Rittal's guide to rack power distribution units covers placement, phase and current ratings, connector types and temperature rating. It argues that cheap socket strips are a reliability and fire risk under German electrical rules, and that metered, managed PDUs belong in modern racks.
On this page
Overview
PDUs come single- or three-phase with 16, 32 or 63 A; a 63 A three-phase PDU distributes a little over 43 kW, and nearly 90 kW with two redundant PDUs on separate paths. C14 inlets carry up to 10 A and C20 up to 16 A for large consumers such as blade PSUs. At 27 C inlet, servers exhaust 42-45 C air, so PDUs should be rated for ambient up to 45 C.
Relay design is examined: permanently energised mechanical relays can draw up to 50 W in a fully populated PDU, whereas bistable relays avoid this and keep their state on supply loss. Energy (kWh) is metered to +/-1 % and other values to +/-2 %; the cited PDU MTBF is 80,000 h and CMC III handles up to 32 external sensors or devices.
The power-factor section touches UPS sizing: UPSs are designed for +0.8 inductive PF while blade servers present -0.95 to -0.90 capacitive PF, so UPSs reach their limits sooner than planned. On security, SNMP v1/v2 send passwords in clear text, and SNMPv3 (RFC 3410-3419) with USM should be preferred. The paper rests on German rules (DIN VDE 0100-420) and reflects a manufacturer view.
Key points
- PDUs come single- or three-phase at 16, 32 or 63 A; a 63 A three-phase unit distributes a little over 43 kW, nearly 90 kW with two redundant PDUs.
- C14 inlets carry up to 10 A; C20 up to 16 A for large consumers.
- At 27 C inlet servers exhaust 42-45 C air; PDUs should be rated for 45 C ambient.
- Permanently energised mechanical relays can draw up to 50 W in a full PDU; bistable relays avoid this.
- UPSs are designed for +0.8 inductive PF while blade servers show -0.95 to -0.90 capacitive PF.
- kWh metered to +/-1 %, other values +/-2 %; PDU MTBF 80,000 h; CMC III handles up to 32 sensors/devices.
- SNMP v1/v2 send passwords in clear text; SNMPv3 should be preferred.
Using it in design
- Keep PDU selection criteria for phases, input A, max kW, outlet types, ambient rating, metering accuracy, relay type and management protocol (SNMPv3).
- Warn if a rear-mounted PDU rating is below the design exhaust temperature, and compute per-PDU kW from V x A x phases.
- In UPS sizing allow a (leading) load power-factor input and warn when IT PF is capacitive against the UPS rating.
- Flag SNMP v1/v2-only devices in the security check.
Who should read it
Electrical designers selecting rack PDUs and accounting for UPS power-factor effects, plus network security owners.
Related standards
- DIN VDE 0100-420
- EN 60950-1
- IEC 60320
- RFC 3410-3419 (SNMPv3)
Publication details
- Authors
- Rittal
- Publisher
- Rittal
- Year
- 2014
- Document number
- 5_2236
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Rittal (2014). Whitepaper Rittal PDU international. Rittal. 5_2236. https://www.rittal.com/imf/none/5_2236
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.