A 5 August 2024 Certios report for RVO (PEB23012) shows EEE cutting switch power by 10% to 35% in lab tests, with no loss of bandwidth, while it is switched off at every operator checked.

On this page

Overview

The report, written by Dr. D.H. Harryvan (Certios B.V.) for the Netherlands Enterprise Agency (RVO), examines how much energy IEEE 802.3az Energy Efficient Ethernet (EEE) can save in data centres, especially in network equipment. The derived aim is to judge whether EEE use should enter the list of recognised measures (EML) under the Dutch Environment Regulation. A measure qualifies if it causes no operational disruption, saves energy and pays back within 5 years. As background, per CBS data electricity delivered to data centres rose from 1,647 GWh (1.3%) in 2017 to 3,730 GWh (3.4%) in 2021.

EEE lets a link enter a low power idle (LPI) state instead of continuously sending idle packets when no data flows. The states are active, sleep, quiet and wake; in the quiet state about 90% of the network electronics' energy is saved. The report stresses two observations: the first packet incurs at most 22 ms extra delay on the adapter shown, and EEE works only if enabled on both ends of the link, otherwise the link stays active. Savings therefore arise not only in switches but also in connected servers and computers.

Lab measurements at Aliter Networks cover several scenarios. In a minimal star network a 24-port switch saves 11% and an 8-port switch 6%. With no traffic, a switch with one cable connected saves 10% and a fully cabled switch 35% (15 W of 42.5 W on a WS-C2960XR-48TD-I). Under heavy load savings fall, in line with theory. With EEE enabled the switches lose no bandwidth, and all ports still deliver the manufacturer's rated bandwidth.

The practice finding is striking: all equipment checked supports EEE, yet it is disabled at all operators involved, because most devices ship with it off and network specialists lacked knowledge of it. The report uses an estimate of 370 million kWh/year for network energy in Dutch data centres. Assuming 40% idle time and 10% saving during idle, about 4% of network energy (roughly 15 million kWh) could be saved; the report states the potential as above 10 million kWh. The recommendation is not to add an 'enable EEE on all devices' measure on this report alone, but to persuade manufacturers (Cisco and HPE/Aruba hold about 90% of the market) to ship with EEE enabled by default.

Key points

  1. Report prepared by Certios for RVO; reference PEB23012, version 1.0 delivered 5 August 2024.
  2. Electricity delivered to data centres: 1,647 GWh (1.3%) in 2017, 3,730 GWh (3.4%) in 2021.
  3. EML criteria: no operational disruption, energy saving and payback within 5 years; EEE meets all three.
  4. In the LPI state about 90% of network electronics energy is saved; the first packet incurs at most 22 ms extra delay.
  5. EEE works only if enabled at both ends of the link and also saves energy in connected servers and computers.
  6. Lab: 24-port switch 11%, 8-port switch 6%; no traffic, one cable 10%, fully cabled 35%; less under heavy load.
  7. No bandwidth is lost with EEE enabled.
  8. EEE is disabled at every operator checked, because the default is off and knowledge is lacking.
  9. Dutch data-centre network energy is estimated at 370 million kWh/year; with 40% idle and 10% saving, about 4% (roughly 15 million kWh); the report states the potential as above 10 million kWh.

Using it in design

  • Add IEEE 802.3az (EEE) support to switch and server NIC specifications and put an 'enabled by default' setting on the commissioning list.
  • Because EEE must be active at both ends, plan server NIC and operating-system settings together with switch settings.
  • Assess port by port whether the roughly 22 ms extra delay on the first packet is acceptable for latency-sensitive workloads (for example AI, HPC, financial trading).
  • In energy audits, treat EEE as a measure with payback under 5 years where jurisdictions such as the Netherlands impose an energy-saving duty.
  • Pilot EEE on access switches with many idle ports and verify with power measurement.

Who should read it

Data-centre network designers, engineers responsible for energy efficiency and regulatory compliance, and policy makers.

Document contents

  1. Summary
  2. Background
  3. Energy Efficient Ethernet: laboratory research (minimal star network, point to point multi-port without data traffic, tests with network traffic)
  4. Relation to practice
  5. Conclusion and recommendations

Related standards

  • IEEE 802.3az

Publication details

Authors
D. H. Harryvan
Publisher
Netherlands Enterprise Agency (RVO)
Year
2024
Document number
PEB23012
Document language
Dutch
Source type
Government / public
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

RVO landing https://www.rvo.nl/onderwerpen/energie-besparen-de-industrie/datacenters opened via TinyFish and PDF downloaded/extracted. PDF marked classification open and copyright RVO August 2024; classification is not a reuse licence. No commercial redistribution grant verified.

Citation

D. H. Harryvan (2024). IEEE 802.3az Energie Efficiënt Ethernet. Netherlands Enterprise Agency (RVO). PEB23012. https://www.rvo.nl/sites/default/files/2024-08/Energie%20Effici%C3%ABnt%20Ethernet%20EEE.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.