Medium Voltage Cable Current-Carrying Capacity Calculation (6 kV-36 kV)
Original title Orta Gerilim Kablo Akım Taşıma Kapasite Hesabı (6 kV–36 kV için)
Türk Prysmian Kablo ve Sistemleri A.Ş.
Türk Prysmian's guide explains how to determine the ampacity of 6-36 kV medium-voltage XLPE cables using IEC 60287, TS HD 620 S2 and IEC 60502, and how to apply correction factors.
On this page
Overview
The guide opens by noting that the first 35 kV XLPE cable in Türkiye was made in 1975 at the Mudanya plant, and then sets out which standards govern medium-voltage cable ampacity. It stresses that ambient temperature and soil thermal resistivity differ by country, so common standards should anchor the calculation.
Three standards are covered. IEC 60287 (TS IEC 60287) treats current ratings and losses as a thermal problem and is formula based, in nine parts (general, sheath eddy-current losses, current sharing in parallel cables, thermal resistance, groups in free air, ventilated tunnels, operating conditions, economic size optimisation, crossing external heat sources). TS HD 620 S2 covers extruded-insulation cables from 3.6/6 kV to 20.8/36 kV and uses ready tables from test methods; sections follow the insulation: HEPR (9), XLPE (10) and EPR (11). IEC 60502 is likewise table based and covers 1-3 kV and 6-30 kV cables plus 6-30 kV accessories.
The conclusion states that a rise in ambient or cable temperature lowers ampacity and that the effect grows as the number of cables on a route increases. Cable spacing, number of systems, maximum ambient temperature and, for buried cables, soil thermal resistivity by soil type (humus, moist, sand, rock) must be checked. Correction factors must be applied whenever a parameter differs from the table basis; IEC 60502-2 Tables B.10 and B.11 are given as the ambient-temperature example.
Key points
- Three references: IEC 60287 (calculation based, 9 parts), TS HD 620 S2 (3.6/6 to 20.8/36 kV, table based), IEC 60502 (1-30 kV, table based).
- TS HD 620 S2 sections by insulation: Section 9 HEPR, Section 10 XLPE (Part 10C: XLPE with PE or PVC sheath), Section 11 EPR.
- HD 620 tables: Clause 6 Table 9 gives rated current for three-core cables in ground; bending radius is in Clause 4.6.
- IEC 60502-2 Annex B Table B.2 gives ratings for XLPE single-core copper cables (3.6/6 to 18/30 kV).
- Ambient-temperature correction uses IEC 60502-2 Tables B.10 and B.11.
- Influencing parameters: ambient temperature, soil thermal resistivity (humus, moist, sand, rock), number and spacing of cables, phase arrangement and installation type.
- Losses come from conductor resistance, screen, armour and dielectric, and reduce capacity as heat.
Using it in design
- At a data centre medium-voltage intake, verify cable size with site soil resistivity and ambient temperature corrections, not table values alone.
- With many circuits in one duct, apply the grouping factor and cable spacing.
- On critical feeders, cross-check the table result (HD 620 / IEC 60502) against the calculation method (IEC 60287).
- Record separate ratings for buried and in-air installation in the cable route document.
- State phase arrangement and installation formation (flat, trefoil) in the calculation file.
Who should read it
Electrical designers and project engineers sizing medium-voltage cables.
Document contents
- Introduction
- Calculation of cable current ratings (IEC 60287)
- Extruded insulation distribution cables (HD 620)
- Power cables 1 kV to 30 kV (IEC 60502)
- Conclusion
Related standards
- IEC 60287
- HD 620
- IEC 60502
Publication details
- Authors
- Türk Prysmian Kablo ve Sistemleri A.Ş.
- Publisher
- Türk Prysmian Kablo ve Sistemleri A.Ş.
- Year
- Year not stated
- Document number
- Technical article; medium-voltage cable rating methods
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public publisher source inspected on 2026-11-16. No document-specific redistribution permission established. Year unknown. The paragraph describing IEC 60287 ambiguously limits AC/DC voltage to 5 kV; that scope statement is excluded and the current standard itself must be checked.
Citation
Türk Prysmian Kablo ve Sistemleri A.Ş. Orta Gerilim Kablo Akım Taşıma Kapasite Hesabı (6 kV–36 kV için). Türk Prysmian Kablo ve Sistemleri A.Ş.. Technical article; medium-voltage cable rating methods. https://tr.prysmian.com/sites/tr.prysmian.com/files/2024-05/Orta_Gerilim_Kablo_Ak%C4%B1m_Ta%C5%9F%C4%B1ma_Kapasite_Hesab%C4%B1.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
