Project: Cooling Environments, Project Brazos (air-assisted liquid cooling specification v0.75.4)
Original title Project Brazos Specification v0.75.4 - Rack-mounted air-assisted liquid cooling (AALC) sidecar (OCP Cooling Environments)
Open Compute Project Foundation · Google (J. Padilla, M. Iyengar, E. Tuttle et al.)
Google's OCP Project Brazos v0.75.4 (11 September 2026) specification defines a three-module, closed-loop liquid-to-air (aCDU) rack-side cooling system rejecting 60 kW beside an ORV3 rack.
On this page
Overview
Project Brazos is a rack-mounted, closed-loop, liquid-to-air cooling system meant to enable liquid cooling of high-power dense IT pods, including AI/ML ASICs, in air-cooled data centres. The specification covers physical dimensions, mechanical data, thermal-hydraulic performance, functional, electrical, safety, manufacturing, packaging, shipping and validation requirements. Authors are Google; the first release was 30 June 2026 and v0.75.4 was published on 11 September 2026.
The system has three modular air-assisted liquid cooling units (Brazos unit, aCDU or air CDU) and integrated rack manifolds. Each unit is 11 OU tall and interfaces with standard ORV3 racks. The Brazos rack sits beside the IT rack and pumps single-phase liquid to it; heat is rejected to data-centre air through an air-to-liquid heat exchanger (radiator), cold air is drawn by a bank of fans at the rear and exhausted into hot-aisle containment. Hot-swappable pumps (sealless, with integrated variable frequency drive), fans and front-serviceable strainers reduce MTTR; power is 40-60 Vdc from the ORV3 busbar.
Key values: nominal rack thermal capacity 60 kW across three units, coolant deionised water or 25% propylene glycol (PG25), IT flow 19 GPM, liquid pressure drop 25 psi, maximum liquid pressure 130 psig, approach temperature 8°C, rack airflow 7700 CFM at maximum fan speed, maximum power 4 kW per unit, unit weight 261 lb wet and 248 lb dry, rack weight 2200 lb wet. Certification is UL/CSA/IEC 62368-1 and remote monitoring is Modbus over TCP over IPv4/IPv6.
Table 4.1 gives, at nominal liquid flow of 12.8 GPM and 24 psi external hydraulic load, air temperature rise, airflow, liquid flow and approach temperature for 30, 40, 50 and 60 kW at fan speeds of 60, 80 and 100%; for example at 60 kW and 100% fan speed air temperature rise is 17.0°C, liquid temperature rise 11.9°C and approach temperature 7.5°C. Other sections define the expansion tank (1 L, 150 psi, -10 to 99°C), weight (dry under 250 lb, full under 264 lb), rack interfaces, slides, shock and vibration, rack manifold, liquid connections, coolant and materials compatibility, power, serviceability, leak detection and mitigation, acoustics, safety, EMC, control and monitoring (including a dry-run prevention interlock), software update and validation testing.
Key points
- Three-module Brazos rack, nominal 60 kW thermal load; each unit 11 OU and ORV3 compatible.
- Coolant: deionised water or 25% propylene glycol (PG25); maximum liquid pressure 130 psig.
- IT flow 19 GPM and liquid pressure drop 25 psi (DI water); approach temperature 8°C.
- Rack airflow 7700 CFM at maximum fan speed; unit fan range 28-100% (456-2622 SCFM).
- Maximum power 4 kW per unit; 40-60 Vdc busbar input; unit weight 261 lb wet, 248 lb dry.
- At 60 kW and 100% fan speed air temperature rise is 17.0°C, liquid temperature rise 11.9°C, approach temperature 7.5°C.
- Expansion tank 1 L stainless steel, 150 psi, -10 to 99°C.
- Default pump control is fixed pressure drop; selectable fixed flow, fixed supply temperature, fixed return temperature and fixed speed.
- Leak detection cable inside and outside the chassis; external cable 17 ft (+6/-0 inches).
- Remote monitoring Modbus over TCP; certification UL/CSA/IEC 62368-1.
Using it in design
- For liquid cooled racks in an air-cooled hall evaluate the side-rack liquid-to-air (aCDU) solution by capacity (60 kW), approach temperature (8°C) and heat rejected into hot-aisle containment.
- Add the 60 kW the aCDU rejects to air to hall cooling capacity; check air temperature rise (9.7-27.0°C) and airflow against fan speed from the table.
- Plan rack manifold and hose routing, the front protrusion limit (101.6 mm) and liquid connector type with the ORV3 rack layout and service slides.
- Wire the leak detection cable (inside chassis and on the floor in front of the rack) and drain path to hall BMS alarms and the response procedure.
- Carry unit weight (dry under 250 lb), rack weight (2200 lb wet) and lift-assist need into floor loading and installation procedures; specify the DI water or PG25 fluid separately.
Who should read it
Engineers designing and procuring rack-level aCDU solutions that connect liquid cooled AI racks to air in air-cooled data centres.
Document contents
- Version History
- License
- Compliance with OCP Tenets
- Specification overview
- Thermal-hydraulic performance requirements
- Expansion tank
- Environmental
- Mechanical
- Rack Manifold
- Liquid interconnects
- Coolant and materials compatibility
- Power & Electrical
- Serviceability
- Leak detection & mitigation
- Acoustics
- Safety
- EMC
- Regulatory compliance
- Control and monitoring
- Controls operating modes
- Internet Protocol version
- Software & firmware
- Manufacturing
- Shipment requirements
- Second source components
- Documentation and tools
- Validation
Related standards
- OCP Open Rack V3
- IEC 62368-1
- OCP UQD
Publication details
- Authors
- Google (J. Padilla, M. Iyengar, E. Tuttle et al.)
- Publisher
- Open Compute Project Foundation
- Year
- 2026
- Document number
- v0.75.4
- Document language
- English
- Source type
- Industry body
- Access
- Free to read
- Licence
- OWFa 0.9: Open Compute open specification licence; redistribution permitted
Original licence note
Section 1.1: contributions under Modified OWFa 0.9; usage governed by Modified OWFa 0.9 FSA (as of 16 Oct 2024). Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Google (J. Padilla, M. Iyengar, E. Tuttle et al.) (2026). Project Brazos Specification v0.75.4 - Rack-mounted air-assisted liquid cooling (AALC) sidecar (OCP Cooling Environments). Open Compute Project Foundation. v0.75.4. https://www.opencompute.org/wp-content/uploads/2026/10/OCP-Specification-Project-Brazos-v-0.75.4-FINAL.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
