Huawei SmartLi 5.0 passes the world's first UL 9540A:2026 large-scale fire test

Original title SmartLi battery fire-test demonstration

Huawei Digital Power

Huawei Digital Power reports that its SmartLi 5.0 data-centre lithium-ion battery passed the ANSI/CAN/UL 9540A:2026 large-scale fire test and holds a DEKRA conformity certificate; fire did not spread to the adjacent cabinet.

On this page

Overview

The news article reports that Huawei Digital Power's new-generation SmartLi 5.0 lithium battery passed the ANSI/CAN/UL 9540A:2026 large-scale fire test. DEKRA issued the conformity certificate, and Huawei says it is the first data-centre lithium-ion battery manufacturer to pass this standard. The text is published by the manufacturer and relays the test results with the manufacturer's interpretation.

The sixth edition of UL 9540A (2026) is described as strengthening verification of thermal runaway propagation, large-scale fire tests, passive safety and fire-suppression boundaries, moving evaluation from cell level to installation level. In the test, a full-pack overcharge combined with external forced ignition was applied, deliberately bypassing the product's regular protection barriers.

Results: the triggered cabinet burned fully, but fire did not spread to the adjacent target cabinet and none of its cell valves opened due to thermal runaway. After the flames were out the target cabinet was structurally intact, its management and protection system powered on and off normally, and records such as abnormal-temperature alarms were complete and exportable.

The second finding is a water-based suppression test in a semi-open space 8 m high. The sprinkler system triggered normally after thermal runaway and sprayed for about 90 minutes, with no short circuit, arcing or secondary ignition in the target cabinet. The fire was controlled at a spray density of 3.7 L/min/m2 and a sprinkler spacing of 4.4 m x 4 m, and no re-ignition occurred after the water was stopped.

Key points

  1. SmartLi 5.0 passed the ANSI/CAN/UL 9540A:2026 large-scale fire test; certificate issued by DEKRA.
  2. The test used full-pack overcharge and forced ignition, deliberately bypassing protection barriers.
  3. The triggered cabinet burned fully; the adjacent cabinet saw no fire spread and no cell valve opened.
  4. After the test the target cabinet was structurally intact; the BMS cycled normally and alarm records were exportable.
  5. In an 8 m semi-open space the sprinkler triggered normally and sprayed for about 90 min.
  6. Spray density 3.7 L/min/m2, sprinkler spacing 4.4 m x 4 m; no re-ignition after water stopped.
  7. Safety mechanisms: high-protection pack, positive-pressure oxygen blocking, directed smoke exhaust, thermal isolation.
  8. Cells are described as A-grade LFP.

Using it in design

  • In lithium battery room fire design, request the UL 9540A report (cell, module, unit and installation level) for the exact product and confirm the results apply only to the tested configuration.
  • Set the spacing and separation between adjacent cabinets from the product's thermal propagation test result.
  • Compare the test conditions (3.7 L/min/m2, 4.4 m x 4 m, 8 m ceiling) with your own facility.
  • Add electrical risk during water spray (short circuit, arcing) and post-extinguishing re-ignition criteria to acceptance testing.
  • A manufacturer announcement is not a substitute for the standard itself; assess authority-having-jurisdiction approval and local regulation separately.

Who should read it

Data-centre designers selecting lithium-ion UPS battery systems, fire safety engineers, and operations teams doing risk assessment.

Document contents

  1. Test result summary and DEKRA certificate
  2. Thermal propagation: zero fire spread between cabinets
  3. Water-based suppression in an 8 m semi-open space
  4. Intrinsic safety versus fire suppression dependence
  5. Safety design of SmartLi 5.0

Publication details

Authors
Huawei Digital Power
Publisher
Huawei Digital Power
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Huawei Digital Power SmartLi battery fire-test demonstration. Huawei Digital Power. https://digitalpower.huawei.com/mea/news/data-center-facility/smartli-fire-test

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.