Saran Fiberglass (FRP) Cooling Tower Catalogue, SRFCT series
Original title Saran Fiberglass Cooling Tower
Saran
Saran's SRFCT series covers induced-draft, counterflow circular FRP cooling towers from 8 to 500 TR; the catalogue gives flow, fan, weight and connection data for 23 models.
On this page
Overview
The catalogue presents Saran's SRFCT fiberglass (FRP) cooling tower series. The towers are induced-draft, counterflow and film-filled, offered from 8 to 500 tons of refrigeration (TR) for refrigeration, air-conditioning and industrial process cooling. Casing and hot and cold water basins are FRP; frame and steel sections are hot-dip galvanized.
The manufacturer cites as advantages a low-speed efficient fan and low-pressure-drop waved fill for energy saving, a cylindrical shape that allows installation in any direction and resists wind, factory pre-assembly for crane placement and a low-noise fan. The efficient fill reduces required pump head and motor power.
Selection needs four inputs: water flow rate, entering water temperature, leaving water temperature and ambient wet-bulb temperature. Range (entering minus leaving) and approach (leaving minus wet bulb) are calculated first, then the model is found on the selection chart. The worked example uses 95/85 °F, 75 °F wet bulb and 1000 GPM and selects SRFCT-300.
The technical table gives nominal tonnage, flow (27.7 to 1,738 GPM), nozzle head (4.3 to 17 ft), motor power (0.25 to 15 HP), air flow (3,000 to 120,200 CFM), fan diameter (60 to 326 cm) and net and operating weights. The physical data table has connection sizes (1 1/2 to 10 in) and dimensions; the final pages are foundation drawings.
Key points
- 23 models (SRFCT-8 to SRFCT-500), 8-500 TR; counterflow, induced-draft, film-filled FRP tower.
- Flow ranges from 27.7 GPM (SRFCT-8) to 1,738 GPM (SRFCT-500).
- Motor power 0.25 HP (SRFCT-8, 10) to 15 HP (SRFCT-450, 500); air flow 3,000 to 120,200 CFM.
- Fan diameter 60 cm (SRFCT-8) to 326 cm (SRFCT-450, 500).
- Operating weight 129 kg (SRFCT-8) to 7,756 kg (SRFCT-500).
- Casing and basins FRP; frame and sections hot-dip galvanized.
- Inlet and outlet connections 1 1/2 in (small) to 10 in (SRFCT-450, 500).
- Selection inputs: flow, entering and leaving water temperature, wet bulb; the example 95/85 °F, 75 °F, 1000 GPM selects SRFCT-300.
Using it in design
- Select the tower on range, approach and local design wet-bulb temperature, not on tonnage alone; use the summer design wet bulb.
- Carry the operating weight (for example 996 kg for SRFCT-100 and 4,114 kg for SRFCT-300) into the roof or ground structural calculation and the foundation drawing.
- Add the nozzle head (in ft) to the pump head calculation.
- Plan connection sizes and the overflow, make-up and drain lines together with N+1 tower or cell redundancy.
- Consider covering the capacity with several smaller towers for load sharing during maintenance.
Who should read it
Mechanical designers selecting and placing cooling towers for data centres.
Document contents
- Nomenclature
- Introduction
- Advantages
- Selection information
- Selection example
- Selection chart
- Technical data
- Physical data
- Foundation specification and drawings
Publication details
- Authors
- Saran
- Publisher
- Saran
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Saran Saran Fiberglass Cooling Tower. Saran. https://saran-mfg.com/wp-content/uploads/2024/05/Fiber_Cooling_Tower-99.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.