White Paper: Novel Low-Carbon Material Assessment Framework, Version 1.0 (July 2026)

Open Compute Project Foundation · Josefine A. Olsson (UC Davis), Maria Abadie (Google) et al.

Summarises a Google and UC Davis framework used to decide whether a novel low-carbon cement or concrete should be incubated, piloted or deployed in data centre construction. It is a reference for embodied-carbon decisions on slabs, foundations and precast elements.

CC BY-SA 4.0: share with attribution under the same licence

On this page

Overview

The paper notes that, for data-centre owners and contractors pursuing sustainability goals, a large share of Scope 3 emissions comes from the embodied carbon of construction materials, with concrete a key contributor. Many low-carbon cement and concrete technologies exist, but there is no standardised, efficient way to compare them. The framework is a systematic method developed in collaboration between Google and the University of California, Davis (UC Davis) and is based on a separate full technical report.

The difficulty it addresses is balancing three often competing criteria: environmental impact, material performance and feasibility. A low-carbon material may not meet durability standards, and a high-performing alternative may be costly or rely on a fragile supply chain. The framework is meant for early to mid-stage technologies and exposes research gaps, risks and technology readiness. The user first applies their own initial screening (Step 1), then moves on to the detailed evaluation (Step 2).

The detailed evaluation is a series of questions in three focus areas. Environmental questions cover the method used to quantify emissions and other burdens, performance questions cover engineering properties and conformance with standards, and feasibility questions cover scalability, safety, supply-chain resilience and regulation. Each question is answered low, medium or high risk; a high answer on a red-flag question means rejection, and where information is missing the evaluator selects IM/uncertain, which marks a gap to close during incubation or piloting. The method borrows from NASA's Technology Readiness Levels and the US DOE Adoption Readiness Level.

Results map to risk, uncertainty and readiness: below 4 shelve or reject; 5-6 incubate; 7-8 pilot; 9 deploy. The case study evaluates limestone calcined clay cement (LC3: about 15% limestone, 30% calcined clay, 5% gypsum and 50% clinker) for the US market, giving readiness 7 for environmental impact, 8 for material performance and 5 for feasibility. Studies of LC3 produced in California show a 36-40% reduction in GHG emissions compared with conventional cement.

Key points

  1. Three evaluation criteria: environmental impact, material performance and feasibility (scalability, safety, supply chain, regulation).
  2. Each question is answered low, medium or high risk; a high answer on a red-flag question means the product is rejected.
  3. Missing information is marked IM/uncertain and tracked as a gap to close during incubation or piloting.
  4. The method builds on NASA Technology Readiness Levels and the US DOE Adoption Readiness Level.
  5. Workflow: initial screening (Step 1), detailed evaluation (Step 2), then incubation, piloting and deployment (Steps 3-5).
  6. Suggested mapping: readiness below 4 shelve or reject, 5-6 incubate, 7-8 pilot, 9 deploy.
  7. LC3 example: about 15% limestone, 30% calcined clay, 5% gypsum and 50% clinker; 36-40% GHG reduction for LC3 produced in California.
  8. LC3 readiness levels: environmental impact 7, material performance 8, feasibility 5 (medium risk).
  9. US barriers for LC3 are permitting for low-kaolin clays, infrastructure and supply chain, investment in kiln adjustments, and workforce training.

Using it in design

  • When a low-carbon cement or concrete is proposed for slabs, foundations and precast elements, use the three-criterion question list as a supplier information form and track information gaps as a separate list.
  • Make red-flag questions (for example standards conformance or safety) the first screening criteria and remove from the project materials list any material that returns a high-risk answer.
  • Apply materials at readiness 7-8 first in a pilot element (for example a small slab section) to collect long-term durability data.
  • Include conformance with standards such as ASTM C595 and ASTM C618, and local specification approvals, in the structural design and approval process.
  • For the embodied-carbon target, request a product-specific environmental product declaration (EPD) or life cycle study and check the scope of the calculation (for example cradle to gate).

Who should read it

Data-centre owners and developers, structural and construction engineers, sustainability managers and cement and concrete suppliers.

Document contents

  1. Introduction
  2. Compliance with Open Compute Project Tenets
  3. Navigating the Low Embodied Carbon Material Landscape
  4. A Systematic Approach to Risk & Readiness (initial screening, detailed evaluation, scoring)
  5. Case Study: De-Risking a Novel Material (LC3)
  6. Conclusion and references

Related standards

  • OCP Report: Field Pilot of Low Carbon Concrete
  • OCP Embodied Carbon Disclosure Base Specification

Read the document

ocp-dcf-novel-low-carbon-material-framework-2026.pdf

PDF · 0.9 MB · English

CC BY-SA 4.0: share with attribution under the same licence

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Josefine A. Olsson (UC Davis); Maria Abadie (Google); Priya Chhiba (Google); Sabbie A. Miller (UC Davis)
Publisher
Open Compute Project Foundation
Year
2026
Document number
Version 1.0
Document language
English
Source type
Industry body
Access
Open licence (downloadable)
Licence
CC BY-SA 4.0: share with attribution under the same licence
Licence evidence
www.opencompute.org
Original licence note

Creative Commons Attribution-ShareAlike 4.0 International; licence verified from the licence statement in the document itself. Attribution to the authors and publisher is kept; adaptations must keep the same licence.

Citation

Josefine A. Olsson (UC Davis); Maria Abadie (Google); Priya Chhiba (Google); Sabbie A. Miller (UC Davis) (2026). White Paper: Novel Low-Carbon Material Assessment Framework, Version 1.0 (July 2026). Open Compute Project Foundation. Version 1.0. https://www.opencompute.org/documents/ocp-white-paper-novel-material-framework-final-pdf/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.