Optimization of Heat Transfer and Flow Performance of Microchannel Liquid-Cooled Plate Based on Orthogonal Test
Buildings (MDPI AG) · Zhengchao Yang, Qiufei Yao et al.
A 2025 Buildings (MDPI) paper optimising a counter-flow microchannel cold plate for a 350 W CPU by orthogonal test and simulation; best set: aspect ratio 2, 0.5 m/s, side-inlet middle-outlet.
On this page
Overview
The paper addresses the trade-off between heat transfer and pressure drop in microchannel cold plates widely used in high-performance electronics. A counter-flow rectangular microchannel plate is designed, and the effects of velocity, aspect ratio and inlet/outlet form are studied through orthogonal tests and numerical simulation. The target load is a 350 W CPU.
Velocity is the dominant parameter: raising it substantially improves heat transfer but steeply raises pressure drop. Aspect ratio matters less than velocity, and smaller aspect ratios help balance thermal and flow properties.
Jointly optimising the inlet/outlet form and velocity strongly affects temperature uniformity and pressure drop. The CM form (side inlet, middle outlet) improves temperature distribution and lowers pressure drop at high velocity. The best overall set is K2V0.5CM: aspect ratio 2, velocity 0.5 m/s and CM inlet/outlet. A correlation for Nu is finally established and compared with simulated values.
Key points
- Target load is a 350 W CPU; the design is a counter-flow rectangular microchannel cold plate.
- Velocity dominates performance: it improves heat transfer but sharply raises pressure drop.
- Smaller aspect ratios give a better balance of thermal and flow performance.
- The CM inlet/outlet form (side inlet, middle outlet) improves temperature distribution and lowers pressure drop at high velocity.
- Best set K2V0.5CM: aspect ratio 2, velocity 0.5 m/s, CM form.
- A correlation equation for Nu is derived and compared with simulation.
Using it in design
- Select cold-plate flow rate by weighing the heat transfer gain against the added pump head.
- Treat inlet and outlet placement as a design parameter for temperature uniformity.
- Use about 0.5 m/s channel velocity as a starting point for 350 W-class CPUs and verify it on the real geometry.
- Use orthogonal design to compare plate geometries with few runs.
Who should read it
Thermal engineers designing or selecting cold plates and teams developing CPU cooling solutions.
Publication details
- Authors
- Zhengchao Yang; Qiufei Yao; Yu Wang; Junlong Gu; Zhichen Yu; Qipeng Li; Xiaoyi Sun; Xuejing Yang
- Publisher
- Buildings (MDPI AG)
- Year
- 2025
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Article-specific publisher copyright/rights statement explicitly grants CC BY; version 4.0 is corroborated by publisher-deposited Crossref license metadata. Third-party material may have separate rights. Round 3/4 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Zhengchao Yang; Qiufei Yao; Yu Wang; Junlong Gu; Zhichen Yu; Qipeng Li; Xiaoyi Sun; Xuejing Yang (2025). Optimization of Heat Transfer and Flow Performance of Microchannel Liquid-Cooled Plate Based on Orthogonal Test. Buildings (MDPI AG). https://doi.org/10.3390/buildings15060905
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.