Aunilec MultiNET_ATS 50-600 A Static Transfer Switch

Original title Aunilec MultiNET_ATS50-600A brochure, p.2 (image PDF OCR and visual check)

Aunilec

Aunilec MultiNET_ATS, a 50-600 A thyristor-controlled three-phase static transfer switch: 380-415 Vac, under 4 ms transfer between synchronous sources, over 99% efficiency at full load and EN 62310 compliance.

On this page

Overview

The brochure presents the MultiNET_ATS range in eight ratings: 50, 100, 150, 200, 250, 300, 400 and 600 A. Despite ATS in its name, the device is a thyristor-controlled static transfer switch operating break-before-make. The system takes power from two separate supply circuits, which can be replaced hot in normal operation without risk of interrupting the load. If both sources fail, a power supply backup function draws on an external independent source. The unit has a redundant ventilation system.

The technical table gives nominal voltage 380-400-415 Vac 3-phase + N, range 180-264 Vac phase to neutral, 50/60 Hz ±10%, compatible with TT, IT, TNC and TNS systems. Transfer is automatic, manual or remote; time is below 4 ms for synchronised sources (S1/S2) and 10 ms for non-synchronised ones. Efficiency at full load is above 99%. Operation is 0-40 °C, humidity 95%, altitude up to 4000 m, noise 55-57 dB at 1 m, protection IP20, standards EN 62310-1 and -2.

There are three enclosure sizes: 685x530x1500 mm for 50-150 A, 685x580x1770 mm for 200-400 A and 950x730x1900 mm for 600 A (W x D x H). Weights range from 140 kg at 50 A to 375 kg at 600 A. The interface is RS485, TCP/IP and two serial ports; an LCD shows status, alarms and information and a power event log is kept. Warranty is 2 years.

Key points

  1. Ratings: 50, 100, 150, 200, 250, 300, 400, 600 A; 380-400-415 Vac 3Ph+N.
  2. Range 180-264 Vac (L-N), 50/60 Hz ±10%; compatible with TT, IT, TNC, TNS.
  3. Transfer: break-before-make, <4 ms (synchronised) and 10 ms (non-synchronised).
  4. Efficiency at full load >99%; noise 55-57 dB at 1 m.
  5. Operation 0-40 °C, humidity 95%, altitude up to 4000 m; IP20; EN 62310-1 and -2.
  6. Dimensions: 685x530x1500, 685x580x1770, 950x730x1900 mm; weight 140-375 kg.
  7. Interface: RS485, TCP/IP, 2 serial ports; power event log; 2-year warranty.

Using it in design

  • In an A/B fed data hall, place this switch at the critical distribution board input for single-corded loads.
  • Choose the switch current from load current plus a 20-30% growth margin; reserve 950x730x1900 mm at 600 A.
  • Compare the 10 ms transfer on non-synchronised sources with load tolerance.
  • Verify compatibility with TT, IT and TN systems together with the earthing design.

Who should read it

Data-centre electrical engineers designing A/B power distribution and maintenance bypass.

Document contents

  1. Redundant system
  2. Specifications and working principle
  3. LED indications and navigation
  4. Model table

Publication details

Authors
Aunilec
Publisher
Aunilec
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Aunilec Aunilec MultiNET_ATS50-600A brochure, p.2 (image PDF OCR and visual check). Aunilec. https://onduleurs-aunilec.com/gb/index.php?controller=attachment&id_attachment=165

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.