ELTENA Monolith V 10000RT2U technical table

ELTENA

A Russian-language product page from ELTENA describing the Monolith V 10000RT2U online double-conversion UPS: 10 kVA / 10 kW (output power factor 1), a 2U rack or tower chassis, 94% double-conversion efficiency and parallel operation of up to 4 units.

On this page

Overview

The page covers the largest model of the Monolith V RTLT/RT2U family (1000-10000 VA) from Moscow-based ELTENA. The Monolith V 10000RT2U is a single-phase online double-conversion UPS delivering 10000 VA / 10000 W; the manufacturer stresses that a unity output power factor lets the same kVA protect more load when the equipment is modern IT hardware with a high input power factor. The chassis is only 2U high and installs in a 19-inch rack or vertically on feet. Target applications are server groups, a server rack, a telecom node, a small data centre and an automation node.

According to the technical table, input voltage is selectable at 208, 220, 230 or 240 V; the unit runs from 110 to 286 V without going to battery and the frequency range is 40-70 Hz. The text states that a sag down to 50% below nominal is ridden through from the mains at 60% load. Input power factor at full load is at least 0.99, output voltage stability is ±1% and transfer time is 0 ms. Connection is by terminal block. Communication is through RS-232, USB and a slot for an SNMP or dry-contact card.

The unit has no internal batteries. BFR240-9V battery blocks are used for short runtimes and an external 240 V battery set for long runtimes. The DC bus is ±120 V and can be configured to ±96 or ±108 V, which means 16-20 blocks of 12 V. Charge current is adjustable from 1 to 10 A and batteries up to 300 Ah can be connected. The page includes a runtime table by battery capacity for loads of 5000, 7500 and 10000 W.

The UPS chassis measures 440 x 87 x 625 mm (WxHxD) and weighs 18 kg; the BFR240-9V battery block measures 440 x 132 x 680 mm and weighs 63 kg. Operating conditions are given as 0-40 °C, 0-95% non-condensing humidity and altitude up to 3000 m. The delivery set includes battery and communication cables, feet for vertical installation and rack ears. Other models in the series are listed as V1000RTLT, V2000RTLT, V3000RTLT and V 6000RT2U.

Key points

  1. Model: Monolith V 10000RT2U, 10000 VA / 10000 W, output power factor 1, online double conversion.
  2. Input: 208, 220, 230 or 240 V; operation from 110 to 286 V without going to battery; 40-70 Hz; power factor ≥ 0.99 at full load.
  3. Double-conversion efficiency 94%; output voltage stability ±1%; transfer time 0 ms.
  4. Input current THD < 5%; output voltage THD ≤ 2% on linear and ≤ 5% on non-linear load; noise below 58 dB at 1 m.
  5. DC bus ±120 V (configurable to ±96 / ±108 V); 16-20 batteries of 12 V up to 300 Ah, or BFR240-9V blocks.
  6. Charge current adjustable from 1 to 10 A.
  7. UPS: 440 x 87 x 625 mm (2U), 18 kg; BFR240-9V battery block: 440 x 132 x 680 mm, 63 kg.
  8. Parallel operation of up to 4 UPSs (redundancy or capacity).
  9. Environment: 0-40 °C, 0-95% humidity non-condensing, altitude up to 3000 m.

Using it in design

  • Use it to protect up to 10 kW per rack in 2U; allow a further 3U (132 mm) and 63 kg for the battery block and check that rack depth accommodates 680 mm.
  • Add about 640 W of loss at full load, from the 94% efficiency, to the rack heat load.
  • A 10 kW single-phase load draws about 43 A at 230 V; design the supply cable, breaker and phase balance on the three-phase distribution accordingly.
  • For long autonomy, select battery capacity from the runtime table on the page and calculate recharge time against the 10 A charge-current ceiling.
  • Where N+1 is needed, parallel two or more units, and record the 4-unit limit and the parallel output board on the single-line diagram.

Who should read it

Electrical designers and IT infrastructure engineers selecting a single-phase UPS of up to 10 kW for in-rack or edge locations.

Document contents

  1. Product introduction
  2. Protection applications
  3. Особенности ИБП ELTENA Monolith V 10000RT2U (Features)
  4. Характеристики ИБП (UPS specifications)
  5. Battery block BFR240-9V
  6. Runtime table

Publication details

Authors
ELTENA
Publisher
ELTENA
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ELTENA ELTENA Monolith V 10000RT2U technical table. ELTENA. https://eltena.com/catalog/ibp-eltena-monolith-v-10000rt2u/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.