ELTENA Monolith XM4 180–600 kVA technical table
ELTENA
A Russian-language product page from ELTENA describing three frames of the fourth-generation modular Monolith XM4 UPS series: XM4 180 (180 kVA / 180 kW), XM4 300 (300/300) and XM4 600 (600/600). The system is built from hot-swappable 60 kW power modules in a 3U case and double-conversion efficiency is 96%.
On this page
Overview
The page covers the fourth generation of the modular UPS family from Moscow-based ELTENA. Monolith XM4 is an online double-conversion, redundant and scalable system made from small, easily transported standard modules. The power modules are connected in parallel: where the system holds surplus modules the failure of one has no effect on the load, and any module is hot-swapped without interrupting load protection. With a spare module on hand, recovery time approaches zero. Capacity can be raised at any time by adding modules. Target applications are data centres, medical facilities, industrial and commercial sites and security systems.
The technical table compares the three frames. Each power module is 60 kW; XM4 180 takes up to 3, XM4 300 up to 5 and XM4 600 up to 10 modules, for maximum power of 180, 300 and 600 kVA/kW respectively. Output power factor is 1. Nominal voltage is 380/400/415 V, input frequency range 40-70 Hz, input power factor above 0.99 at full load and input current distortion below 3%. A sag down to 110 V per phase does not cause a transfer to battery.
Output voltage distortion is below 2% on linear load and below 4% on non-linear load. The synchronisation range is configurable at ±1, ±2 or ±4 Hz. Overload capability is up to 110% for 1 hour, up to 125% for 10 minutes and up to 150% for 1 minute. The DC bus is configurable from ±192 V to ±240 V and maximum charge current is 18 A per module. The page includes a runtime table for external batteries from 55 Ah to 200 Ah: 80 batteries of 12 V in series are required for XM4 180, 120 for XM4 300 and 200 for XM4 600.
Mechanical data is given separately for module and frame. The power module measures 438 x 130 x 750 mm (WxHxD) and weighs 44 kg. The frames are 600 x 1475 x 1100 mm for XM4 180, 600 x 2010 x 1100 mm for XM4 300 and 1000 x 2000 x 1065 mm for XM4 600; frame weights without modules are 352, 516 and 1020 kg. Operating temperature is 0-40 °C. According to the runtime table, with 200 Ah batteries at full load XM4 180 runs for 26 minutes, XM4 300 for 23 minutes and XM4 600 for 17 minutes.
Key points
- Frames: XM4 180 (180 kVA/kW, up to 3 modules), XM4 300 (300 kVA/kW, 5 modules), XM4 600 (600 kVA/kW, 10 modules).
- Power module: 60 kW, 3U, 438 x 130 x 750 mm, 44 kg, hot-swappable.
- Output power factor 1; double-conversion efficiency 96%.
- Input: 380/400/415 V, 40-70 Hz, power factor > 0.99, THDi < 3% at full load.
- Output THDv < 2% on linear load and < 4% on non-linear load.
- Overload: up to 110% for 1 hour, up to 125% for 10 minutes, up to 150% for 1 minute.
- Battery: configurable ±192 V to ±240 V; maximum charge current 18 A times the number of modules.
- Frame (WxHxD) and weight without modules: 600 x 1475 x 1100 mm, 352 kg; 600 x 2010 x 1100 mm, 516 kg; 1000 x 2000 x 1065 mm, 1020 kg.
- Runtime at full load with 200 Ah batteries: XM4 180 0:26, XM4 300 0:23, XM4 600 0:17 (h:min).
- Redundancy: N+1 or N+X parallel module redundancy.
Using it in design
- Choose the module count for N+1: for a 240 kW load use 4+1 modules (5 x 60 kW) in the XM4 300 frame; the frame's maximum module count caps redundant capacity.
- Calculate floor loading as frame weight plus module count times 44 kg: 1020 + 440 = 1460 kg for a fully populated XM4 600, excluding batteries.
- Use 96% efficiency for the heat load: about 25 kW of loss at 600 kW load is added to UPS room cooling.
- Select the battery set from the runtime table on the page and carry the string structure (80, 120 or 200 blocks of 12 V) into the battery room layout and breaker selection.
- Calculate recharge time from the installed module count; with 18 A per module, charging takes longer in an early phase with few modules.
- Modular redundancy sits inside one frame; for designs requiring 2N, plan two separate frames with separate battery sets and treat the common busbar and bypass inside a frame as a single point of failure.
Who should read it
Data-centre electrical designers selecting a modular UPS in the 180-600 kW range and planning engineers phasing capacity growth.
Document contents
- Monolith XM4 180 - 600 кВА (introduction)
- Защита (Protection applications)
- Особенности ИБП ELTENA Monolith XM4 (Features)
- Характеристики ИБП (UPS specifications)
- Время автономной работы ИБП Monolith XM4 с внешними батареями (Runtime with external batteries)
Publication details
- Authors
- ELTENA
- Publisher
- ELTENA
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
ELTENA ELTENA Monolith XM4 180–600 kVA technical table. ELTENA. https://eltena.com/catalog/3-h-faznyie-ibp/monolith-xm4-180---600-kva/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.