Enhancing seismic resilience of tier III/IV data centers: A comparative performance-based evaluation of fixed base and DCFP isolated structures
Research on Engineering Structures & Materials · Arif Rusyana, Yuskar Lase
A Universitas Indonesia study of a four-story data centre shows base isolation cut base shear by 67% and kept server-floor accelerations below 0.22g, while a stiffened fixed-base frame did not.
On this page
Overview
The paper, by Rusyana and Lase in Research on Engineering Structures & Materials (2026), studies seismic behaviour for Tier III/IV data centres. Data centres typically carry about three times the seismic mass and twice the floor height of conventional buildings, and TIA-942 specifies a minimum total load of 14.4 kPa. Annual downtime limits are 1.6 hours for Tier III and 0.4 hours for Tier IV, and natural disasters count toward them.
Method: a four-story data centre was modelled in three configurations: a Risk Category II fixed-base baseline (Model 1), a stiffened Risk Category IV fixed-base frame (Model 2) and a double concave friction pendulum (DCFP) base-isolated structure (Model 3) using the Model 1 superstructure. They were evaluated by nonlinear time history analysis (NLTHA) with 11 real ground motions at the Maximum Considered Earthquake (MCER) level.
Results: Model 2, although compliant with ASCE 7 and SNI 1726, limited displacements but did not reduce floor accelerations, increasing roof acceleration by 25% on average relative to Model 1. Model 3 moved the superstructure as a rigid body with average drift of 0.2%, and accelerations on stories 1-4 where server racks sit stayed below the 0.22g threshold. The threshold is a floor-level indicator based on hard-drive damage, not a component-level safety limit.
The scope is limited to regular geometry; near-fault directivity, vertical ground motion and significant irregularities are excluded. The work still gives quantitative support to the TIA-942 recommendation of base isolation for Tier IV, which is often treated as optional in countries such as Indonesia.
Key points
- Tier III and Tier IV annual downtime limits are 1.6 and 0.4 hours; TIA-942B specifies passive protection such as base isolation at MCER level for Tier IV.
- The floor acceleration indicator is 0.22g (Seagate hard-drive limit); 0.2g is also used in the literature.
- The isolated Model 3 reduced average total base shear by 67% versus Model 1, while the stiffened Model 2 increased it by 6%.
- Model 3 averaged 0.2% inter-story drift; Model 2 stayed below the 1% limit for Risk Category IV while Model 1 exceeded it.
- Plastic hinges reached Life Safety to Collapse Prevention in Model 1, IO-LS in Model 2 and stayed within A-IO in Model 3.
- Both fixed-base models exceeded 0.22g; Model 2 amplified roof acceleration by 25% on average while Model 3 reduced it by 71% on average.
- Model 1 peak accelerations on stories 1-4 range from 0.49g to 0.73g; in the isolated model server-floor accelerations stayed below 0.22g for all records.
- ASCE 7 counts 100% of permanently anchored equipment in effective seismic weight, whereas only about 25% of live load counts in office or residential buildings.
Using it in design
- Define the seismic criterion for Tier III/IV buildings not only as structural safety (drift, base shear) but also as a target floor acceleration at server levels (for example 0.22g).
- In high-seismicity regions, do not assume added stiffness reduces acceleration; it can raise it, so evaluate base isolation as an alternative.
- Include 100% of permanent equipment in effective seismic weight and reflect heavy load assumptions such as 14.4 kPa in the model.
- Check the height-to-footprint ratio (limit 2.0 in this study) and DCFP isolator capacity early in the design.
- Analyse effects outside the study scope (near-fault, vertical component, irregularity) separately for the site.
Who should read it
Structural engineers designing data-centre buildings in seismic regions, consultants assessing TIA-942 conformance, and investors.
Document contents
- Introduction
- Seismic performance requirements for data center facilities
- Methodology
- Results and discussion: comparative performance analysis
- Conclusions and limitations
Publication details
- Authors
- Arif Rusyana; Yuskar Lase
- Publisher
- Research on Engineering Structures & Materials
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official author institution, repository or publisher page inspected. No article-specific redistribution permission established; metadata and original brief summaries only. Free access may refer to the public abstract, not the full paper.
Citation
Arif Rusyana; Yuskar Lase (2026). Enhancing seismic resilience of tier III/IV data centers: A comparative performance-based evaluation of fixed base and DCFP isolated structures. Research on Engineering Structures & Materials. https://doi.org/10.17515/resm2026-1485st0129rs
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.