ELTENA Monolith XF 20–80 kVA technical table

ELTENA

A Russian-language product page from ELTENA describing five models of the Monolith XF three-phase online double-conversion UPS series: XF20RT (20 kVA / 20 kW), XF60RT (60/60), XF40 (40/40), XF60 (60/60) and XF80 (80/80), with output power factor 1, 95-96% double-conversion efficiency and 99% in economy mode.

On this page

Overview

The page covers the Monolith XF series, which Moscow-based ELTENA positions for data centres, telecom nodes, industrial plants, banks and medical centres. The series is a three-phase online double-conversion UPS and on every model the kVA rating equals the kW rating. The power section is modular, which eases repair and shortens recovery time after a failure. There is a 7-inch touch screen, USB and RS-232 ports and a slot for an SNMP, MODBUS RTU or dry-contact card. The XF20RT model can also run with single-phase input and output.

The technical table compares five models. The input voltage range without going to battery is 190-520 V at 50% load and 305-478 V at 100% load; input frequency is 40-70 Hz and input power factor is above 0.99. Output voltage stability is ±1% and voltage distortion is below 2% on linear load and below 5% on non-linear load. Overload capability is up to 110% for 60 minutes, up to 125% for 10 minutes and up to 150% for 1 minute. By default the bypass line carries 130% for 1 minute or until the breaker trips.

Efficiency is given as two values by model group: 95% or 96% in double conversion and 94% or 95.5% in battery mode, with 99% in economy mode. The manufacturer states that the high efficiency reduces electricity and cooling costs and that low input current distortion with soft start eases matching with generator sets. The DC bus is between ±192 V and ±240 V (32-40 blocks of 12 V). The three-stage charger delivers a maximum of 12 A or 18 A, and more than 1000 Ah of battery capacity can be connected.

Up to four UPSs can form a parallel system, working with a common battery set or separate ones. Mechanically the page lists two rack chassis (680 x 438 x 133 mm and 797 x 438 x 176 mm, DxWxH) and two tower cabinets (815 x 300 x 1000 mm and 1200 x 430 x 1000 mm). Weights are 28 kg for XF20RT, 45 kg for XF60RT, 67 kg for XF40, 74 kg for XF60 and 133 kg for XF80. Operating conditions are 0-40 °C, 0-95% non-condensing humidity and altitude up to 1600 m; noise is below 65 dBA at 1 m.

Key points

  1. Models (kVA/kW): XF20RT 20/20, XF60RT 60/60, XF40 40/40, XF60 60/60, XF80 80/80; output power factor 1.
  2. Input: 190-520 V at 50% load, 305-478 V at 100% load; 40-70 Hz; power factor > 0.99.
  3. Efficiency: double conversion 95% or 96% (by model), battery mode 94% or 95.5%, economy mode 99%.
  4. Overload: up to 110% for 60 minutes, up to 125% for 10 minutes, up to 150% for 1 minute; 130% for 1 minute on bypass.
  5. Output: ±1% stability, THDv < 2% on linear and < 5% on non-linear load, crest factor 3:1.
  6. Battery: ±192 V to ±240 V (32-40 blocks); maximum charge current 12 A on XF20RT and XF40, 18 A on XF60RT, XF60 and XF80.
  7. Weight: XF20RT 28 kg, XF60RT 45 kg, XF40 67 kg, XF60 74 kg, XF80 133 kg.
  8. Parallel: up to 4 UPSs, with a common or separate battery set.
  9. Environment: 0-40 °C, 0-95% humidity non-condensing, up to 1600 m; noise < 65 dBA at 1 m.

Using it in design

  • With power factor 1, take kW capacity equal to kVA, and assess an N+1 arrangement (for example 3+1 x 80 kW) within the 4-unit parallel limit.
  • For in-rack installation, compare the 680-797 mm depth of XF20RT (133 mm, 28 kg) and XF60RT (176 mm, 45 kg) with rack depth and rear cabling allowance, and plan batteries in a separate cabinet.
  • Use 95% or 96% double-conversion efficiency by model group for the heat load; if the design relies on the 99% economy-mode figure, record the reduced protection in the design decision.
  • For long autonomy, calculate recharge time against the 12 A or 18 A charge-current limit; the time lengthens for battery sets approaching 1000 Ah.
  • On weak-grid sites, compare the 305-478 V full-load window with site voltage records; excursions outside it set the number of battery discharges.
  • In generator sizing, reflect the 0.99 input power factor and the soft-start feature in the step-load calculation.

Who should read it

Electrical designers selecting a 20-80 kVA three-phase UPS and engineers planning in-rack or small data room power systems.

Document contents

  1. Monolith XF 20-80 кВА (introduction)
  2. Защита (Protection applications)
  3. Особенности ИБП ELTENA Monolith XF (Features)
  4. Характеристики ИБП (UPS specifications)

Publication details

Authors
ELTENA
Publisher
ELTENA
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ELTENA ELTENA Monolith XF 20–80 kVA technical table. ELTENA. https://eltena.com/catalog/3-h-faznyie-ibp/monolith-xf-60-200-kva/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.