Saran Galvanized Cooling Tower Catalogue (single and double stage, 10-1140 TR)

Original title Saran Galvanized Cooling Tower

Saran

Saran galvanized cooling towers offer 10 to 1140 TR in single and double stage with centrifugal fans; the catalogue includes a correction-factor selection method and model data.

On this page

Overview

The catalogue presents Saran towers with galvanized steel bodies. The series spans 10 to 1140 TR in two types, single stage (S) and double stage (D); the nomenclature also encodes the fan layout (blower on one side or both sides). Casing and water basin are heavy-gauge galvanized sheet and the fans are double-inlet forward-curved centrifugal fans.

Motors are squirrel cage with IP-54 protection and insulation class F, 380 V, 3 phase, 50 Hz and 1450 rpm. The fill is PVC, splash type and non-clogging; water distribution uses non-clogging nozzles and the drift eliminators are galvanized sheet.

Nominal capacity is defined as 3 GPM of water flow at 10 °F range, 10 °F approach and 87 °F entering wet bulb. The required capacity formula is TR = CF x flow (GPM) / 3. CF is read from correction-factor charts: for range below 15 °F a single-stage tower and figure 1 apply, above 15 °F a double-stage tower and figure 2. The two examples give 133 TR (1SRCT-140S) and 160 TR (2SRCT-160D).

The tables give fans, motor power, total current, wire size, net and operating weights, dimensions and connections for models from 1SRCT-10 (30 GPM, 0.75 kW) to 2SRCT-1140 (3,420 GPM, 112 kW). For a double stage, 300 mm is added to height and 23 ft of nozzle head per unit is to be considered.

Key points

  1. Capacity range 10-1140 TR; single stage (S) and double stage (D).
  2. Nominal capacity definition: 3 GPM, 10 °F range, 10 °F approach, 87 °F entering wet bulb.
  3. Required capacity: TR = CF x GPM / 3; for range above 15 °F a double-stage tower is selected.
  4. Motors 380 V, 3 phase, 50 Hz, 1450 rpm, IP-54, insulation class F.
  5. PVC splash-type fill; double-inlet forward-curved centrifugal fans.
  6. 1SRCT-10: 30 GPM and 0.75 kW; 1SRCT-300: 900 GPM and 28 kW; 2SRCT-1140: 3,420 GPM and 112 kW.
  7. 1SRCT-300 operating weight 9,220 kg (single stage); 2SRCT-1140 operating weight 36,400 kg.
  8. For double stage add 300 mm to model height; take 23 ft of nozzle head per unit.

Using it in design

  • Read the correction factor for the real regime (range, approach, wet bulb) and compute the required TR; do not select directly on nominal tonnage.
  • Consider the double-stage tower for designs with range above 15 °F.
  • Use motor total current and wire size (table note: maximum 70 m and 40 °C) in the electrical design.
  • Add operating weight and the 23 ft nozzle head to the structural calculation and pump head.
  • Carry service area and fan layout (one-sided or two-sided) into the tower yard plan.

Who should read it

Mechanical designers selecting cooling towers and planning tower space.

Document contents

  1. Nomenclature
  2. Introduction
  3. Main features
  4. Selection procedure
  5. Correction factor graphs
  6. Schematic drawings
  7. Technical data
  8. Service area

Publication details

Authors
Saran
Publisher
Saran
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Saran Saran Galvanized Cooling Tower. Saran. https://saran-mfg.com/wp-content/uploads/2024/05/Galvanized_Cooling_Tower-99.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.