White paperFree to read2020

An Advanced Liquid Cooling Rack Design for Data Center (JD.COM and Intel, OCP White Paper)

Original title White Paper: An Advanced Liquid Cooling Rack Design for Data Center (JD.COM and Intel), v0.8

Open Compute Project Foundation · Ruiyu Sun, Yongwei Li, Shifeng Wang, Guofeng Chen, Qingming Fu (JD.COM), Jun Zhang, Nishi Ahuja, Yuyang Xia, Hongxing Zhou, Jinwen Yang, Qing Qiao (Intel)

A version 1.0 OCP white paper by JD.COM and Intel describing a redundant two-CDU direct-to-chip liquid cooling rack architecture, hose tests and node-level leak detection, with design figures.

On this page

Overview

Published in June 2020, the white paper describes the architecture of JD.COM's direct-to-chip (D2C) liquid cooling rack system and the lessons from field practice. The system uses two CDUs; each can meet the maximum cooling load alone and runs at 50% load in normal operation. Inside a CDU sit the main pump, a 200 µm filter, a pre-charged buffer tank, a plate heat exchanger and an independent controller.

Design parameters are explicit: inner loop pure water at 57 m3/h with inlet up to 45°C and a 6-7°C temperature difference; outer loop water with 40% ethylene glycol at 65 m3/h with inlet up to 35°C; rated capacity 400 kW with a 5-20% design margin. The buffer tank is pre-charged at 0.5-0.75 bar. Piping is 304 stainless steel designed for at least 6 years of normal operation. Operating conditions: supply water 20-45°C, node inlet 0.6-3 bar, altitude up to 2,000 m.

The engineering-lessons section covers a CPU cold plate performance index, memory cooling methods (liquid loop, heat pipe, fin type), a nine-item test of five hose types (BIIR, reinforced and unreinforced EPDM, PTFE, FEP), quick disconnects and node-level leak detection. The coolant water-quality report is deferred to a later publication; the document is an architecture reference contributed to OCP.

Key points

  1. Two CDUs give redundancy; each can carry full load and normally runs at 50%.
  2. The heat exchanger is rated 400 kW: inner loop 57 m3/h at ≤45°C, outer loop 65 m3/h at ≤35°C, with 6-7°C ΔT on both.
  3. Filter rating is 200 µm; buffer tank pre-charge 0.5-0.75 bar; pipe material 304 stainless steel.
  4. Operating conditions: supply water 20-45°C, node inlet 0.6-3 bar, humidity 10-90% RH, altitude ≤2,000 m, temperature change rate ≤20°C/h.
  5. In cold plate tests the common flow rate is 1 L/min; design 6 scores best at 0.5-1 L/min, design 5 at 1.2 L/min and design 1 at 1.5 L/min.
  6. In hose tests PTFE and FEP failed the deformation test, sample 03 (unreinforced EPDM) failed the 1 MPa static pressure test; daily infiltration was 0.020% for FEP and 0.223% for BIIR.
  7. Loops above 0.45 MPa should use plastic or reinforced rubber pipe.
  8. The node leak sensor gives about 1.65 V on a 3.3 V board; thresholds of 1.4-2.0 V define normal, low voltage signals a leak and high voltage a sensor fault.
  9. A plastic quick disconnect passed a no-drip connect and disconnect test at 0.8 MPa.

Using it in design

  • For a redundant CDU architecture size each CDU for full load alone and reflect the 50% normal load in pump selection.
  • Use the ≤45°C inner-loop inlet and 6-7°C ΔT as a starting point for CDU heat exchanger selection.
  • Check operating pressure when choosing hoses; above 0.45 MPa use reinforced or plastic pipe, and weigh infiltration rates (low for FEP and PTFE).
  • Provide leak detection both in the drainage trough under pipework and at the server node, with BMC voltage thresholds that separate a sensor fault from a leak.
  • Compare cold plates with a combined flow, pressure-drop and thermal-resistance index at the design flow (1 L/min in the example).

Who should read it

System engineers designing direct-to-chip rack and CDU architectures, and server and cold plate designers.

Document contents

  1. Introduction
  2. Liquid cooling rack system architecture and design (CDU, pump, filtering, pressure stabilization, heat exchanger, leak detection, pipeline, manifold, IT equipment, environmental requirements)
  3. JD engineering practice and key learnings (CPU and memory cold plate, pipeline, connection, mini-manifold, server node leak detection, coolant requirement)

Related standards

  • OCP Cold Plate Cooling Loop Requirements

Publication details

Authors
Ruiyu Sun, Yongwei Li, Shifeng Wang, Guofeng Chen, Qingming Fu (JD.COM); Jun Zhang, Nishi Ahuja, Yuyang Xia, Hongxing Zhou, Jinwen Yang, Qing Qiao (Intel)
Publisher
Open Compute Project Foundation
Year
2020
Document number
v0.8
Document language
English
Source type
Industry body
Access
Free to read
Licence
OCPHL-P: OCP hardware licence; redistribution permitted
Original licence note

License section: contributions under OCP CLA; usage governed by OCP Hardware License - Copyleft (OCPHL Reciprocal). Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Ruiyu Sun, Yongwei Li, Shifeng Wang, Guofeng Chen, Qingming Fu (JD.COM); Jun Zhang, Nishi Ahuja, Yuyang Xia, Hongxing Zhou, Jinwen Yang, Qing Qiao (Intel) (2020). White Paper: An Advanced Liquid Cooling Rack Design for Data Center (JD.COM and Intel), v0.8. Open Compute Project Foundation. v0.8. https://www.opencompute.org/documents/an-advanced-liquid-cooling-design-for-data-center-final-v3-1-pdf/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.