU NVL72 configuration with hybrid cooling: the most power-intensive components such as GPUs and CPUs are liquid cooled, and the rest are air cooled. The rack holds 18 compute trays and 9 NVLink switch trays. On power, there are eight power shelves, each delivering up to 33 kW from six 5.5 kW PSUs. Compared with the previous generation, larger energy storage is added to lower the peak load seen by the data centre power system.

The paper is a product architecture description; detailed facility and OT integration guidance is left to NVIDIA's separate data centre design guide and the Mission Control software. Power shelf capacity is not a system input-load measurement, so actual demand must be established separately.

Key points

  1. One scalable unit (SU) holds 8 DGX GB300 rack systems and requires 1.2 MW TDP.
  2. The reference architecture scales to 128 racks and 9216 GPUs.
  3. Target facility level: Uptime Tier 3, TIA-942-B Rated 3 or EN 50600 Availability Class 3.
  4. DGX GB300 rack system is NVL72: 72 GPUs, 18 compute trays, 9 NVLink switch trays.
  5. Hybrid cooling: GPUs and CPUs are liquid cooled, other components are air cooled.
  6. Each power shelf has 6 x 5.5 kW PSUs for up to 33 kW; the rack has eight power shelves.
  7. Larger energy storage in the power shelf reduces the peak load the data centre must supply.
  8. Networking: Quantum-X800 InfiniBand (800 Gb/s) compute fabric and Spectrum-4 (800 Gb/s) Ethernet storage fabric.

Using it in design

  • Size facility power and cooling to the 1.2 MW TDP per SU rather than a single rack, and count network, management and storage racks.
  • Read eight power shelves x 33 kW as source capacity rather than a load limit; set grid input from measured load.
  • For hybrid cooling plan the liquid loop (cold water inlet, hot water outlet) and the remaining air-cooled load separately.
  • To meet the Tier 3 target build concurrently maintainable power and cooling distribution with no single point of failure.
  • Evaluate the peak-smoothing effect of power shelf storage in UPS and generator transfer load calculations.

Who should read it

Data-centre designers, capacity planners and infrastructure architects planning large-scale AI clusters.

Document contents

  1. DGX SuperPOD Architecture
  2. Key Components of DGX SuperPOD
  3. NVIDIA Mission Control
  4. Design Requirements
  5. Network Fabrics
  6. Customer Edge Connectivity
  7. Storage Architecture
  8. DGX SuperPOD Software
  9. Summary

Publication details

Authors
NVIDIA
Publisher
NVIDIA
Year
2025
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

NVIDIA (2025). NVIDIA DGX SuperPOD: Next Generation Scalable Infrastructure for AI Leadership: Featuring NVIDIA DGX GB300 Systems. NVIDIA. https://docs.nvidia.com/pdf/dgx-spod-gb300-ra.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.