White paperFree to read2014

Whitepaper Rittal PDU international

Rittal

Rittal's guide to rack power distribution units covers placement, phase and current ratings, connector types and temperature rating. It argues that cheap socket strips are a reliability and fire risk under German electrical rules, and that metered, managed PDUs belong in modern racks.

On this page

Overview

PDUs come single- or three-phase with 16, 32 or 63 A; a 63 A three-phase PDU distributes a little over 43 kW, and nearly 90 kW with two redundant PDUs on separate paths. C14 inlets carry up to 10 A and C20 up to 16 A for large consumers such as blade PSUs. At 27 C inlet, servers exhaust 42-45 C air, so PDUs should be rated for ambient up to 45 C.

Relay design is examined: permanently energised mechanical relays can draw up to 50 W in a fully populated PDU, whereas bistable relays avoid this and keep their state on supply loss. Energy (kWh) is metered to +/-1 % and other values to +/-2 %; the cited PDU MTBF is 80,000 h and CMC III handles up to 32 external sensors or devices.

The power-factor section touches UPS sizing: UPSs are designed for +0.8 inductive PF while blade servers present -0.95 to -0.90 capacitive PF, so UPSs reach their limits sooner than planned. On security, SNMP v1/v2 send passwords in clear text, and SNMPv3 (RFC 3410-3419) with USM should be preferred. The paper rests on German rules (DIN VDE 0100-420) and reflects a manufacturer view.

Key points

  1. PDUs come single- or three-phase at 16, 32 or 63 A; a 63 A three-phase unit distributes a little over 43 kW, nearly 90 kW with two redundant PDUs.
  2. C14 inlets carry up to 10 A; C20 up to 16 A for large consumers.
  3. At 27 C inlet servers exhaust 42-45 C air; PDUs should be rated for 45 C ambient.
  4. Permanently energised mechanical relays can draw up to 50 W in a full PDU; bistable relays avoid this.
  5. UPSs are designed for +0.8 inductive PF while blade servers show -0.95 to -0.90 capacitive PF.
  6. kWh metered to +/-1 %, other values +/-2 %; PDU MTBF 80,000 h; CMC III handles up to 32 sensors/devices.
  7. SNMP v1/v2 send passwords in clear text; SNMPv3 should be preferred.

Using it in design

  • Keep PDU selection criteria for phases, input A, max kW, outlet types, ambient rating, metering accuracy, relay type and management protocol (SNMPv3).
  • Warn if a rear-mounted PDU rating is below the design exhaust temperature, and compute per-PDU kW from V x A x phases.
  • In UPS sizing allow a (leading) load power-factor input and warn when IT PF is capacitive against the UPS rating.
  • Flag SNMP v1/v2-only devices in the security check.

Who should read it

Electrical designers selecting rack PDUs and accounting for UPS power-factor effects, plus network security owners.

Related standards

  • DIN VDE 0100-420
  • EN 60950-1
  • IEC 60320
  • RFC 3410-3419 (SNMPv3)

Publication details

Authors
Rittal
Publisher
Rittal
Year
2014
Document number
5_2236
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Rittal (2014). Whitepaper Rittal PDU international. Rittal. 5_2236. https://www.rittal.com/imf/none/5_2236

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.