ELTENA Monolith XF WB 20–40 kVA technical table
ELTENA
A Russian-language product page from ELTENA describing two models of the Monolith XF WB three-phase online UPS series with built-in batteries: XF20WB (20 kVA / 20 kW, 40 batteries of 12 V 9 Ah) and XF40WB (40 kVA / 40 kW, 64 batteries of 12 V 9 Ah), with 95.5% double-conversion efficiency and 98.5% in economy mode.
On this page
Overview
The page covers the WB version of the Monolith XF family from Moscow-based ELTENA, which houses the batteries inside the cabinet. The series is an online double-conversion UPS with output power factor 1, positioned for data centres, telecom nodes, industrial plants, banks and medical centres. Two models are offered: XF20WB at 20 kVA / 20 kW and XF40WB at 40 kVA / 40 kW. The power section is modular; a 7-inch touch screen, USB, RS-232 and a slot for an SNMP, MODBUS RTU or dry-contact card are standard.
The internal battery set is stated in the table: 40 batteries of 12 V 9 Ah in XF20WB and 64 in XF40WB. This removes the need for a separate battery cabinet in installations that need short autonomy. The three-stage charger also allows more than 1000 Ah of external battery capacity to be connected for long autonomy. Up to four UPSs can form a parallel system with a common battery set or separate ones.
The input voltage window is wide. With three-phase input the range without going to battery is 190-520 V up to 50% load and 305-478 V at full load. With single-phase input it is 110-300 V up to 50% load and 176-276 V at full load. Input power factor is at least 0.99 at full load. XF20WB can deliver single-phase (220/230/240 V) or three-phase (380/400/415 V) output; XF40WB output is 380/400/415 V ±1% three-phase. Output voltage distortion is below 2% on linear load and below 5% on non-linear load.
Efficiency is 95.5% in double conversion, 94.5% in battery mode and 98.5% in economy mode. Overload capability is up to 110% for 60 minutes, up to 125% for 10 minutes and up to 150% for 1 minute; by default the bypass carries 130% for 1 minute or until the breaker trips. XF20WB measures 630 x 250 x 826 mm (DxWxH) and weighs 159 kg; XF40WB measures 815 x 300 x 1000 mm and weighs 250 kg. Operating conditions are 0-40 °C, 0-95% non-condensing humidity and altitude up to 1500 m.
Key points
- Models: XF20WB 20 kVA / 20 kW and XF40WB 40 kVA / 40 kW; output power factor 1.
- Internal batteries: 40 in XF20WB and 64 in XF40WB, each 12 V 9 Ah.
- Three-phase input: 190-520 V up to 50% load, 305-478 V at full load; single-phase input: 110-300 V up to 50% load, 176-276 V at full load.
- Input frequency: 46-54 or 56-64 Hz for XF20WB, 40-70 Hz for XF40WB; power factor ≥ 0.99.
- Efficiency: double conversion 95.5%, battery mode 94.5%, economy mode 98.5%.
- Overload: up to 110% for 60 minutes, up to 125% for 10 minutes, up to 150% for 1 minute; 130% for 1 minute on bypass.
- Size and weight: XF20WB 630 x 250 x 826 mm, 159 kg; XF40WB 815 x 300 x 1000 mm, 250 kg.
- Noise at 1 m: < 65 dBA for XF20WB, < 63 dBA for XF40WB.
- Environment: 0-40 °C, 0-95% humidity non-condensing, up to 1500 m; up to 4 UPSs in parallel.
Using it in design
- In small data rooms with no separate battery room, prefer the WB version with built-in batteries; check floor loading with the weight including batteries (159 kg or 250 kg) on the small footprint (0.16 m² or 0.24 m²).
- Take the autonomy delivered by the internal 9 Ah batteries from the manufacturer's runtime table; if it falls short, calculate an external battery set together with recharge time.
- Because the batteries share the cabinet with the UPS, design room temperature in the 20-25 °C band for battery life; the 40 °C upper limit applies to the electronics only.
- Use 95.5% double-conversion efficiency for the heat load: about 1.9 kW of loss at 40 kW load.
- Consider the single-phase output option of XF20WB for small single-phase distributions; XF40WB delivers three-phase output only.
- When paralleling two units for N+1, decide between a common or separate battery set from the redundancy target; separate sets give independence on a battery fault.
Who should read it
Electrical designers and IT infrastructure engineers selecting a 20-40 kVA UPS with built-in batteries for small data rooms and branch facilities.
Document contents
- Monolith XF WB 20-40 кВА (introduction)
- Защита (Protection applications)
- Особенности ИБП ELTENA Monolith XF (Features)
- Характеристики ИБП (UPS specifications)
Publication details
- Authors
- ELTENA
- Publisher
- ELTENA
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
ELTENA ELTENA Monolith XF WB 20–40 kVA technical table. ELTENA. https://eltena.com/catalog/3-h-faznyie-ibp/monolith-xf-wb-20-40-kva/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.