Emerging Technologies Review: Water Reuse Systems for Cooling Tower Applications

Pacific Northwest National Laboratory · Carmen E. Cejudo, Bryan C. Pamintuan et al.

PNNL-34788, a national laboratory review for US Air Force installations assessing eight alternative water sources, storage, treatment and distribution for cooling tower make-up.

On this page

Overview

This 2023 Pacific Northwest National Laboratory report was prepared at the request of the Air Force Civil Engineer Center. Most Air Force missions depend on water and energy; cooling is a critical requirement, and alternative water supplies that keep cooling towers running during a disruption of utility water increase resilience. The report explores water reuse systems for cooling tower make-up and their viability for installations.

A reuse system comprises an alternative water supply, storage, treatment and distribution, plus the cooling tower itself. Alternative sources, not derived from fresh surface water or groundwater, fall into eight groups: HVAC condensate, atmospheric harvesting, rainwater, stormwater, greywater, reclaimed wastewater (blackwater), cooling tower blowdown and desalinated water. Components are widely available on the market and scale from a single tower to multiple buildings.

Treatment requirements depend on both the source water and the quality the cooling tower requires. Target-site selection considers cooling loads, existing infrastructure, mission-critical supply gaps and supportive regulatory conditions. The report's original context is military installation resilience, but its screening principles can inform data-centre water planning.

Key points

  1. The report reviews water reuse systems for cooling tower make-up, commissioned by the Air Force Civil Engineer Center.
  2. System components: alternative water source, storage, treatment, distribution and the cooling tower.
  3. Eight alternative sources: HVAC condensate, atmospheric harvesting, rainwater, stormwater, greywater, reclaimed wastewater, cooling tower blowdown, desalinated water.
  4. Alternative sources can provide a redundant supply to utility or on-site fresh water.
  5. Required treatment depends on source water and the quality the tower requires.
  6. Target-site selection weighs cooling loads, existing infrastructure, critical supply gaps and regulatory conditions.

Using it in design

  • Build an inventory of alternative sources for tower make-up (condensate, rain and stormwater, greywater, blowdown recovery, desalinated water) and compare each source's volume with tower demand.
  • Match each source's treatment requirement to the tower's make-up water quality specification.
  • Size storage and alternative-source feed capacity against a redundancy target for utility outages.
  • Add cooling load, existing infrastructure and regulatory conditions to site screening criteria.

Who should read it

Mechanical and water engineers planning alternative make-up sources for cooling towers and designers of critical facilities.

Publication details

Authors
Carmen E. Cejudo; Bryan C. Pamintuan; Kate Stoughton
Publisher
Pacific Northwest National Laboratory
Year
2023
Document number
PNNL-34788
Document language
English
Source type
Government / public
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Publisher page is datedMarch 21,2024 but its recommended report citation and PDF identify 2023. Public access is not treated as blanket commercial redistribution permission.

Citation

Carmen E. Cejudo; Bryan C. Pamintuan; Kate Stoughton (2023). Emerging Technologies Review: Water Reuse Systems for Cooling Tower Applications. Pacific Northwest National Laboratory. PNNL-34788. https://doi.org/10.2172/2325011

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.