Technical guideFree to readYear not stated

Riello UPS SuperCaps: battery-free supercapacitor UPS solutions, 1-800 kVA

Original title SuperCaps UPS: solutions with supercapacitors

Riello UPS

Riello UPS's SuperCaps series is a battery-free supercapacitor online UPS from 1 to 800 kVA: 1-60 seconds of autonomy, over a million cycles, and 5 to 10 times the life of lead batteries.

On this page

Overview

The brochure presents Riello UPS's SuperCaps UPS family, which stores energy in supercapacitors instead of batteries. The range runs from 1-10 kVA in 1:1 models to 10-800 kVA in 3:3 models, aimed at data centre, e-medical and industry applications. Autonomy is in the range of seconds (1 to 60 s). The manufacturer states that at least 87% of power interruptions last less than a second (an EPRI study), so a short autonomy is enough in most cases.

The reasoning is that in modern data centre, medical and industrial installations an efficient generator set supported by a UPS with brief autonomy is the most efficient continuity solution. Standard UPSs are installed with 5-10 minute batteries against generator start-up failure; SuperCaps UPS removes battery installation, monitoring, maintenance, replacement and recycling costs. The manufacturer cites a theoretically infinite life against the 5-7 years of standard batteries, and over a million cycles against about 300 for lead batteries.

The range is given in model tables: SENTINEL PRO SC (SEP 1000 and 3000 VA, 8 and 7 s), SENTINEL TOWER SC (6 and 10 kVA, 8 and 7 s), SENTRY UM SC (S3M/S3T 10-40 kVA, 7-30 s), MASTER MPS SC (60-160 kVA, 10-20 s) and MASTER HP SC (100-200 kVA, 10-18 s). Input power factor is above 0.99 (above 0.9 for the MPS HC version) and input current distortion is from 7% or less down to 3% or less depending on model. Recharge time is 2-7 minutes.

Notes: backup time is calculated at 70% load for the SENTINEL models and at 100% load for the SENTRY and MASTER models. For example the S3T 30 kVA gives 10 or 20 s, the MASTER MPS 60 kVA 20 s and the 160 kVA 15 s. The systems work with 480-648 V DC supercapacitor modules (BTC), and modular expansion gives more power and runtime. The high working temperature is said to remove any need for cooling or heating systems.

Key points

  1. Power range: 1-10 kVA in 1:1 models, 10-800 kVA in 3:3 models; online double conversion.
  2. Autonomy 1-60 s; tables show 7-30 s depending on load condition.
  3. At least 87% of power interruptions last less than a second (EPRI study).
  4. Over a million cycles against about 300 for lead; life 5 to 10 times that of lead batteries.
  5. Recharge time 2-7 min; input PF >0.99; input current distortion from 7% or less to 3% or less.
  6. SENTINEL PRO SC: 1000 VA/900 W and 3000 VA/2700 W, 8.1 and 17.6 kg.
  7. SENTRY UM SC: 10, 15, 20 kVA (30/40 kVA in the S3T line), 130-202 kg; 440x840x1320 mm.
  8. MASTER MPS SC 60-160 kVA and MASTER HP SC 100-200 kVA; supercapacitor cabinet (BTC) separate.

Using it in design

  • Consider SuperCaps UPS only in generator-backed sites; verify the 7-30 s autonomy against generator start-up time (for example 10-15 s) and ATS transfer.
  • Check at which load (70% or 100%) the autonomy is given and recompute at the design load.
  • Reflect the removal of battery room, ventilation and battery monitoring costs in the floor area and TCO calculation.
  • Add cabinet sizes and weight (for example 700+540 kg for the MASTER MPS 160 kVA) to the electrical room layout.
  • For critical loads that need long autonomy against generator failure, choose a battery UPS or a hybrid solution instead of supercapacitors.

Who should read it

Electrical designers and facility managers looking for short-autonomy UPS in generator-backed data centres, medical and industrial sites.

Document contents

  1. Highlights and clean-energy rationale
  2. Sentinel PRO SC
  3. Sentinel Tower SC
  4. Sentry UM SC (S3M/S3T)
  5. Master MPS SC
  6. Master HP SC
  7. Technical tables

Publication details

Authors
Riello UPS
Publisher
Riello UPS
Year
Year not stated
Document number
DATCAPX0Y25CREN
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Riello UPS SuperCaps UPS: solutions with supercapacitors. Riello UPS. DATCAPX0Y25CREN. https://www.riello-ups.com/uploads/file/750/3750/DATCAPX0Y25CREN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.