Solid State Transformer (SST) Specification: Medium Voltage to 800 VDC Power Conversion Platform, Revision 0.3.0 (effective 22 June 2026)

Open Compute Project Foundation · Google (J. Wang, S. Kim, S. Bal, K. Hao, D. Ristanovic, A. Upreti, J. Adrian, C. Peabody), Microsoft (E. Nasr, P. Patel, X. Feng) et al.

An early-draft black-box interface specification from Google, Microsoft and NVIDIA for megawatt-scale medium-voltage solid-state transformers that replace the line-frequency MV transformer and rectifier (and, with storage, can act as an MV-UPS) to feed 800 VDC distribution to AI racks. It is a key reference for evaluating 800 VDC facility architectures; many values are still marked TBD.

On this page

Overview

The scope defines a medium voltage solid-state transformer (MVSST) as a megawatt-scale power electronic converter that, coupled with energy storage, could function as a medium voltage uninterruptible power supply (MV-UPS). The MVSST replaces the conventional 50/60 Hz line-frequency MV transformer, rectifier units and, depending on architecture, energy storage. It uses medium- to high-frequency magnetics and wide-bandgap semiconductors such as SiC and GaN; the product is defined as a black box through its interfaces (mechanical, thermal, environmental, control, communications and behaviour expectations), and vendors fill the design target with their own engineering solutions.

The product has five components: power conversion, MVAC input (switchgear and filters, surge protection), LVDC output (switchgear and terminations), firmware, control and communications, and auxiliary power. Two input SKUs are defined: 13.8 kVac +/-10% at 5 MW, and 34.5 kVac +/-10% at 5 or 10 MW DC output, both 57-63 Hz with up to 5 Hz/s ROCOF.

Input power factor is above 0.99 at full load, 0.98 at load of 20% or more and above 0.95 below 20%. Harmonics follow IEEE 519 and IEC 61800-3 (C4). BIL is at least 110 kV at 13.8 kV and 150-200 kV at 34.5 kV. Short-circuit capability is given as 18-40 kA for 13.8 kV (about 104 kA asymmetrical) and 25-50 kA for 34.5 kV (about 130 kA asymmetrical); duration is TBD.

The output is an 800 Vdc unipolar system: +/-0.5% (switching ripple), +/-1% (static tolerance, 0-100% loading) and +/-3% (dynamic regulation). IT ground is floating or high-resistance grounded (HRG) with insulation monitoring and protection coordination. The recommended overload behaviour is 150% for 150 ms in constant-current mode for fault coordination (after which the SST may trip) and 120% for 5 s in constant-voltage mode; power-train efficiency is at least 98% at 50-100% utilisation.

Voltage ride-through (VRT) is based on references such as ERCOT, Fingrid, ITIC, IEEE 1547 and IEEE 2800: the SST is fully functional at 0.9-1.1 pu and 1.1-1.2 pu overvoltage; in LVRT range #1 it supplies 100% of rated output load while sourcing no more than nominal input current; in range #2 it draws no input current and coupled storage supplies the full load. Frequency ride-through is continuous at 58.8-61.2 Hz, with a minimum of 299 seconds at 57.0-58.8 and 61.2-61.8 Hz. MVAC load acceptance and rejection is recommended at about 20-50 MW/min for utility supply, with genset values TBD. Environmental requirements are NEMA 3R outdoor rating, a design life of 15+ years, -30 to 40 degC (derating above) and altitude up to 1000 m.

Key points

  1. Revision 0.3.0 is an early draft; many values are TBD, including short-circuit duration, genset and renewable ramp rates and grounding impedance.
  2. Two input SKUs: 13.8 kVac +/-10% at 5 MW, and 34.5 kVac +/-10% at 5 or 10 MW DC output; 57-63 Hz with up to 5 Hz/s ROCOF.
  3. Input power factor above 0.99 at full load, 0.98 at load of 20% or more and 0.95 below 20%; harmonics per IEEE 519 and IEC 61800-3 C4.
  4. Output is 800 Vdc unipolar with +/-1% static tolerance, +/-3% dynamic regulation and +/-0.5% switching ripple.
  5. IT ground is floating or high-resistance grounded with insulation monitoring and protection coordination.
  6. Recommended overload: 150% for 150 ms in constant-current mode and 120% for 5 s in constant-voltage mode; power-train efficiency at least 98% at 50-100% utilisation.
  7. VRT: fully functional at 0.9-1.1 pu and 1.1-1.2 pu; in LVRT range #1 input current is limited to nominal, in range #2 input current is zero and storage supplies the load.
  8. Frequency ride-through: continuous at 58.8-61.2 Hz; at least 299 seconds at 57.0-58.8 and 61.2-61.8 Hz.
  9. Recommended MVAC load acceptance and rejection: about 20-50 MW/min for utility; genset rates TBD.

Using it in design

  • In 800 VDC architecture evaluation, match the 13.8 kV (5 MW) and 34.5 kV (5 or 10 MW) input SKUs to the facility's medium-voltage level; carry short-circuit and BIL requirements into the switchgear specification.
  • When sizing the SST with energy storage (MV-UPS), use the grid voltage and frequency ride-through curves (ERCOT, Fingrid and others) and LVRT range #1 and #2 behaviour as inputs; set the storage capacity by the grid code you connect to.
  • Use the load acceptance and rejection rate between generator and grid (20-50 MW/min for utility) as the reference in control design; because genset rates are TBD, ask the supplier for values.
  • In LVDC distribution, reflect the 800 Vdc tolerance band (+/-1% static, +/-3% dynamic), overload coordination (150% for 150 ms, 120% for 5 s) and floating or high-resistance IT grounding in the protection design.
  • In site layout, account for the outdoor NEMA 3R unit size (10-20 ft x 8 ft x 8.5 ft), transport and serviceability limits and derating above 40 degC and 1000 m; record in the risk register that many values are TBD.

Who should read it

Electrical designers evaluating 800 VDC facility architectures and MV-UPS alternatives, grid-connection and protection engineers, and SST and power-electronics manufacturers.

Document contents

  1. License
  2. Compliance with OCP Tenets
  3. Scope
  4. Base product specifications (product internal compositions, MVAC and power rating configurations, LVDC definitions)
  5. Electrical (upstream MVAC interface, voltage ride through, frequency ride through, downstream LVDC interface, MVAC load acceptance and rejection, grounding)
  6. Environmental and structural
  7. System behavior (state machine and transitions)
  8. Appendices (example architectures: distributed redundancy, busway and switchboard integration)

Related standards

  • IEEE 519
  • IEC 61800-3
  • IEC 61000-6-2
  • IEC 61000-6-4
  • OCP Diablo 400
  • OCP Mt. Diablo

Publication details

Authors
Google (J. Wang, S. Kim, S. Bal, K. Hao, D. Ristanovic, A. Upreti, J. Adrian, C. Peabody); Microsoft (E. Nasr, P. Patel, X. Feng); NVIDIA (M. Tu)
Publisher
Open Compute Project Foundation
Year
2026
Document number
Rev 0.3.0
Document language
English
Source type
Industry body
Access
Free to read
Licence
OWFa 0.9: Open Compute open specification licence; redistribution permitted
Original licence note

Section 1.1: contributions under OWFa 0.9 (16 Oct 2024); usage under Modified OWFa 0.9 FSA. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Google (J. Wang, S. Kim, S. Bal, K. Hao, D. Ristanovic, A. Upreti, J. Adrian, C. Peabody); Microsoft (E. Nasr, P. Patel, X. Feng); NVIDIA (M. Tu) (2026). Solid State Transformer (SST) Specification: Medium Voltage to 800 VDC Power Conversion Platform, Revision 0.3.0 (effective 22 June 2026). Open Compute Project Foundation. Rev 0.3.0. https://www.opencompute.org/documents/ocp-sst-design-specification-v0-3-final-pdf/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.