Saran Water Cooled Chiller catalogue, R134a performance p.13, rating basis pp.6-7
Original title Saran Water Cooled Chiller catalogue, R134a performance p.13, rating basis pp.6–7
Saran
The Saran water-cooled chiller catalogue gives performance tables, correction factors and a worked selection for screw, reciprocating and scroll units from 5 to 720 TR.
On this page
Overview
The catalogue introduces the Saran water-cooled chiller family from 5 to 720 tons of refrigeration (TR) in one to four independent refrigerant circuits; capacities above 560 TR go to the manufacturer. Compressor types are screw, semi-hermetic reciprocating and hermetic scroll, with R22, R407C and R134a as refrigerants. The evaporator is a shell-and-tube design built to TEMA and the ASME pressure-vessel code; the condenser is a cleanable through-tube type.
The selection section sets the rating range: evaporator leaving water 42 to 46°F and condenser leaving water 85 to 105°F. Performance tables assume a 10°F range on both evaporator and condenser, 95°F condenser leaving water and fouling factors of 0.0001 (evaporator) and 0.00025 (condenser) h.ft2.°F/Btu. For other conditions the range, fouling and condenser leaving-temperature correction factors (C1 to C5) are multiplied to obtain actual capacity and power.
A step-by-step example works through 450 GPM, 44°F evaporator leaving water and 105°F condenser leaving water and confirms model 2SRLCS-250W. Later sections cover evaporator and condenser pressure-drop curves, technical and electrical data, dimensions, a typical piping diagram and installation recommendations.
The catalogue makes no field-performance or acceptance-test claim; capacities apply only at the stated water temperatures and heat-rejection conditions. Compressor input power is not total plant power.
Key points
- Capacity 5-720 TR in one to four independent circuits; above 560 TR consult the manufacturer.
- Refrigerants R22, R407C and R134a; compressors screw, reciprocating and scroll.
- Rating range: evaporator leaving water 42-46°F, condenser leaving water 85-105°F.
- Standard condition: 10°F range, 95°F condenser leaving water, fouling 0.0001 (evaporator) and 0.00025 (condenser).
- Flow formula: GPM = 24 x TR / water range (°F).
- Condenser head pressure control (tower fan or water valve) is needed where leaving condenser water can fall below 85°F.
- A condenser fouling factor of 0.002 gives a capacity multiplier of 0.910 and a power multiplier of 1.092.
- Worked example: a 187.5 TR (2250 MBH) duty is met by 2SRLCS-250W at 2252.6 MBH and 181.1 kW with 105°F condenser leaving water; condenser flow 561.7 GPM.
Using it in design
- Do not use table values directly; apply range, fouling and condenser leaving-temperature corrections and keep the result above the load.
- If tower leaving water can drop below 85°F, add tower fan control or a condenser water regulating valve.
- Read evaporator and condenser pressure drop from the unit curve (32.8 and 6.1 ft of water in the 2SRLCS-250W example) when sizing pumps.
- Do not confuse compressor input with total plant power; add pumps, tower and auxiliaries separately.
Who should read it
Mechanical engineers selecting water-cooled chillers who must correct catalogue ratings to design conditions.
Document contents
- Nomenclature
- Introduction
- Main Features
- Selection Information
- Selection Example
- Performance Data
- Evaporator/Condenser Pressure Drop
- Technical Data
- Electrical Data
- Dimension
- Typical Piping Diagram
- Installation Recommendation
Publication details
- Authors
- Saran
- Publisher
- Saran
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Saran Saran Water Cooled Chiller catalogue, R134a performance p.13, rating basis pp.6–7. Saran. https://sarantahvieh.com/wp-content/uploads/2024/05/Water_Cooled_Chiller-99.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.