AI infrastructure ready to deploy: Hybrid liquid cooling architecture for scalable AI inference (2 MW)

Original title Reference Design: AI infrastructure ready to deploy - Hybrid liquid cooling architecture for scalable AI inference (2 MW)

Submer · Submer, 2CRSi

A 2CRSi and Submer reference design for a 2 MW hybrid AI architecture combining immersion-cooled compute holding up to 2,688 GPUs with air-cooled networking and storage racks, on 35 °C facility water.

On this page

Overview

Citing surging GPU demand and infrastructure complexity that slow scaling, the document offers a pre-validated, plug-and-play reference design that combines immersion-cooled GPU clusters with networking, storage and management. It is built on 2CRSi immersion servers and Submer SmartPod EXO tanks and can scale to any cluster size with NVIDIA H200 NVL or RTX PRO 6000 Blackwell GPUs.

The architecture is hybrid: all GPU compute sits in immersion tanks, while networking, storage and management sit in air-cooled racks. The text speaks of twenty-four SmartPod EXO tanks and 2,688 GPUs; the bill of materials lists 12 SmartPod EXO TwinTank S100 units, 40,000 litres of ENEOS Type H fluid and 5 APC 42U racks. A dedicated network rack holds Spectrum-X switches and a combined storage and management rack holds storage platforms and orchestration nodes.

The tech mix: GPU NVIDIA H200 NVL (141 GB memory, 600 W TDP), server Atlas 1.8 SP5-D 3OU 21-inch (dual AMD EPYC), tank SmartPod EXO TwinTank (99.999% SLA with full redundancy, 35 °C FWS inlet and fluid setpoint up to 45 °C) and fluid ENEOS Type H (meets the OCP over-300 °C spontaneous auto-ignition standard, low viscosity).

The data centre set-up section shows facility water supply (35 °C inlet), piping, power and cabling, and the tap-off scheme from the main busbar to a secondary busbar and to the SmartPods. The document ends with detailed part-numbered bills of materials for cooling, compute, network and power (PDUs, cables, optics). It is a manufacturer reference design and contains no measured PUE or energy data.

Key points

  1. A 2 MW AI-ready hybrid architecture: compute in immersion, networking and storage in air-cooled racks.
  2. The immersion tanks hold up to 2,688 GPUs.
  3. Bill of materials: 12 SmartPod EXO TwinTank S100, 40,000 L ENEOS Type H, 5 APC NetShelter 42U racks.
  4. SmartPod EXO TwinTank: full-redundancy (HA) 99.999% SLA; 35 °C FWS inlet, fluid setpoint up to 45 °C.
  5. GPU: NVIDIA H200 NVL, 141 GB memory, 600 W TDP.
  6. ENEOS Type H fluid meets the OCP over-300 °C spontaneous auto-ignition standard and has low viscosity.
  7. Per tank, 5 H200 NVL servers and 9 RTX PRO 6000 servers; PDU 400 V, 3-phase, 63 A, 43.6 kVA.
  8. The network rack uses Spectrum-X switches aligned with NVIDIA's AI Factory reference architecture.

Using it in design

  • In a hybrid design, calculate the heat load of the air-cooled racks separately: networking, storage and management sit outside immersion.
  • Design for 35 °C facility water inlet and up to 45 °C fluid setpoint to evaluate dry-cooler-led heat rejection.
  • Carry PDU count per tank and the 400 V 3-phase 63 A supply into the power distribution scheme (main busbar, secondary busbar, SmartPod).
  • In fluid selection, check spontaneous ignition, viscosity and oxidation stability for fire and pump energy.
  • Put optical and copper cable, patch panel and transceiver quantities from the bill of materials into the cabling budget.

Who should read it

Designers, system integrators and investors planning immersion-cooled AI clusters.

Document contents

  1. Reference design
  2. Technology set up
  3. Tech-mix
  4. Datacenter set up
  5. Datasheets / SKUs

Related standards

  • OCP immersion fluid requirements

Publication details

Authors
Submer; 2CRSi
Publisher
Submer
Year
2026
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Vendor reference design on submer.com; no open licence stated

Citation

Submer; 2CRSi (2026). Reference Design: AI infrastructure ready to deploy - Hybrid liquid cooling architecture for scalable AI inference (2 MW). Submer. https://submer.com/wp-content/uploads/2026/04/ai-inferencing-reference-design.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.