Aunilec Static Transfer Switch 32/63/120 A (19-inch rack)

Original title Aunilec MultiNET_ATS32A/63A/120A datasheet, p.1 (image PDF visually checked)

Aunilec

Aunilec's thyristor-controlled 19-inch rack static transfer switch: 32, 63 and 120 A, 220/230/240 Vac, transfer under 4 ms for synchronous sources and current distortion below 1%.

On this page

Overview

The one-page brochure presents Aunilec's rack-mounted thyristor-controlled static transfer switch. The device transfers without interruption between two independent sources and can serve as an external maintenance bypass. Models are 32, 63 and 120 A; 63 A is 2U high and 545 mm deep, 120 A is 3U high and 605 mm deep. Listed applications are data centres and IT servers.

Technical features: input voltage 220/230/240 Vac, range 180-264 Vac (phase-neutral), 50 or 60 Hz, source priority selection, microprocessor control, internal manual bypass and automatic static switch. Transfer time is below 4 ms for synchronous sources and below 10 ms for non-synchronous sources. Current distortion is below 1% and a power event log is kept.

Communication is RS232 as standard with STS NET TCP/IP optional. A hot-swap electronic module is optional. Warranty is 2 years. The brochure gives no overload or short-circuit figures beyond the voltage range and transfer time; it is a selection summary for single-phase rack applications.

Key points

  1. Ratings 32, 63 and 120 A; 220/230/240 Vac, 180-264 Vac (L-N).
  2. Transfer time: <4 ms for synchronous sources, <10 ms for non-synchronous.
  3. Current distortion <1%; thyristor controlled; source priority selection.
  4. Internal manual bypass; usable as external maintenance bypass.
  5. 63 A: 2U, depth 545 mm; 120 A: 3U, depth 605 mm.
  6. RS232 standard, STS NET TCP/IP option; power event log.
  7. Option: hot-swap electronic module; 2-year warranty.

Using it in design

  • For single-corded 230 V server loads, use a rack STS between two UPS lines.
  • Compare the up to 10 ms transfer on non-synchronous sources with load tolerance.
  • Carry 2U (63 A) or 3U (120 A) and 545-605 mm depth into the rack plan.
  • Write the internal manual bypass into the maintenance procedure.

Who should read it

Data-centre electrical engineers designing rack-level A/B power distribution.

Document contents

  1. Specifications
  2. Dimensions
  3. Options

Publication details

Authors
Aunilec
Publisher
Aunilec
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Aunilec Aunilec MultiNET_ATS32A/63A/120A datasheet, p.1 (image PDF visually checked). Aunilec. https://onduleurs-aunilec.com/gb/index.php?controller=attachment&id_attachment=163

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.