White paperFree to read2013

Implementing Hot and Cold Air Containment in Existing Data Centers

Schneider Electric · Paul Lin, Victor Avelar et al.

Schneider Electric WP 153 is a retrofit guide for adding air containment to an operating data hall: assess constraints, review options, then select hardware.

On this page

Overview

The paper compares six methods: cold aisle containment, row-cooled cold aisle, ducted rack, ducted hot aisle, row-cooled hot aisle and rack air containment. Each has recommended and poor-fit conditions and an indicative payback. The decisive constraints are aisle arrangement, the free height above racks for a return plenum, raised-floor depth, columns, overhead cabling and the existing air distribution type.

The starting point is waste. Uncontained raised-floor rooms typically keep average rack density below 6 kW to limit hot-air recirculation, and more than 50% of supplied cold air can bypass back to the cooling units. Containment raises cooling-unit deltaT, which can increase cooling capacity by about 20% or more. Without containment, active (fan-assisted) floor tiles can support up to 12 kW per rack and rack-bottom air distribution units up to 4 kW per rack.

The decision threshold is the gap between rack top and ceiling. Below 508 mm (20 in), use cold aisle containment (with raised floor) or rack air containment; above 508 mm with a drop-ceiling return, ducted hot aisle or ducted racks become options. A ducted rack is recommended for scattered high-density racks above 6 kW with front-to-back airflow, with payback from a few months to three years, similar to ducted HACS. Row-cooled HACS/CACS and RACS pay back in about 6 months to 2 years when row coolers already exist, and several years if they must be purchased.

Hot and cold containment types should never be mixed in one room because the result is lower efficiency than either alone. Recurring side effects are lighting, fire detection and suppression, and occupant heat exposure: containment overhead panels can transmit as much as 90% of light, and some systems drop ceiling panels automatically on smoke or heat detection so suppression agent can reach the aisle.

Key points

  1. Uncontained raised-floor rooms typically keep average density below 6 kW/rack; more than 50% of supplied cold air can bypass back to the cooling units.
  2. Containment raises cooling-unit deltaT and can add about 20% or more cooling capacity.
  3. Rack-top-to-ceiling gap under 508 mm (20 in): cold aisle containment (with raised floor) or rack air containment; above it with a drop-ceiling return: ducted hot aisle or ducted racks.
  4. Active floor tiles support up to 12 kW per rack without containment; rack-bottom air distribution units up to 4 kW.
  5. Ducted rack suits scattered racks above 6 kW with front-to-back airflow; payback a few months to three years, like ducted HACS.
  6. Row-cooled HACS/CACS and RACS pay back in about 6 months to 2 years with existing row coolers, several years if purchased.
  7. Never mix hot and cold containment in one room; efficiency falls below either alone.
  8. Containment overhead panels can transmit as much as 90% of light; some drop automatically on smoke or heat detection.

Using it in design

  • For retrofit selection among the six containment types, record aisle arrangement, raised-floor depth, ceiling return, rack-top clearance, columns, overhead cabling and existing coolers.
  • Disable ducted HACS and ducted rack options when clearance is below 508 mm; raise an error if a room model contains both hot- and cold-aisle containment objects.
  • Warn for CACS with perimeter storage or tape or permanently staffed desks (the room becomes the hot return); for any aisle containment add AHJ fire detection/suppression and lighting checklist items, and for ducted racks require a smoke detector in the duct.
  • Default to a warning above 6 kW/rack average for uncontained raised floor and cap active tiles at 12 kW/rack.

Who should read it

Operations and facilities engineers planning to retrofit containment into a live data hall.

Related standards

  • ASHRAE TC 9.9 Thermal Guidelines
  • NFPA 75
  • NFPA 76
  • ISO 7243

Publication details

Authors
Paul Lin; Victor Avelar; John Niemann
Publisher
Schneider Electric
Year
2013
Document number
WP 153
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Paul Lin; Victor Avelar; John Niemann (2013). Implementing Hot and Cold Air Containment in Existing Data Centers. Schneider Electric. WP 153. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_VAVR-8K6P9G_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.