Enhancing seismic resilience of tier III/IV data centers: A comparative performance-based evaluation of fixed base and DCFP isolated structures

Research on Engineering Structures & Materials · Arif Rusyana, Yuskar Lase

A Universitas Indonesia study of a four-story data centre shows base isolation cut base shear by 67% and kept server-floor accelerations below 0.22g, while a stiffened fixed-base frame did not.

On this page

Overview

The paper, by Rusyana and Lase in Research on Engineering Structures & Materials (2026), studies seismic behaviour for Tier III/IV data centres. Data centres typically carry about three times the seismic mass and twice the floor height of conventional buildings, and TIA-942 specifies a minimum total load of 14.4 kPa. Annual downtime limits are 1.6 hours for Tier III and 0.4 hours for Tier IV, and natural disasters count toward them.

Method: a four-story data centre was modelled in three configurations: a Risk Category II fixed-base baseline (Model 1), a stiffened Risk Category IV fixed-base frame (Model 2) and a double concave friction pendulum (DCFP) base-isolated structure (Model 3) using the Model 1 superstructure. They were evaluated by nonlinear time history analysis (NLTHA) with 11 real ground motions at the Maximum Considered Earthquake (MCER) level.

Results: Model 2, although compliant with ASCE 7 and SNI 1726, limited displacements but did not reduce floor accelerations, increasing roof acceleration by 25% on average relative to Model 1. Model 3 moved the superstructure as a rigid body with average drift of 0.2%, and accelerations on stories 1-4 where server racks sit stayed below the 0.22g threshold. The threshold is a floor-level indicator based on hard-drive damage, not a component-level safety limit.

The scope is limited to regular geometry; near-fault directivity, vertical ground motion and significant irregularities are excluded. The work still gives quantitative support to the TIA-942 recommendation of base isolation for Tier IV, which is often treated as optional in countries such as Indonesia.

Key points

  1. Tier III and Tier IV annual downtime limits are 1.6 and 0.4 hours; TIA-942B specifies passive protection such as base isolation at MCER level for Tier IV.
  2. The floor acceleration indicator is 0.22g (Seagate hard-drive limit); 0.2g is also used in the literature.
  3. The isolated Model 3 reduced average total base shear by 67% versus Model 1, while the stiffened Model 2 increased it by 6%.
  4. Model 3 averaged 0.2% inter-story drift; Model 2 stayed below the 1% limit for Risk Category IV while Model 1 exceeded it.
  5. Plastic hinges reached Life Safety to Collapse Prevention in Model 1, IO-LS in Model 2 and stayed within A-IO in Model 3.
  6. Both fixed-base models exceeded 0.22g; Model 2 amplified roof acceleration by 25% on average while Model 3 reduced it by 71% on average.
  7. Model 1 peak accelerations on stories 1-4 range from 0.49g to 0.73g; in the isolated model server-floor accelerations stayed below 0.22g for all records.
  8. ASCE 7 counts 100% of permanently anchored equipment in effective seismic weight, whereas only about 25% of live load counts in office or residential buildings.

Using it in design

  • Define the seismic criterion for Tier III/IV buildings not only as structural safety (drift, base shear) but also as a target floor acceleration at server levels (for example 0.22g).
  • In high-seismicity regions, do not assume added stiffness reduces acceleration; it can raise it, so evaluate base isolation as an alternative.
  • Include 100% of permanent equipment in effective seismic weight and reflect heavy load assumptions such as 14.4 kPa in the model.
  • Check the height-to-footprint ratio (limit 2.0 in this study) and DCFP isolator capacity early in the design.
  • Analyse effects outside the study scope (near-fault, vertical component, irregularity) separately for the site.

Who should read it

Structural engineers designing data-centre buildings in seismic regions, consultants assessing TIA-942 conformance, and investors.

Document contents

  1. Introduction
  2. Seismic performance requirements for data center facilities
  3. Methodology
  4. Results and discussion: comparative performance analysis
  5. Conclusions and limitations

Publication details

Authors
Arif Rusyana; Yuskar Lase
Publisher
Research on Engineering Structures & Materials
Year
2026
Document language
English
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official author institution, repository or publisher page inspected. No article-specific redistribution permission established; metadata and original brief summaries only. Free access may refer to the public abstract, not the full paper.

Citation

Arif Rusyana; Yuskar Lase (2026). Enhancing seismic resilience of tier III/IV data centers: A comparative performance-based evaluation of fixed base and DCFP isolated structures. Research on Engineering Structures & Materials. https://doi.org/10.17515/resm2026-1485st0129rs

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Redundancy scenarios in SoSo CAD

Compare normal operation with equipment failures and see served loads and capacity shortfalls in the same view.

Normal operation and failure scenario comparison in SoSo CAD

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.