Whole-Life Carbon–Cost–Circularity Optimization for AI-Era Data Centers: A Robust Multi-Objective Framework Under Carbon Pricing Uncertainty
Buildings (MDPI AG) · Arezou Shafaghat, Da Hu et al.
A 2026 Buildings (MDPI) paper compares 192 design configurations of a modelled 30 MW AI facility across three carbon-price scenarios on whole-life cost, carbon and circularity.
On this page
Overview
The paper introduces DC-WLC3O, a framework that simultaneously optimizes whole-life cost, whole-life carbon and material circularity index. It combines cradle-to-cradle life cycle assessment with dynamic material flow analysis, and uses a four-layer stack: Monte Carlo simulation, NSGA-III tri-objective Pareto optimization, Sobol' variance-based sensitivity analysis and Many-Objective Robust Decision Making (MORDM).
The framework evaluates 192 design configurations for a 30 MW hyperscale facility under three carbon pricing scenarios. Operational carbon dominates grid-dependent configurations (96.2%), while low-carbon energy produces an 8.5x inversion. Sobol' analysis confirms that energy strategy dominates carbon outcomes (S1 = 0.87).
On-site renewable energy combined with a full circular economy strategy is found unconditionally robust. The cost-circularity correlation is negative (rho = -0.488), which counters the assumption that circular strategies raise lifecycle cost in this model. The results are scenario outcomes and depend on energy, replacement and investment assumptions.
Key points
- 192 design configurations, a 30 MW hyperscale facility and three carbon pricing scenarios are evaluated.
- Operational carbon dominates grid-dependent configurations at 96.2%; low-carbon energy produces an 8.5x inversion.
- Energy strategy dominates carbon outcomes (Sobol' S1 = 0.87).
- On-site renewable energy with a full circular economy strategy is unconditionally robust (R = 0.056, stable across 94.2% of weight permutations).
- The cost-circularity correlation is negative (rho = -0.488).
- The finding holds under a +71% renewable LCOE perturbation; stability declines to about 80% under worst-case capital cost and to about 61% when generation degradation and battery replacement are combined.
Using it in design
- In AI facility investment appraisals, score whole-life cost, carbon and circularity together rather than operating PUE alone.
- Model carbon price as a scenario range instead of a single value and test option robustness across it.
- Make the energy sourcing strategy (on-site renewable versus grid mix) the first row of the design decision matrix.
Who should read it
Planners and researchers making investment and sustainability decisions for large-scale AI facilities.
Publication details
- Authors
- Arezou Shafaghat; Da Hu; Ali Keyvanfar
- Publisher
- Buildings (MDPI AG)
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Article-specific publisher copyright/rights statement explicitly grants CC BY; version 4.0 is corroborated by publisher-deposited Crossref license metadata. Third-party material may have separate rights. Round 3/4 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Arezou Shafaghat; Da Hu; Ali Keyvanfar (2026). Whole-Life Carbon–Cost–Circularity Optimization for AI-Era Data Centers: A Robust Multi-Objective Framework Under Carbon Pricing Uncertainty. Buildings (MDPI AG). https://doi.org/10.3390/buildings16152961
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.