Technical guideFree to read2025

Erosion and Corrosion in Liquid Cooling Systems: Investigating Velocity-Dependent Degradation Mechanisms (OCP EMEA Summit 2025)

Open Compute Project Foundation · Christy Gonis, Reza Najjari

A CoolIT presentation at the OCP EMEA Summit 2025 reporting early results of a programme to find safe coolant velocity limits in single-phase direct liquid cooling loops.

On this page

Overview

This presentation by Christy Gonis and Reza Najjari, given in the Liquid Cooling track of the OCP EMEA Summit 2025 in Dublin, describes early results of a programme run by CoolIT. The programme aims to find safe coolant velocity limits in single-phase direct liquid cooling (DLC) loops.

The deck first reviews published velocity limits for copper: the OCP OAI liquid-cooling guidance gives 1-2 L/min per cold plate; the Copper Development Association gives 1.5-2.4 m/s for cold water and 0.6-0.9 m/s for water above 60 C; another source gives 2 m/s cold and 0.5 m/s hot. That these values differ from one another shows that a common empirical basis is lacking in the industry.

The mechanisms section explains erosion, corrosion and their combined acceleration: damage accelerates sharply above a system-specific critical flow velocity or critical wall shear stress when erosion combines with corrosion. The test method uses impinging-jet flow loops on copper coupons with CFD to derive wall shear stress, and 384 data points were collected in the first round. Indicators tracked include azole inhibitor depletion, copper particles, erosion depth, weight loss and roughness.

Preliminary results at 5 m/s with passivated copper, in heated and room-temperature loops, showed no measurable weight change after more than 10 days, but visual differences appeared after about 3 days and surface changes after 146-318 hours. The talk stresses the need for empirical industry data to set DLC velocity guidance. The results are preliminary and should not be read as a final design limit.

Key points

  1. Published limits cited: OCP OAI 1-2 L/min per cold plate; Copper Development Association 1.5-2.4 m/s cold water and 0.6-0.9 m/s above 60 C; another source 2 m/s cold and 0.5 m/s hot.
  2. Damage accelerates sharply above a system-specific critical flow velocity or wall shear stress when erosion combines with corrosion.
  3. Method: impinging-jet flow loops on copper coupons with CFD-derived wall shear stress; 384 data points in the first round.
  4. Heated and room-temperature loops at 5 m/s with passivated copper showed no measurable weight change after 10+ days.
  5. Visual differences appeared after about 3 days and surface changes after 146-318 hours.
  6. Indicators tracked include azole inhibitor depletion, copper particles, erosion depth, weight loss and roughness.
  7. The talk calls for empirical industry data to set DLC velocity guidance.

Using it in design

  • In pipe and manifold sizing rules, check coolant velocity against a configurable copper limit, warning above about 1.5 m/s for warm-water loops and at a lower threshold above 60 C.
  • Record the inhibitor type for wetted copper surfaces.
  • State the source of the velocity limit used (OCP, Copper Development Association and so on) in the design report.
  • Use the preliminary results as justification for a cautious approach, not as a firm limit.

Who should read it

Mechanical engineers sizing direct liquid cooling loops and cold plate or CDU designers.

Related standards

  • OCP cold plate loop requirements

Publication details

Authors
Christy Gonis; Reza Najjari
Publisher
Open Compute Project Foundation
Year
2025
Document number
OCP EMEA Summit 2025, Liquid Cooling track
Event
OCP EMEA Summit 2025, Dublin
Document language
English
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Christy Gonis; Reza Najjari (2025). Erosion and Corrosion in Liquid Cooling Systems: Investigating Velocity-Dependent Degradation Mechanisms (OCP EMEA Summit 2025). Open Compute Project Foundation. OCP EMEA Summit 2025, Liquid Cooling track. OCP EMEA Summit 2025, Dublin. https://drive.google.com/file/d/1xSs1eUGk2p3Pvv6PR_T_7O5PosnBe3sW/view

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.