Huawei UPS2000-G 6-20 kVA Technical Specifications
Original title Huawei UPS2000-G 6-20 kVA technical specifications
Huawei
The Huawei UPS2000-G series covers 6 kVA / 5.4 kW and 10 kVA / 9 kW rack or tower double-conversion online UPS units with 100% load from 280 to 176 Vac, up to 4 units in parallel and 125% overload for 5 minutes.
On this page
Overview
The page is the product introduction and parameter table for the 6-10 kVA models of the Huawei UPS2000-G series (series title 1-20 kVA). The UPS2000-G is a double-conversion online sine-wave system that can be installed as rack or tower and supplies small computing centres, network and communication rooms, automatic control systems and precision instruments. Reliability features include a 5 kA lightning protection design, early alarms for key components (bus capacitance, fans, batteries) and a black box that records operation data.
Input specifications: nominal 220/230/240 Vac, input range 280-176 Vac at 100% load and 176-80 Vac at 100-40% load (linear derating), frequency 40-70 Hz and input power factor above 0.99. Overload is 125% for 5 min and 150% for 1 min. Efficiency is stated up to 95% for 15/20 kVA, 94.5% for 10 kVA and 93.5% for 6 kVA, and the table gives system efficiency of 94% and 94.5%. ECO mode can be enabled in areas with a good grid.
Battery voltage is 192-240 Vdc and maximum charge current is 2±0.5 A on RTS models and 4±0.5 A on RTL (long backup) models; battery count is adjustable 16-20 for 6/10 kVA and 32-40 for 15/20 kVA. Intelligent charge and discharge management with temperature compensation is stated to extend battery life by 50%. Size is 86 x 430 x 585 mm (H x W x D), weight 14 kg and 16 kg, operation 0-40 °C, altitude 1000 m, noise below 55 dB and output THDv below 2%. Options are a dry contact card, Modbus card, SNMP card, PDU and STS (16 A).
Key points
- 6 kVA / 5.4 kW and 10 kVA / 9 kW; RTS standard, RTL long backup; rack or tower convertible.
- Input: 280-176 Vac at 100% load, 176-80 Vac at 100-40% load; input PF above 0.99; 40-70 Hz.
- Overload: 125% for 5 min, 150% for 1 min.
- Efficiency: up to 94.5% for 10 kVA and 93.5% for 6 kVA (95% for 15/20 kVA); ECO mode option.
- Battery 192-240 Vdc; 16-20 batteries for 6/10 kVA; charge current RTS 2 A, RTL 4 A (±0.5 A).
- Up to 4 units in parallel; one communication card manages all parallel units.
- 86 x 430 x 585 mm; 14 and 16 kg; operation 0-40 °C, 1000 m; noise below 55 dB; output THDv below 2%.
- 5 kA lightning protection; interfaces RS485, USB, SNMP, dry contacts; certifications CB, CE, TLC, CQC.
Using it in design
- Consider using the wide input range (280-176 Vac at full load) to reduce battery cycling on weak grids.
- For a small room, base 6 or 10 kVA selection on kW (5.4 or 9 kW); for long autonomy choose the RTL model and set battery count (16-20) from the runtime.
- Plan redundancy with up to 4 units in parallel and the PDU / STS accessories.
- In rack layout, account for the 86 mm height and weight (14-16 kg) plus battery packs.
Who should read it
Electrical designers selecting rack-type UPS units for small server and network rooms.
Document contents
- Product introduction
- Features
- Key parameters
- Configurations and optional components
Publication details
- Authors
- Huawei
- Publisher
- Huawei
- Year
- Year not stated
- Document language
- Spanish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Huawei Huawei UPS2000-G 6-20 kVA technical specifications. Huawei. https://enterprise.huawei.com/nla/products/itapp/ups/ups2000-gserial/hw-357253.htm
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.