An Advanced Liquid Cooling Rack Design for Data Center (JD.COM and Intel, OCP White Paper)
Original title White Paper: An Advanced Liquid Cooling Rack Design for Data Center (JD.COM and Intel), v0.8
Open Compute Project Foundation · Ruiyu Sun, Yongwei Li, Shifeng Wang, Guofeng Chen, Qingming Fu (JD.COM), Jun Zhang, Nishi Ahuja, Yuyang Xia, Hongxing Zhou, Jinwen Yang, Qing Qiao (Intel)
A version 1.0 OCP white paper by JD.COM and Intel describing a redundant two-CDU direct-to-chip liquid cooling rack architecture, hose tests and node-level leak detection, with design figures.
On this page
Overview
Published in June 2020, the white paper describes the architecture of JD.COM's direct-to-chip (D2C) liquid cooling rack system and the lessons from field practice. The system uses two CDUs; each can meet the maximum cooling load alone and runs at 50% load in normal operation. Inside a CDU sit the main pump, a 200 µm filter, a pre-charged buffer tank, a plate heat exchanger and an independent controller.
Design parameters are explicit: inner loop pure water at 57 m3/h with inlet up to 45°C and a 6-7°C temperature difference; outer loop water with 40% ethylene glycol at 65 m3/h with inlet up to 35°C; rated capacity 400 kW with a 5-20% design margin. The buffer tank is pre-charged at 0.5-0.75 bar. Piping is 304 stainless steel designed for at least 6 years of normal operation. Operating conditions: supply water 20-45°C, node inlet 0.6-3 bar, altitude up to 2,000 m.
The engineering-lessons section covers a CPU cold plate performance index, memory cooling methods (liquid loop, heat pipe, fin type), a nine-item test of five hose types (BIIR, reinforced and unreinforced EPDM, PTFE, FEP), quick disconnects and node-level leak detection. The coolant water-quality report is deferred to a later publication; the document is an architecture reference contributed to OCP.
Key points
- Two CDUs give redundancy; each can carry full load and normally runs at 50%.
- The heat exchanger is rated 400 kW: inner loop 57 m3/h at ≤45°C, outer loop 65 m3/h at ≤35°C, with 6-7°C ΔT on both.
- Filter rating is 200 µm; buffer tank pre-charge 0.5-0.75 bar; pipe material 304 stainless steel.
- Operating conditions: supply water 20-45°C, node inlet 0.6-3 bar, humidity 10-90% RH, altitude ≤2,000 m, temperature change rate ≤20°C/h.
- In cold plate tests the common flow rate is 1 L/min; design 6 scores best at 0.5-1 L/min, design 5 at 1.2 L/min and design 1 at 1.5 L/min.
- In hose tests PTFE and FEP failed the deformation test, sample 03 (unreinforced EPDM) failed the 1 MPa static pressure test; daily infiltration was 0.020% for FEP and 0.223% for BIIR.
- Loops above 0.45 MPa should use plastic or reinforced rubber pipe.
- The node leak sensor gives about 1.65 V on a 3.3 V board; thresholds of 1.4-2.0 V define normal, low voltage signals a leak and high voltage a sensor fault.
- A plastic quick disconnect passed a no-drip connect and disconnect test at 0.8 MPa.
Using it in design
- For a redundant CDU architecture size each CDU for full load alone and reflect the 50% normal load in pump selection.
- Use the ≤45°C inner-loop inlet and 6-7°C ΔT as a starting point for CDU heat exchanger selection.
- Check operating pressure when choosing hoses; above 0.45 MPa use reinforced or plastic pipe, and weigh infiltration rates (low for FEP and PTFE).
- Provide leak detection both in the drainage trough under pipework and at the server node, with BMC voltage thresholds that separate a sensor fault from a leak.
- Compare cold plates with a combined flow, pressure-drop and thermal-resistance index at the design flow (1 L/min in the example).
Who should read it
System engineers designing direct-to-chip rack and CDU architectures, and server and cold plate designers.
Document contents
- Introduction
- Liquid cooling rack system architecture and design (CDU, pump, filtering, pressure stabilization, heat exchanger, leak detection, pipeline, manifold, IT equipment, environmental requirements)
- JD engineering practice and key learnings (CPU and memory cold plate, pipeline, connection, mini-manifold, server node leak detection, coolant requirement)
Related standards
- OCP Cold Plate Cooling Loop Requirements
Publication details
- Authors
- Ruiyu Sun, Yongwei Li, Shifeng Wang, Guofeng Chen, Qingming Fu (JD.COM); Jun Zhang, Nishi Ahuja, Yuyang Xia, Hongxing Zhou, Jinwen Yang, Qing Qiao (Intel)
- Publisher
- Open Compute Project Foundation
- Year
- 2020
- Document number
- v0.8
- Document language
- English
- Source type
- Industry body
- Access
- Free to read
- Licence
- OCPHL-P: OCP hardware licence; redistribution permitted
Original licence note
License section: contributions under OCP CLA; usage governed by OCP Hardware License - Copyleft (OCPHL Reciprocal). Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Ruiyu Sun, Yongwei Li, Shifeng Wang, Guofeng Chen, Qingming Fu (JD.COM); Jun Zhang, Nishi Ahuja, Yuyang Xia, Hongxing Zhou, Jinwen Yang, Qing Qiao (Intel) (2020). White Paper: An Advanced Liquid Cooling Rack Design for Data Center (JD.COM and Intel), v0.8. Open Compute Project Foundation. v0.8. https://www.opencompute.org/documents/an-advanced-liquid-cooling-design-for-data-center-final-v3-1-pdf/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.