Huawei UPS2000-G 6-20 kVA Technical Specifications

Original title Huawei UPS2000-G 6-20 kVA technical specifications

Huawei

The Huawei UPS2000-G series covers 6 kVA / 5.4 kW and 10 kVA / 9 kW rack or tower double-conversion online UPS units with 100% load from 280 to 176 Vac, up to 4 units in parallel and 125% overload for 5 minutes.

On this page

Overview

The page is the product introduction and parameter table for the 6-10 kVA models of the Huawei UPS2000-G series (series title 1-20 kVA). The UPS2000-G is a double-conversion online sine-wave system that can be installed as rack or tower and supplies small computing centres, network and communication rooms, automatic control systems and precision instruments. Reliability features include a 5 kA lightning protection design, early alarms for key components (bus capacitance, fans, batteries) and a black box that records operation data.

Input specifications: nominal 220/230/240 Vac, input range 280-176 Vac at 100% load and 176-80 Vac at 100-40% load (linear derating), frequency 40-70 Hz and input power factor above 0.99. Overload is 125% for 5 min and 150% for 1 min. Efficiency is stated up to 95% for 15/20 kVA, 94.5% for 10 kVA and 93.5% for 6 kVA, and the table gives system efficiency of 94% and 94.5%. ECO mode can be enabled in areas with a good grid.

Battery voltage is 192-240 Vdc and maximum charge current is 2±0.5 A on RTS models and 4±0.5 A on RTL (long backup) models; battery count is adjustable 16-20 for 6/10 kVA and 32-40 for 15/20 kVA. Intelligent charge and discharge management with temperature compensation is stated to extend battery life by 50%. Size is 86 x 430 x 585 mm (H x W x D), weight 14 kg and 16 kg, operation 0-40 °C, altitude 1000 m, noise below 55 dB and output THDv below 2%. Options are a dry contact card, Modbus card, SNMP card, PDU and STS (16 A).

Key points

  1. 6 kVA / 5.4 kW and 10 kVA / 9 kW; RTS standard, RTL long backup; rack or tower convertible.
  2. Input: 280-176 Vac at 100% load, 176-80 Vac at 100-40% load; input PF above 0.99; 40-70 Hz.
  3. Overload: 125% for 5 min, 150% for 1 min.
  4. Efficiency: up to 94.5% for 10 kVA and 93.5% for 6 kVA (95% for 15/20 kVA); ECO mode option.
  5. Battery 192-240 Vdc; 16-20 batteries for 6/10 kVA; charge current RTS 2 A, RTL 4 A (±0.5 A).
  6. Up to 4 units in parallel; one communication card manages all parallel units.
  7. 86 x 430 x 585 mm; 14 and 16 kg; operation 0-40 °C, 1000 m; noise below 55 dB; output THDv below 2%.
  8. 5 kA lightning protection; interfaces RS485, USB, SNMP, dry contacts; certifications CB, CE, TLC, CQC.

Using it in design

  • Consider using the wide input range (280-176 Vac at full load) to reduce battery cycling on weak grids.
  • For a small room, base 6 or 10 kVA selection on kW (5.4 or 9 kW); for long autonomy choose the RTL model and set battery count (16-20) from the runtime.
  • Plan redundancy with up to 4 units in parallel and the PDU / STS accessories.
  • In rack layout, account for the 86 mm height and weight (14-16 kg) plus battery packs.

Who should read it

Electrical designers selecting rack-type UPS units for small server and network rooms.

Document contents

  1. Product introduction
  2. Features
  3. Key parameters
  4. Configurations and optional components

Publication details

Authors
Huawei
Publisher
Huawei
Year
Year not stated
Document language
Spanish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Huawei Huawei UPS2000-G 6-20 kVA technical specifications. Huawei. https://enterprise.huawei.com/nla/products/itapp/ups/ups2000-gserial/hw-357253.htm

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.