Technical guideFree to read2024

Castrol Coolant Safety Study with Intel's Open IP Immersion Cooling Solutions for Data Center Deployment

Original title Castrol Coolant Safety Study with Intel’s Open IP Immersion Cooling Solutions for Data Center Deployment

Intel / Castrol / Foxconn Industrial Internet / Gospower

An Intel and Castrol technical paper presents a test method showing no flame from overvoltage, overload and short-circuit failures of a 3500 W CRPS power supply immersed in hydrocarbon Castrol ON DC 15 fluid.

On this page

Overview

The paper opens by noting that AI workloads raise CPU and GPU TDP and that cooling takes close to 40% of data centre energy. Fluorinated fluids are being phased out in Europe and the US for high GWP and hazard risk; hydrocarbon fluids have good thermal properties but the industry worries about flash point. To fill the gap, Intel, Castrol, Foxconn Industrial Internet and Gospower developed safety test methods for hydrocarbon fluid.

Tests used Intel's 2U 3 kW AAIC Open IP immersion tank with Castrol ON DC 15 fluid (kinematic viscosity about 7.79 cSt at 40 °C, open cup flash point 168 °C). Rather than relying only on standard cup flash point, the safety of the liquid and of the liquid-vapour-air mixture at the surface was measured by igniting flame, heat, arc and spark when a 3500 W CRPS power supply fails. Flow rates were 1.2 L/min and 0 L/min (static).

Six power supply failure tests were run: overvoltage (266 to 285 VAC, 100 cycles), over-temperature protection (from 50 °C at 1 °C per five minutes, protection engaged at 65 °C), main and secondary side overload (main side 180%, secondary side up to 230%), slow charge (0.03 V/s), short circuit and circuit breaker trip (six breakers from different suppliers). None produced flame. The conclusion is that the fluid is safe in this specific environment; safety depends not on the liquid alone but on the right environment, operation, fire protection and fluid health monitoring.

Key points

  1. Cooling takes close to 40% of data centre energy.
  2. Test fluid Castrol ON DC 15: about 7.79 cSt at 40 °C, open cup flash point 168 °C.
  3. Tank: Intel 2U AAIC, 3 kW cooling capacity; flow rates 1.2 L/min and static.
  4. Power supply 3500 W CRPS; per Baidu Cloud data, PSU failures are 11% of server hardware failures.
  5. Overvoltage test: 266 to 285 VAC, 10 s each, 100 cycles; no flame.
  6. Over-temperature protection engaged at 65 °C; at 180% main and 230% secondary overload no flame occurred.
  7. Slow charge (0.03 V/s), short circuit and six suppliers' circuit breakers produced no flame.
  8. Against air cooling, average PSU temperature was 8.04-14.01 °C lower in immersion.
  9. Fluid health monitoring methods listed include particle counter, water content, FT-IR and H-NMR.

Using it in design

  • When selecting hydrocarbon immersion fluid, look beyond flash point to tank-level safety tests under power supply failure scenarios (overvoltage, overload, short circuit).
  • Design natural or mechanical ventilation to limit the vapour-air mixture at the tank surface; limiting one of heat, combustible vapour or oxygen is enough to inhibit flame.
  • Add fluid health monitoring (particles, water, organic contamination, mixing), online or offline, to the operations plan.
  • Plan fire suppression and fluid storage to local regulations at data centre scale.
  • Treat the results as valid for the specific fluid, tank and PSU combination and repeat them with your own components.

Who should read it

Engineers designing or operating hydrocarbon single-phase immersion cooling and teams doing fire safety and risk assessment.

Document contents

  1. Executive summary
  2. Introduction to Castrol ON single-phase immersion cooling
  3. Test methods for single-phase immersion cooling
  4. Immersion cooling power safety test classifications
  5. Conclusion
  6. Further information

Publication details

Authors
Intel / Castrol / Foxconn Industrial Internet / Gospower
Publisher
Intel / Castrol / Foxconn Industrial Internet / Gospower
Year
2024
Document number
838751
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public manufacturer source inspected. No document-specific redistribution permission established. Metadata and original brief summaries only; local downloads are research evidence, not a redistribution package.

Citation

Intel / Castrol / Foxconn Industrial Internet / Gospower (2024). Castrol Coolant Safety Study with Intel’s Open IP Immersion Cooling Solutions for Data Center Deployment. Intel / Castrol / Foxconn Industrial Internet / Gospower. 838751. https://cdrdv2-public.intel.com/838751/838751_Intel_Open_IP_Immersion_Cooling_Solutions_for_Data_Center_Deployment_Study.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.