Aunilec Static Transfer Switch 32/63/120 A (19-inch rack)
Original title Aunilec MultiNET_ATS32A/63A/120A datasheet, p.1 (image PDF visually checked)
Aunilec
Aunilec's thyristor-controlled 19-inch rack static transfer switch: 32, 63 and 120 A, 220/230/240 Vac, transfer under 4 ms for synchronous sources and current distortion below 1%.
On this page
Overview
The one-page brochure presents Aunilec's rack-mounted thyristor-controlled static transfer switch. The device transfers without interruption between two independent sources and can serve as an external maintenance bypass. Models are 32, 63 and 120 A; 63 A is 2U high and 545 mm deep, 120 A is 3U high and 605 mm deep. Listed applications are data centres and IT servers.
Technical features: input voltage 220/230/240 Vac, range 180-264 Vac (phase-neutral), 50 or 60 Hz, source priority selection, microprocessor control, internal manual bypass and automatic static switch. Transfer time is below 4 ms for synchronous sources and below 10 ms for non-synchronous sources. Current distortion is below 1% and a power event log is kept.
Communication is RS232 as standard with STS NET TCP/IP optional. A hot-swap electronic module is optional. Warranty is 2 years. The brochure gives no overload or short-circuit figures beyond the voltage range and transfer time; it is a selection summary for single-phase rack applications.
Key points
- Ratings 32, 63 and 120 A; 220/230/240 Vac, 180-264 Vac (L-N).
- Transfer time: <4 ms for synchronous sources, <10 ms for non-synchronous.
- Current distortion <1%; thyristor controlled; source priority selection.
- Internal manual bypass; usable as external maintenance bypass.
- 63 A: 2U, depth 545 mm; 120 A: 3U, depth 605 mm.
- RS232 standard, STS NET TCP/IP option; power event log.
- Option: hot-swap electronic module; 2-year warranty.
Using it in design
- For single-corded 230 V server loads, use a rack STS between two UPS lines.
- Compare the up to 10 ms transfer on non-synchronous sources with load tolerance.
- Carry 2U (63 A) or 3U (120 A) and 545-605 mm depth into the rack plan.
- Write the internal manual bypass into the maintenance procedure.
Who should read it
Data-centre electrical engineers designing rack-level A/B power distribution.
Document contents
- Specifications
- Dimensions
- Options
Publication details
- Authors
- Aunilec
- Publisher
- Aunilec
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Aunilec Aunilec MultiNET_ATS32A/63A/120A datasheet, p.1 (image PDF visually checked). Aunilec. https://onduleurs-aunilec.com/gb/index.php?controller=attachment&id_attachment=163
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.