Riello UPS SuperCaps: battery-free supercapacitor UPS solutions, 1-800 kVA
Original title SuperCaps UPS: solutions with supercapacitors
Riello UPS
Riello UPS's SuperCaps series is a battery-free supercapacitor online UPS from 1 to 800 kVA: 1-60 seconds of autonomy, over a million cycles, and 5 to 10 times the life of lead batteries.
On this page
Overview
The brochure presents Riello UPS's SuperCaps UPS family, which stores energy in supercapacitors instead of batteries. The range runs from 1-10 kVA in 1:1 models to 10-800 kVA in 3:3 models, aimed at data centre, e-medical and industry applications. Autonomy is in the range of seconds (1 to 60 s). The manufacturer states that at least 87% of power interruptions last less than a second (an EPRI study), so a short autonomy is enough in most cases.
The reasoning is that in modern data centre, medical and industrial installations an efficient generator set supported by a UPS with brief autonomy is the most efficient continuity solution. Standard UPSs are installed with 5-10 minute batteries against generator start-up failure; SuperCaps UPS removes battery installation, monitoring, maintenance, replacement and recycling costs. The manufacturer cites a theoretically infinite life against the 5-7 years of standard batteries, and over a million cycles against about 300 for lead batteries.
The range is given in model tables: SENTINEL PRO SC (SEP 1000 and 3000 VA, 8 and 7 s), SENTINEL TOWER SC (6 and 10 kVA, 8 and 7 s), SENTRY UM SC (S3M/S3T 10-40 kVA, 7-30 s), MASTER MPS SC (60-160 kVA, 10-20 s) and MASTER HP SC (100-200 kVA, 10-18 s). Input power factor is above 0.99 (above 0.9 for the MPS HC version) and input current distortion is from 7% or less down to 3% or less depending on model. Recharge time is 2-7 minutes.
Notes: backup time is calculated at 70% load for the SENTINEL models and at 100% load for the SENTRY and MASTER models. For example the S3T 30 kVA gives 10 or 20 s, the MASTER MPS 60 kVA 20 s and the 160 kVA 15 s. The systems work with 480-648 V DC supercapacitor modules (BTC), and modular expansion gives more power and runtime. The high working temperature is said to remove any need for cooling or heating systems.
Key points
- Power range: 1-10 kVA in 1:1 models, 10-800 kVA in 3:3 models; online double conversion.
- Autonomy 1-60 s; tables show 7-30 s depending on load condition.
- At least 87% of power interruptions last less than a second (EPRI study).
- Over a million cycles against about 300 for lead; life 5 to 10 times that of lead batteries.
- Recharge time 2-7 min; input PF >0.99; input current distortion from 7% or less to 3% or less.
- SENTINEL PRO SC: 1000 VA/900 W and 3000 VA/2700 W, 8.1 and 17.6 kg.
- SENTRY UM SC: 10, 15, 20 kVA (30/40 kVA in the S3T line), 130-202 kg; 440x840x1320 mm.
- MASTER MPS SC 60-160 kVA and MASTER HP SC 100-200 kVA; supercapacitor cabinet (BTC) separate.
Using it in design
- Consider SuperCaps UPS only in generator-backed sites; verify the 7-30 s autonomy against generator start-up time (for example 10-15 s) and ATS transfer.
- Check at which load (70% or 100%) the autonomy is given and recompute at the design load.
- Reflect the removal of battery room, ventilation and battery monitoring costs in the floor area and TCO calculation.
- Add cabinet sizes and weight (for example 700+540 kg for the MASTER MPS 160 kVA) to the electrical room layout.
- For critical loads that need long autonomy against generator failure, choose a battery UPS or a hybrid solution instead of supercapacitors.
Who should read it
Electrical designers and facility managers looking for short-autonomy UPS in generator-backed data centres, medical and industrial sites.
Document contents
- Highlights and clean-energy rationale
- Sentinel PRO SC
- Sentinel Tower SC
- Sentry UM SC (S3M/S3T)
- Master MPS SC
- Master HP SC
- Technical tables
Publication details
- Authors
- Riello UPS
- Publisher
- Riello UPS
- Year
- Year not stated
- Document number
- DATCAPX0Y25CREN
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document