Research paperFree to read2026

A Bayesian-Optimized LightGBM Approach for Reliable Cooling Load Prediction

Buildings (MDPI AG) · Zhiying Zhang, Li Ling et al.

A 2026 paper in Buildings predicts data centre cooling load with Bayesian-optimised LightGBM at an RMSE of 4.3234 kW and MAPE of 0.07% on EnergyPlus-generated data for a medium-scale facility.

On this page

Overview

The paper begins from data centre energy use being a critical issue and accurate cooling load prediction being needed to improve cooling operation and energy efficiency. Conventional models struggle to capture nonlinear, multi-variable coupling in data centres. The study combines the LightGBM algorithm with Bayesian optimisation to improve training efficiency and generalisation.

The model was validated with data generated from an EnergyPlus simulation of a representative medium-scale data centre; measured operational data were not used. It surpasses the naive T-1, T-24 and T-168 benchmarks and the SVR, XGBoost and LSTM models. A noise robustness analysis shows R2 stays above 0.99 even at SNR = 20 dB.

Key points

  1. The model reaches RMSE 4.3234 kW, R2 0.9999 and MAPE 0.07%.
  2. Comparison models: naive T-1, T-24 and T-168 benchmarks, SVR, XGBoost and LSTM.
  3. In noise analysis at SNR = 20 dB, R2 exceeds 0.99 and RPD exceeds 12.
  4. Total runtime is 33.45 s.
  5. Validation uses EnergyPlus-generated simulation data; independent testing on site is needed.

Using it in design

  • Treat cooling load prediction as an input to intelligent cooling control and revalidate the model with the facility's own measured data.
  • Use naive benchmarks (previous hour, day and week) as the reference for forecasting skill.
  • Include sensor noise robustness in commissioning tests.
  • Do not take the very high accuracy on simulated data as field performance.

Who should read it

Engineers and data scientists working on data centre cooling control and energy forecasting.

Publication details

Authors
Zhiying Zhang; Li Ling; Jinjie He; Honghua Yang
Publisher
Buildings (MDPI AG)
Year
2026
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

Article-specific publisher copyright/rights statement explicitly grants CC BY; version 4.0 is corroborated by publisher-deposited Crossref license metadata. Third-party material may have separate rights. Round 3/4 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Zhiying Zhang; Li Ling; Jinjie He; Honghua Yang (2026). A Bayesian-Optimized LightGBM Approach for Reliable Cooling Load Prediction. Buildings (MDPI AG). https://doi.org/10.3390/buildings16071357

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.