Technical guidePDF2020

Hose and Manual Couplings - Best Practices, Revision 01 (OCP ORv3 Blind Mate Liquid Cooling Interfaces Group)

Open Compute Project Foundation · Jeff Grau (Parker, editor), Michael Gonzalez (CEJN, editor) et al.

An OCP reference guide to selecting flexible hoses and manual quick couplings in liquid-cooled racks and row distribution. It covers construction, spillage, pressure drop and rating, permeation, ozone resistance, bend radius, working life, barb terminations, flame resistance, burst and fail-safe practice, and storage and shipping effects.

CC BY-SA 4.0: share with attribution under the same licence

On this page

Overview

The paper was written by the OCP ORv3 Blind Mate Liquid Cooling Interfaces Group to give the community shared reference knowledge. At rack level, large manual hoses and couplings complete the closed circuit between the door heat exchanger, the reservoir and pumping unit (RPU/CDU) and the manifolds. A hose is reinforced flexible piping made of an inner tube, a tension-bearing reinforcement and an outer cover, and is distinguished from tubing of homogeneous material. Hoses for computer coolant are typically low-pressure rubber products with fibre reinforcement.

The coupling section describes straight-through (valveless), poppet-valve and spill-free flat-face (dry break) types; the spill-free type is the most common in thermal-control applications. Connection force depends on coupling size, valve type and internal pressure, and flat-face designs need more force than poppet types. Couplings are made of stainless steel, nickel- or chrome-plated brass and hard-anodised aluminium; the most common seal material is EPDM. Typical spillage on disconnect is at most 0.10 cc for a 3/4 inch dry-break coupling (ISO 18869:2017 for test methods). To prevent cross-connection, supply and return manifolds use opposite male and female halves; red and blue colour coding is an extra measure but not foolproof on its own.

Hose properties covered include durability and resistance to external forces (sharp edges, abrasion, cut-resistant braid covers), permeation of water-based coolant (non-polar polymers such as butyl and EPDM resist it; silicone hose is problematic for closed loops because of high permeation), oxygen ingress, ozone resistance (EPDM is naturally resistant), hose-assembly tensile strength, minimum bend radius and working life. Hose selection follows the STAMP method (size, temperature, application, media, pressure); life is hard to predict and is monitored by routine inspection.

Pressure ratings most commonly rest on a 4:1 safety factor from burst testing; 3:1 is the lowest most suppliers will offer. Flame-resistance references include UL 94, UL 224 (VW-1), UL 723 and ISO 15540. For storage and shipping, hose should be kept cool, dry and dark with end caps in place; coolant-filled shipments must avoid freezing, and in dry shipments the assembly technician must keep the environment clean. The document dates from 2020.

Key points

  1. Coupling pressure ratings are most commonly based on a 4:1 burst safety factor; 3:1 is the lowest factor to consider.
  2. Non-polar polymers such as butyl and EPDM resist permeation of water-based coolants; EPDM is also naturally ozone resistant and the most common seal material.
  3. Silicone hose is problematic for closed loops because of high permeation and suits open loops that are continually replenished.
  4. Supply and return manifolds normally use opposite male and female coupling halves (and red/blue colour coding) to prevent cross-connection.
  5. Typical spillage on disconnect is at most 0.10 cc for a 3/4 inch dry-break coupling; ISO 18869:2017 is the reference for testing and pressure drop.
  6. Flame-resistance references include UL 94, UL 224 (VW-1) and ISO 15540; burst testing refers to ASTM D380, ozone to ASTM D380 and D1149.
  7. Hose selection follows the STAMP method: size, temperature, application, media, pressure.
  8. The most common coupling materials are stainless steel, nickel- or chrome-plated brass and hard-anodised aluminium, chosen against the coolant and other loop metals to avoid galvanic problems.
  9. A hose with visible reinforcement, bulges or soft spots should be replaced.
  10. For terminations, soft-sealed threads such as ISO 6149-1 and ISO 1179-1 are preferred.

Using it in design

  • In the hose and coupling specification, derive maximum operating pressure from pump capacity or relief-valve setting and require at least a 3:1, preferably 4:1, burst safety factor.
  • For water or PG coolant, choose low-permeation hose such as EPDM or butyl and EPDM seals; avoid silicone hose in closed loops.
  • Prevent cross-connection by design with opposite male and female coupling halves and colour coding on supply and return manifolds.
  • Include every coupling in the total pressure-drop calculation, choosing high flow-coefficient (Cv) types and requesting values at peak flow tested per ISO 18869:2017.
  • Check hose routing for sharp edges, vibrating parts and minimum bend radius; where a fire rating is needed, write UL 94, UL 224 or ISO 15540 compliance into the specification.
  • Define in the shipping and storage procedure end caps, cool and dark storage, and freeze protection for filled hoses.

Who should read it

Mechanical engineers designing liquid-cooled racks and distribution, procurement and quality teams, and hose and coupling manufacturers.

Document contents

  1. Introduction and rack-level connections
  2. Hose Basics (thermoplastic and rubber hose, reinforcement, manufacturing)
  3. Basics of Manual Coupling Construction (types, connection force, materials, seals, end connections, cross-connection, spillage, pressure drop, pressure rating, fluid compatibility)
  4. Hose Properties (durability, permeation, oxygen ingress, ozone resistance, tensile strength, bend radius, working life)
  5. Manual Coupling Hose Termination Options and Considerations (barb connections and others)
  6. Flame Resistance
  7. Pressure/Burst and Fail Safe Considerations
  8. Storage/Shipping Considerations (environmental impact, shipping with coolant)
  9. Conclusion

Related standards

  • UL 94
  • UL 224
  • ISO 15540
  • ASTM E96

Read the document

ocp-hose-manual-couplings-best-practices.pdf

PDF · 0.7 MB · English

CC BY-SA 4.0: share with attribution under the same licence

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Jeff Grau (Parker, editor); Michael Gonzalez (CEJN, editor); Parker, SafeWay, CEJN, Eaton and Facebook contributors
Publisher
Open Compute Project Foundation
Year
2020
Document number
Revision 01
Document language
English
Source type
Industry body
Access
Open licence (downloadable)
Licence
CC BY-SA 4.0: share with attribution under the same licence
Licence evidence
www.opencompute.org
Original licence note

Creative Commons Attribution-ShareAlike 4.0 International; licence verified from the licence statement in the document itself. Attribution to the authors and publisher is kept; adaptations must keep the same licence.

Citation

Jeff Grau (Parker, editor); Michael Gonzalez (CEJN, editor); Parker, SafeWay, CEJN, Eaton and Facebook contributors (2020). Hose and Manual Couplings - Best Practices, Revision 01 (OCP ORv3 Blind Mate Liquid Cooling Interfaces Group). Open Compute Project Foundation. Revision 01. https://www.opencompute.org/documents/ocp-manual-couplings-at-hoses-pdf/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.