Technical guideFree to read2022

Near term Photonic applications in Datacom and Telecom with impact on reducing energy demand

Netherlands Enterprise Agency (RVO)

An RVO report of October 2022 estimates how photonic transceivers, switches and processors affect data-centre energy, calculating 0.32 to 0.64 TWh/year of savings against the Dutch data centres' 3.2 TWh consumption in 2020.

On this page

Overview

The report was commissioned by the Ministry of Economic Affairs and Climate Policy and states that the high energy consumption of data centres is increasingly a bottleneck, with one solution perspective being greater use of photonics for data transmission. For network cables interconnecting data centres, optical is already commonplace. The next big step is to use photonic integrated chips instead of electronic chips. The foreword says fibre networks already reach deep into data centres, but photonics inside the servers is still in its infancy, and the photonic chips that should make the difference are still too expensive and unproven for large-scale adoption.

The report lists products expected to become commercially available at scale in the near term: photonic transceivers (from 2020; about 50% saving potential in data-transport power), photonic switches (from 2020; about 1 MWh per switch per year), and photonic AI/ML accelerators and processors (from 2024-2025; about 20% of related workload energy). Supplier tables for telecom (over 10 km) and datacom (500 m to 2 km, intra-data-centre and campus) list speeds from 10G to 800G, with 1600G announced. In the Netherlands KPN, VodafoneZiggo and EuroFiber have deployed such products in long-haul, metro and DCI networks; US hyperscalers are starting co-packaged optics (CPO) transceivers in campus networks, and no Dutch example was found.

The savings calculations are indicative. Per CBS, Dutch data centres used 3.2 TWh in 2020 (2.8% of national electricity). Based on US averages, about a third of consumption goes to the CPU and about 20% to data transport. If energy per bit falls from 8 pJ to 3 pJ with co-packaged photonic processors, a saving of about 20% of annual electricity use results, around 0.64 TWh/year; with coherent DWDM transceivers 50% x 20% x 3.2 TWh = 0.32 TWh/year; and for a 32-port 400G switch 5 pJ x 32 x 400G = 0.064 J/s, which at 50% on-time is about 1 MWh/year. The report also says best practices in operations and planning can cut waste by up to 35% and typical savings are 15% to 35%.

It concludes that technology development is faster than anticipated, with most progress in optical transceivers, while delay in adoption of photonic switching and processors is expected because of the need for proven technology, high volumes and reliability. Photonics will not lower absolute energy consumption but let more traffic be processed with the same energy, and initially affects only useful power consumption. The report is from 2022; its timelines are its 2022 outlook and should not be presented as current product availability.

Key points

  1. Dutch data-centre consumption in 2020 was 3.2 TWh, 2.8% of national electricity (CBS).
  2. Photonic transceivers (from 2020): about 50% saving potential in data-transport power; products from 10G to 800G from many vendors, 1600G announced.
  3. Photonic switches (from 2020): about 1 MWh per switch per year; co-packaged optics cuts energy from 8 pJ/bit to 3 pJ/bit.
  4. Photonic AI accelerators and processors (from 2024-2025): about 20% saving potential of related workload energy.
  5. Indicative savings: about 0.64 TWh/year for photonic processors, 0.32 TWh/year for coherent DWDM transceivers.
  6. A tenfold reduction in power consumption is expected over time; long-haul networks achieved a similar result in the past decade.
  7. Savings do not lower absolute consumption; they appear relatively, as flat total energy despite traffic growth.
  8. Best practices (retiring systems, power management, virtualisation, right-sizing and others) typically give 15% to 35% savings.
  9. Photonic chips are still too expensive and unproven for large-scale adoption; delay in adoption is expected.

Using it in design

  • In data-centre network design compare 400G and 800G optical transceiver options and co-packaged optics (CPO) switches on power (pJ/bit) and maturity.
  • Treat the photonic switch and processor expectations as 2022 forecasts and verify design decisions against current product availability and vendor data.
  • In the energy-saving plan prioritise best practices (activate power management, retire unused systems, virtualise, right-size capacity) independently of photonics expectations.
  • Track energy consumption and cost as a separate item; add measurement that shows the effect of configuration changes quickly.
  • In the equipment-refresh plan consider the three-year upgrade suggestion and a modular, energy-efficient growth design.

Who should read it

Planners shaping data-centre network and energy strategy, policy makers and architects evaluating photonic technology.

Document contents

  1. Foreword
  2. Summary
  3. Introduction
  4. Photonic technologies and applications: optical networking in transport, access and indoor networks, all-optical data-centre interconnect, radio over fibre, power over fibre, free-space optics, optical network timing, co-packaged optics
  5. Power consumption and savings estimates
  6. Fibre infrastructure and operators
  7. Energy-efficiency best practices
  8. Conclusions and recommendations

Publication details

Authors
Netherlands Enterprise Agency (RVO)
Publisher
Netherlands Enterprise Agency (RVO)
Year
2022
Document language
English
Source type
Government / public
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

RVO energy-saving landing opened and linked PDF downloaded/extracted. Colophon copyright Netherlands Enterprise Agency October 2022; no explicit commercial reuse licence found. Third-party figures are credited separately.

Citation

Netherlands Enterprise Agency (RVO) (2022). Near term Photonic applications in Datacom and Telecom with impact on reducing energy demand. Netherlands Enterprise Agency (RVO). https://www.rvo.nl/sites/default/files/2023-02/Near-term-Photonic-applications-in-datacom-and-telecom.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.