Adaptive Global Control with jDE and Grid Search for Energy-Saving Optimization of Data Center Central Air Conditioning Systems
Energies (MDPI AG) · Weike Ding, Kexin Guo et al.
A 2026 Energies paper cuts total power by 17.24-33.55% (mean 27.34%) over 48 representative cases in a Nanjing data centre chilled-water plant using TRNSYS and jDE; the results are simulated.
On this page
Overview
The study by Ding and colleagues presents a plant-level supervisory optimisation framework combining TRNSYS operating scenarios, component-level surrogate models and self-adaptive differential evolution (jDE). The system has three chillers, three cooling towers, three chilled-water pumps and three cooling-water pumps. Decision variables are cooling-tower approach temperature difference, cooling-water temperature difference, chilled-water temperature difference and the common cooling-tower fan frequency; chilled-water supply temperature is examined separately over 14-18 degrees C.
Across 48 representative cases from four seasonal days, optimised operation reduces total power by 17.24-33.55% (mean 27.34%) and raises system COP by 20.78-50.42% (mean 38.12%), relative to matched baseline values at the same timestamps. Savings come mainly from pump and cooling-tower relief, with chiller power changes secondary and season dependent. All results come from matched simulation evaluations, not field measurements.
Key points
- Total power falls by 17.24-33.55% over 48 representative cases, mean 27.34%.
- System COP rises by 20.78-50.42%, mean 38.12%.
- The system has three chillers, three cooling towers, three chilled-water pumps and three cooling-water pumps.
- Savings come mainly from pump and cooling-tower relief.
- Optimised cooling-water supply temperatures range from 20.05 to 27.75 degrees C.
- Results are matched simulation evaluations, not field measurements.
Using it in design
- For central chilled-water plants, evaluate a supervisory control strategy that optimises chillers, towers and pumps together at design stage.
- Define tower fan frequency and temperature-difference setpoints as variables of plant-level energy optimisation.
- Verify the simulated saving by field measurement after commissioning.
- Keep the cooling-water temperature floor within the chiller manufacturer's operating limits.
Who should read it
Engineers working on data centre chilled-water plant control and energy optimisation.
Publication details
- Authors
- Weike Ding; Kexin Guo; Li Wang; Da Feng; Chong Chen; Bo Xu
- Publisher
- Energies (MDPI AG)
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Article-specific publisher copyright/rights statement explicitly grants CC BY; version 4.0 is corroborated by publisher-deposited Crossref license metadata. Third-party material may have separate rights. Round 3/4 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Weike Ding; Kexin Guo; Li Wang; Da Feng; Chong Chen; Bo Xu (2026). Adaptive Global Control with jDE and Grid Search for Energy-Saving Optimization of Data Center Central Air Conditioning Systems. Energies (MDPI AG). https://doi.org/10.3390/en19092126