Technical guideFree to read2025

Veri Merkezi Çözümleri: Sismik İzolatör Sistemleri

SAMM Teknoloji

SAMM Teknoloji's 2025 catalogue presents the SSI-1000 under-cabinet steel-ball seismic isolator: 200 mm displacement, 2,000 kg recommended load (tested to 3,000 kg) and Telcordia GR-63-CORE conformance.

On this page

Overview

The catalogue presents the SSI-1000 seismic isolator system for data-centre cabinets, made by Gebze-based SAMM Teknoloji. It opens with a map of Turkish data centres by province (Istanbul 40, Ankara 11, Izmir 9, Bursa 6, Denizli 4 and so on) set against major earthquake epicentres, stressing isolator use in seismic regions.

The isolator works as a friction pendulum: a concave lower plate and a steel ball moving freely on it. Horizontal ground motion becomes a controlled sliding motion rather than passing to the supported load; its duration and intensity depend on the surface radius and friction coefficient. Friction converts part of the energy to heat, and gravity returns the ball to the centre after the event (self-centring).

The catalogue lists benefits as protection of servers and hardware, prevention of data loss, protection of network and power connections, personnel safety and retrofit applicability in existing facilities. It also states that manufacturers claiming '7-9 Richter' ratings are misleading, since isolator effectiveness depends on ground-motion frequency, amplitude, duration and soil conditions rather than magnitude.

This is a manufacturer's product catalogue, so technical values are the manufacturer's claims. The most useful parts for a designer are cabinet load capacity ranges (standard 500-1,000 kg, special 1,000-2,000 kg) compared with isolator capacity, and the platform sizes against the layout.

Key points

  1. The SSI-1000 is a maintenance-free steel-ball friction-pendulum isolator that responds in all directions (360 degrees).
  2. Maximum displacement is 200 mm; recommended maximum working load is 2,000 kg and it was tested at 3,000 kg.
  3. It is declared to meet Telcordia GR-63-CORE fully; test partners are Allianz Teknik and the Kandilli Observatory.
  4. In the 3,000 kg test no cracks, pits or tracks formed on the isolator plates.
  5. Standard server cabinets carry 500-1,000 kg and special designs 1,000-2,000 kg (EIA-310, IEC 60297 context).
  6. Platform sizes are 800, 1000, 1200 and 1400 mm; profile sizes 602, 802 and 1002 mm; single or multiple (2 or 4) plate layouts exist.
  7. A lock mechanism holds the whole assembly still during cabinet loading and unloading.
  8. Turkish data centres by province: Istanbul 40, Ankara 11, Izmir 9, Bursa 6, Denizli 4; the catalogue cites proximity to seismic risk.
  9. The catalogue states there is no direct relationship between Richter magnitude and isolator effectiveness; performance depends on ground-motion frequency and amplitude.

Using it in design

  • Compare loaded cabinet weight (cabinet, servers, cables) with the 2,000 kg isolator capacity; check cases near the limit for 1,000-2,000 kg special cabinets.
  • Ask suppliers for the tested ground-motion records, displacement and acceleration reduction values rather than 'Richter' claims.
  • Leave movement clearance around cabinets for 200 mm displacement and design cable and busbar connections to be flexible.
  • For retrofit in existing halls, check platform height, ramps and the effect on floor loading.

Who should read it

Mechanical and structural engineers designing data centres in seismic regions of Turkey, and operators procuring isolators.

Document contents

  1. Company introduction
  2. Importance of seismic isolators for data centres in Turkey
  3. Benefits of seismic isolators
  4. Richter magnitude and isolator effectiveness
  5. SSI-1000 seismic isolator
  6. Under-cabinet load requirements
  7. Platform layout and dimensions
  8. Shake-table test

Related standards

  • Telcordia GR-63-CORE

Publication details

Authors
SAMM Teknoloji
Publisher
SAMM Teknoloji
Year
2025
Document number
DOC-C-13/000-V2-TR
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public publisher source inspected on 2026-11-16. No document-specific redistribution permission established. 2025 footer inspected. Manufacturer claims of uninterrupted operation and full standard compliance were not independently tested.

Citation

SAMM Teknoloji (2025). Veri Merkezi Çözümleri: Sismik İzolatör Sistemleri. SAMM Teknoloji. DOC-C-13/000-V2-TR. https://telecom.samm.com/Data/EditorFiles/Catalog/data-center-sismik-izolator-sistemleri.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Redundancy scenarios in SoSo CAD

Compare normal operation with equipment failures and see served loads and capacity shortfalls in the same view.

Normal operation and failure scenario comparison in SoSo CAD

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.