Open Rack V3 HPR V2 12kW PSU Specification, Rev 1.0.0 (12 June 2026)
Open Compute Project Foundation · Jingjing Sun, Mohammed Alisa et al.
Specification of the 12 kW AC-to-50 V PSU module used in ORv3 high-power-rack (HPR) V2 power shelves, the building block of the existing 72 kW shelf. Beyond efficiency and power-quality limits it defines PSU-to-BBU hand-off signalling on AC loss and a pulse-load management mode for GPU loads with repetitive peaks, which matters for upstream UPS and generator sizing.
On this page
Overview
The specification defines single-phase 48 V PSUs that fit the 48 V power shelf. The power shelf includes several PSUs with at least N+1 redundancy. Output is 50 V nominal with an adjustable range; the document calls this a narrow-range 48 V architecture, which avoids oversized voltage and current design compared with ORv2's 40-60 V range, enables 4:1 fixed-ratio converters and 12 V PoL converters, and lets power flow naturally without software dependency. The initial OCP release is dated 12 June 2026.
Input and efficiency requirements are: 12 kW output; 200-277 VAC nominal, +/-10%; the PSU supplies output power over 180-305 VAC and 47-63 Hz, with the full 12 kW from 218-305 VAC and power derated to 10 kW at 180-218 VAC. Efficiency is measured at 230-277 V input with fans connected, at 25 degC ambient after 30 minutes at full load: over 97.5% peak and over 96.5% minimum across 30-100% load, and at least 94% at 10-30% load. Active power factor correction is included: power factor above 0.99 at 80-100% load and above 0.98 at 20-80% load; input current harmonic distortion at most 5% at 30-100% load.
Output voltage is 50 V at no load and 49 V at full load (1 V default droop, 48.5 V at 150% load); ripple is at most 500 mV peak to peak. Hold-up time after AC is lost is 20 ms at 100% load and 13.33 ms at 150% load.
On detecting AC loss the PSU asserts AC_Loss_L after a 4-5 ms validation delay so that the BBU shelf takes over; a second condition keeps remaining bulk-capacitor energy above 5 ms to let the BBU ramp up. When AC returns, the signal is released after at least 500 ms; to avoid BBU over-discharge in single-fault cases it is released after 300 seconds. The rack monitor can force BBUs to discharge while mains is present by toggling AC_Loss_L over Modbus.
The pulse load management mode is defined for GPU-based loads that may have repetitive peaks: the PSU must carry repetitive pulse loads while keeping output regulation and the input power limit, without triggering the BBU; the requirement is 140% (50 ms moving average), 160% (400 us) and 100% (1 s and longer) average, and the PSU's maximum input power limit must be adjustable to system requirements. High-voltage bus capacitance is maximised as an energy buffer for pulse power, and if the bulk capacitor energy is depleted a Pulse_Mgmt_L signal asks the BBU to share the pulse load. The operating environment is -5 to +45 degC inlet air and 10-90% relative humidity.
Key points
- 12 kW output at a nominal 50 V; input 200-277 VAC nominal +/-10%, operating range 180-305 VAC and 47-63 Hz; full 12 kW from 218 VAC, 10 kW at 180-218 VAC.
- Output voltage is 50 V at no load and 49 V at full load.
- Peak efficiency above 97.5%; minimum efficiency 96.5% across 30-100% load and at least 94% at 10-30% load.
- Power factor above 0.99 at 80-100% load and above 0.98 at 20-80% load; input current THD at most 5% at 30-100% load.
- Hold-up time is 20 ms at 100% load and 13.33 ms at 150% load.
- On AC loss the PSU asserts AC_Loss_L after a 4-5 ms validation delay so the BBU shelf takes over; the signal is released at least 500 ms after AC returns.
- Pulse load: 140% (50 ms average) and 160% (400 us) peaks must be carried without triggering the BBU; the PSU maximum input power limit must be adjustable.
- AC inrush current is at most 60 A RMS (85 A peak); re-rush current after dropout is below five times steady-state current for under 2 ms.
- The power shelf must include at least N+1 PSU redundancy.
- Operating environment: inlet air -5 to +45 degC, relative humidity 10-90%.
Using it in design
- In upstream UPS and generator sizing, account for the GPU pulse load (140% and 160% peaks); the PSU can carry these peaks without triggering the BBU, but the upstream power fluctuation changes with the input power limit setting.
- Check the AC input range (180-305 VAC) against the facility distribution voltage; allow in capacity calculations for PSU power falling to 10 kW at 180-218 VAC.
- In loss and PUE calculations, enter PSU efficiency by load percentage: at least 96.5% at 30-100% load with 97.5% at peak, and at least 94% at 10-30% load.
- In BBU shelf integration, write the AC_Loss_L and Pulse_Mgmt_L signal connections and timings (4-5 ms validation delay, 20 ms hold-up, 500 ms release delay) into trip and transfer scenarios.
- Use the power factor (0.99) and THD (5%) values as inputs to upstream power-quality and harmonic calculations; carry the inrush (60 A RMS) and re-rush (five times, 2 ms) limits into protection coordination.
Who should read it
Electrical and hardware engineers designing ORv3 racks and power shelves, UPS and backup-power designers, and PSU and BBU manufacturers.
Document contents
- License
- Scope and glossary of acronyms
- Overview (narrow-range 48V architecture)
- Electrical Requirements (AC input, start-up, AC failure and recovery, input protection, inrush, efficiency, power factor, THD, output voltage, droop, ripple, dynamic response, hold-up time, PSU-BBU transition with AC_Loss_L, forced discharge, pulse load management, pulse power, output protections, current sharing, grounding, Y-cap, random timer, transition and synchronization, power system stability, connector, interoperability)
- Communication (firmware upgrades, metering accuracy, blackbox)
- Environment (temperature, humidity, gaseous contamination, altitude, acoustic noise, vibration and shock)
- Thermal
- Mechanical
- Reliability, manufacturing, quality and compliance
Related standards
- OCP ORv3 HPR V2 72kW Power Shelf
- OCP ORv3 BBU Shelf
- IEC 61000-3-2
Publication details
- Authors
- Jingjing Sun; Mohammed Alisa; David Sun; Wenying Zhang; Dmitriy Shapiro; John Fernandes; Ben Kim; Jaswanth Vutukury; Baby Neil Escuadro; Siu Lam; Bo Wen; Zibo Chen
- Publisher
- Open Compute Project Foundation
- Year
- 2026
- Document number
- Rev 1.0.0
- Document language
- English
- Source type
- Industry body
- Access
- Free to read
- Licence
- OWFa 0.9: Open Compute open specification licence; redistribution permitted
Original licence note
Section 1.1: contributions under Modified OWFa 0.9 (16 Oct 2024); usage under Modified OWFa 0.9 FSA. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Jingjing Sun; Mohammed Alisa; David Sun; Wenying Zhang; Dmitriy Shapiro; John Fernandes; Ben Kim; Jaswanth Vutukury; Baby Neil Escuadro; Siu Lam; Bo Wen; Zibo Chen (2026). Open Rack V3 HPR V2 12kW PSU Specification, Rev 1.0.0 (12 June 2026). Open Compute Project Foundation. Rev 1.0.0. https://www.opencompute.org/documents/open-rack-v3-hpr-v2-12kw-psu-module-spec-v1-0-0-pdf/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.